Plan Review Details - Permit 20070718
Plan Review Stops For Permit 20070718
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 14:39 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 14:01 Rev Time 0.00
Received By shill Date 2020-08-21 Time 13:54 Sent To  
Notes
2020-08-21 14:03:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, THE ENGINEERING FOR THE GENERATOR
 REQUIRES MINIMUM WEIGHT OF 526 POUNDS, PAGE 6 OF THE
 GENERATOR SPECS STATE THAT THE GENERATOR WEIGHS 410#.
 ALSO THE DIMENSIONS OF THE PROPOSED GENERATOR DO NOT
 APPEAR TO PROPERLY CORRELATE WITH THE GENERATOR SLAB
 ENGINEERING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cthroop Date 2020-07-31 Time 13:19 Rev Time 0.00
Received By cthroop Date 2020-07-31 Time 11:54 Sent To  
Notes
2020-07-31 13:21:29PLAN REVIEW GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE WIND DESIGN LOADS FOR THE GENERATOR PER FBC
 107.3.5.3 AND R301.2 AS REQUIRED FOR THE GENERATOR PAD
 ENGINEERING.
 2) STRUCTURAL DETAIL OF PAD AND DESIGN LOADS SHALL BE
 SIGNED BY THE DESIGNER.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 14:39 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 12:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-08-26 Cont ID  
Sent By cthroop Date 2020-08-26 Time 10:24 Rev Time 0.00
Received By cthroop Date 2020-08-26 Time 09:22 Sent To  
Notes
2020-08-26 10:30:34PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED.
 PROVIDE DOCUMENTATION THAT THE PROPOSED 22KW GENERATOR
 IS CAPABLE OF SUPPLYING THE DEMAN LOADS OF THE
 RESIDENCE.
  
 NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED
 GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED?
 IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE
 RECOMMENDATION?
  
 1) RISER
  
 1A) INCLUDE EXISTING SERVICE. INDICATE IF THE SERVICE
 AND MDC ARE EXISTING OR NEW.
 1B) INCLUDE GROUNDING ELECTRODE SYSTEM. IF EXISTING
 SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM.
 1C) INCLUDE INTERSYSTEM BONDING CONNECTION. IF EXISTING
 SERVICE THIS IS NOT REQUIRED ON RISER DIAGRAHM.
  
 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF
 COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE
 SIZE AND TYPE OF CONDUIT.
  
 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cthroop Date 2020-07-31 Time 13:23 Rev Time 0.00
Received By cthroop Date 2020-07-31 Time 11:54 Sent To  
Notes
2020-07-31 13:52:53PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: LOAD CALC'S RECOMMEND A 30 KW GENERATOR. PROPOSED
 GENERATOR IS ONLY 22KW. IS THIS GENERATOR UNDERSIZED?
 IS OWNER AWARE OF THESE CALCULATIONS AND GENERATOR SIZE
 RECOMMENDATION?
  
 1) RISER
  
 1A) INCLUDE EXISTING SERVICE.
 1B) INCLUDE GROUNDING ELECTRODE SYSTEM.
 1C) INCLUDE INTERSYSTEM BONDING CONNECTION.
  
 2) PROVIDE SPECIFICATIONS FOR COMPOSITE CABLE. IF
 COMPOSITE CABLE WILL BE ENCASED IN CONDUIT, PROVIDE
 SIZE AND TYPE OF CONDUIT.
  
 3) PROVIDE SPECIFICATIONS FOR GENERATOR CONTROLLERS.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-07-31 Cont ID  
Sent By cthroop Date 2020-07-31 Time 11:54 Rev Time 0.00
Received By cthroop Date 2020-07-31 Time 11:53 Sent To  
Notes
2020-07-31 11:55:02A SEPERATE GAS PERMIT IS REQUIRED. CT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 14:43 Rev Time 0.00
Received By cthroop Date 2020-09-10 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-02 Cont ID  
Sent By lmarchan Date 2020-09-02 Time 08:59 Rev Time 0.00
Received By lmarchan Date 2020-08-17 Time 13:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-13 Cont ID  
Sent By lmarchan Date 2020-08-13 Time 09:37 Rev Time 0.00
Received By lmarchan Date 2020-07-16 Time 16:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-09-16 Cont ID  
Sent By shill Date 2020-09-16 Time 15:22 Rev Time 0.00
Received By shill Date 2020-09-16 Time 15:22 Sent To  
Notes
2020-09-16 15:23:27PROVISO: CONTRACTOR TO SUBMIT ORIGINAL ENGINEERING
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-09-11 Cont ID  
Sent By cthroop Date 2020-09-11 Time 14:39 Rev Time 0.00
Received By cthroop Date 2020-09-11 Time 12:34 Sent To  
Notes
2020-09-11 14:43:50PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: GENERATOR PAD SPEC'S
  
 DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT
 CONSIDERED A DIGITAL SIGNATURE.
  
 EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF
 (OR MAIL) ONE PAPER ORIGINAL:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 14:03 Rev Time 0.00
Received By shill Date 2020-08-21 Time 14:03 Sent To  
Notes
2020-08-21 14:04:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A WET SIGNATURE IS NOT CONSIDERED
 A DIGITAL SIGNATURE.
  
 EITHER UPLOAD A DIGITALLY SIGNED DOCUMENT OR DROP OFF
 (OR MAIL) ONE PAPER ORIGINAL:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cthroop Date 2020-07-31 Time 13:22 Rev Time 0.00
Received By cthroop Date 2020-07-31 Time 11:53 Sent To  
Notes
2020-07-31 13:23:52PLAN REVIEW GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 NOTE: YOU MAY PROVIDE A PAPER PLAN WITH WET SIGNATURE
 AND SEAL PRIOR TO PERMIT.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-01 Cont ID  
Sent By kalexand Date 2020-09-01 Time 22:25 Rev Time 0.00
Received By kalexand Date 2020-09-01 Time 22:24 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-13 Cont ID  
Sent By kalexand Date 2020-08-13 Time 08:55 Rev Time 0.00
Received By kalexand Date 2020-08-13 Time 08:55 Sent To I
Notes
2020-08-13 08:58:07ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/12/20
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK. REAR SETBACK IS
 11 FT. GENERATOR MAY BE PLACED A MIN OF 7' FT. FROM
 REAR PROPERTY LINE.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved