| 2020-08-10 17:03:57 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20070540 |
| | ADD: 515 N. FLAGLER DR. |
| | CONT: SOUTHERN AWNING |
| | TEL: 561-586-0464 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: MON. AUGUST 10TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED SITE PLAN IS A COPY OF AN ISSUED |
| | PERMIT. ARCHITECTS ARE INCLUDED IN COPYRIGHT LAWS. ALSO |
| | PAPER PLAN NOT AN DIGITAL ORIGINAL. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A |
| | SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE |
| | OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON |
| | DIGITALLY SIGNED AND SEALED ENGINEERING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) THE PERMIT APPLICATION INDICATES IN THE SCOPE OF |
| | WORK THIS IS A NEW CANOPY FRAME AND COVERING. THERE |
| | WERE NO STRUCTURAL PLANS UPLOADED. |
| | |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | MISSING CODE DATA: |
| | SET BACK / SEPARATION (ASSUMED PROPERTY LINES) |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | DESIGN LOADS |
| | WIND REQUIREMENTS |
| | |
| | 2A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 2. RISK CATEGORY. |
| | |
| | 3. WIND EXPOSURE. |
| | APPLICABLE WIND DIRECTION IF MORE THAN ONE WIND |
| | EXPOSURE IS UTILIZED. TABLE 1609.7.2. HEIGHT AND |
| | EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 2B) RIGID AWNING. PERMANENT OR NON-REMOVABLE FABRIC. |
| | FBC-B 3105.4.2.2. THE WIND DESIGN LOADS FOR ANY FABRIC |
| | OR MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT |
| | OR NON-REMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON |
| | THE FOLLOWING CRITERIA: |
| | 1) MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| | 16 USING FIGURE 1609.3(3) 150 VULT, CATEGORY 1 |
| | BUILDINGS. |
| | 2) EXPOSURES B, C, OR D AS DEFINED IN CHAPTER 16. |
| | 3) IF POST OR VERTICAL PIPE SHOW ANCHORING OF THE BASE, |
| | TO RESIST THE MOMENT OF OVER TURNING. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| 2020-08-10 16:46:12 | IN REVIEW. JW 8/10/2020 |