| 2020-08-08 10:37:23 | PLAN REVIEW - BUILDING ACCESSORY STRUCTURES |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE DESIGNED |
| | PER FBC RES CHPT 3 SECTION R301 OR ASCE 7 |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | 1. PROVIDE A SITE PLAN.... |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | 2. PROVIDE THE FOLLOWING PLANS |
| | |
| | 2A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON |
| | GRADE/REINFORCING/TIE DOWNS |
| | 2B) PROVIDE BUILDING PLANS WITH REQUIRED DIMENSIONS |
| | 2C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION |
| | CONNECTION DETAIL |
| | 2D) PROVIDE A WALL PLAN WITH WALL TO FLOOR CONNECTION |
| | DETAIL |
| | 2E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL |
| | CONNECTION DETAIL |
| | 2F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH |
| | OPENINGS AND DESIGN WIND LOADS IF APPLICABLE. |
| | 2G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS, |
| | DOORS AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2 BELOW |
| | |
| | R301.2.1.2 PROTECTION OF OPENINGS. |
| | STRUTURES THAT ARE NOT DESIGNED FOR HUMAN HABITATION |
| | AND THAT HAVE A FLOOR AREA OF 720 SQUARE FEET (67 M2) |
| | OR LESS ARE NOT REQUIRED TO COMPLY WITH THE MANDATORY |
| | WIND-BORNE DEBRIS IMPACT STANDARD OF THIS CODE |
| | |
| | 3. PROVIDE PRODUCT APPROVALS FOR WINDOWS DOORS ROOFING |
| | AND TIE DOWN ANCHORS |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW, DOOR AND TIE |
| | DOWN SUBMITTALS. |
| | |
| | 4. DESINER SHALL PRINT THEIR NAME AND SIGN EACH PLAN. |
| | SEE DIGITAL SIGNATURE REVIEW COMMENTS |
| | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| | SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT. |
| | 481, F.S. & 61G1. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |