| | SHUTTERS |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1. COMPLETE THE FORM PROVIDED AT THE FRONT COUNTER |
| | "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES OR ASSEMBLIES" FORM OR PROVIDE ALL INFORMATION |
| | REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET) |
| | |
| | 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| | NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE |
| | DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON, |
| | BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED |
| | THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). |
| | |
| | 3. PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW |
| | TO THE EDGE OF THE BUILDING - FOR THE WINDOWS NEXT TO |
| | THE CORNERS - NEEDED TO DETERMINE WIND ZONE 4 OR 5. |
| | |
| | 4. JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION |
| | APPEARS TO BE TOO LOW. PLEASE REVISE BUILDING PERMIT |
| | APPLICATION (SHOW THE JOB VALUE TO INCLUDE LABOR AND |
| | MATERIAL AS IF A CONTRACTOR IS GOING TO INSTALL THE |
| | SHUTTERS). FBC 109.3 |
| | |
| | 5. PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL (2 PAGES |
| | HAVE BEEN PROVIDED) - NEED FRONT PAGES OF THE FLORIDA |
| | PRODUCT APPROVAL AND THE REST OF THE INSTALLATION |
| | INSTRUCTIONS. |
| | HTTPS://WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| | |
| | FORMS CAN BE PROVIDED BY EMAILING [email protected] AND ASKING |
| | FOR "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| | DEVICES OR ASSEMBLIES? FORM. |
| | |