Plan Review Details - Permit 20070654
| Plan Review Stops For Permit 20070654 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2020-08-13 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2020-08-13 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-06 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-08-06 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2020-08-06 10:22:35 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD INFORMATION SUBMITTED DOES NOT | | | MEET THE REQUIREMENTS FOR PREFABRICATED SLABS. | | | PREFABRICATED GENERATOR PADS ARE REQUIRED TO HAVE | | | PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING FROM A | | | FLORIDA LICENSED ENGINEER. FBC 107.3.4 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2020-08-10 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-08-10 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-08-10 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2020-08-10 19:34:30 | PLAN RED-LINED. MUST MAINTAIN SEPARATION BETWEEN | | | SERVICE AND FEEDER CONDUCTOR IN GUTTER PER NEC 230.7 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2020-08-09 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-08-09 |
Time |
23:07 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-08-09 |
Time |
22:13 |
Sent To |
|
|
| Notes |
| 2020-08-09 23:07:51 | SEE PREVIOUS COMMENTS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-08-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2020-08-05 |
Time |
21:30 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2020-08-05 |
Time |
20:59 |
Sent To |
|
|
| Notes |
| 2020-08-05 21:30:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. RISER DIAGRAM IS STILL NOT CODE COMPLIANT. "EXISTING | | | GUTTER" SHOWS UNPROTECTED SERVICE ENTRANCE CONDUCTOR | | | WITH PROTECTED FEEDER CONDUCTORS IN SAME GUTTER. NEC | | | 230.7 | | | | | | 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE | | | VALUE FOR INSTALLATION WITH SIGNED CONTRACT FROM OWNER | | | AND CONTRACTOR OR VALUE WILL BE SET BY BUILDING | | | OFFICIAL | | | | | | CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT | | | VALUATIONS. IF, IN THE OPINION OF THE BUILDING | | | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR | | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE | | | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR | | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-07-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-07-16 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-07-16 |
Time |
09:56 |
Sent To |
G |
|
| Notes |
| 2020-07-16 10:02:02 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE | | | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND | | | BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S). | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, | | | 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC | | | 107.2.1 | | | 2. 230.7 RISER IS NOT CODE COMPLIANT. | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6742 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2020-08-14 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-08-14 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-08-14 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-08-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-08-12 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-08-12 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2020-08-12 14:39:09 | 1) THE SUBMITTED GAS DRAWING SHOWS A TOTAL BTU LOAD OF | | | 517,00 BTU'S. CITY RECORDS SHOW A LARGER EXISTING BTU | | | LOAD ON THE SYSTEM. LIST THE BTU LOAD OF EACH APPLIANCE | | | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 | | | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 | | | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). THE TOTAL | | | BTU LOAD ON THIS SYSTEM WITH THE GENERATOR IS 1,197, 00 | | | BTU'S. 2ND REQUEST. | | | 2) SHOW THE SIZE OF THE METALLIC PIPE AT THE OUTLET | | | (CONSUMER'S SIDE) OF THE GAS METER. THE SIZE OF THIS | | | PIPE SHALL COMPLY WITH FBC-GAS TABLE 402.4 (5) FOR THE | | | DISTANCE FROM THE GAS METER TO THE MOST REMOTE | | | REGULATOR ON THE SYSTEM. CITY RECORDS SHOW THIS | | | DISTANCE AS 100 FEET. THIS DISTANCE AND BTU LOAD WILL | | | DETERMINE THE PIPE SIZE AT THE OUTLET AT THE GAS | | | METER.FBC-GAS SEC.402.1, 402.2. | | | 3) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | | THE REGULATOR. ONLY ONE SHEET OF THE SPECIFICATIONS HAS | | | BEEN SUBMITTED. FBC-FUEL GAS SEC. 410.1, FBC RES. SEC. | | | G2421.1. 2ND REQUEST. | | | 4) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THIS | | | SUBMITTAL. REMOVE OR VOID THE ONE THAT IS NOT | | | APPLICABLE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-07-22 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-07-22 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2020-08-12 12:12:24 | 1.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, ( MP | | | REGULATOR ) TO THE GENERATOR.PER THE 2017 FBC-FUEL GAS | | | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, | | | G2413.4.2. | | | 2) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU | | | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE | | | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. FGC SECS. 401.4, | | | 401.8, 402.1, 402.2, 402.3 OR FBCR SECS.G2412.4, | | | G2412.8, G2413.1, G2413.2, G2413.3. | | | 3) INDICATE ON THE GAS DRAWING HOW THE EXISTING SYSTEM | | | WILL BE RETROFITTED TO HANDLE THE 2 PSI SYSTEM. | | | 4) SUBMIT MANUFACTURER?S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC | | | SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | 5) THE GALVANIZED PIPING SHALL BE LOCATE A MINIMUM OF 3 | | | 1/2/ INCHES ABOVE GRADE. FBC-FUEL GAS SEC. 404.9. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-08-03 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-08-03 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-08-03 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-06 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-15 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2020-07-28 11:12:31 | 07/28/2020 CONTRACTOR RESUB ELECTRICAL RISER DIAGRAM ON | | | 07/22/2020 WITHOUT FINISHING THE 1ST REVIEW CYCLE. | | | UPLOADED THE ELECTRICAL RISER TO PROJECTDOX TO | | | FACILITATE THE REVIEW. JG. | | | | | 2020-07-15 12:09:37 | ROUTED TO PHIL |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2020-08-13 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2020-08-13 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2020-08-13 16:02:04 | PASSED WITH ORIGINAL TO COME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-06 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-08-06 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2020-08-06 10:26:56 | IF ENGINEERED GENERATOR PAD DRAWINGS ARE SUBMITTED, | | | THEY WILL NEED TO BE SIGNED AND SEALED IN ACCORDANCE | | | WITH FS 471 AND FAC 61G15. ELECTRONICALLY SUBMITTED | | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL | | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | PAPER DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-08-17 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-08-17 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-08-17 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-08-03 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2020-08-03 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2020-08-03 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2020-08-03 16:46:39 | NEED SITE PLAN WITH DIMENSIONS SHOWING LOCATION OF | | | PROPOSED GENERATOR AND DISTANCE TO PROPERTY LINES. |
|
|
|