Plan Review Details - Permit 20070426
Plan Review Stops For Permit 20070426
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-28 Cont ID  
Sent By rmcdouga Date 2020-07-28 Time 12:12 Rev Time 0.00
Received By rmcdouga Date 2020-07-28 Time 11:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcdouga Date 2020-07-15 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2020-07-15 Time 15:51 Sent To  
Notes
2020-07-15 16:16:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS FROM THE ENGINEER DO NOT
 SPECIFY THE SYSTEM TYPE OR THE PAGE NUMBER FROM THE NOA
 TO INDICATE WHICH TESTED ASSEMBLY HE BASED HIS
 CALCULATIONS ON. I DID NOT FIND ONE WITH FASTENER
 SPACINGS OF 4"O.C. AT THE LAP AND THREE ROWS 8"O.C. IN
 THE FILED. FBC 107.2.1
  
 2) RAS 117 SECTION 8.1 STATES THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4"O.C.. THEREFORE,
 THE 3" O.C. IN THE ENGINEER'S CALCULATIONS CAN NOT BE
 USED. ADDITIONAL ROWS OF FASTENERS WILL BE REQUIRED.
 SUBMIT CORRECTED CALCULATIONS.
  
 3) CIRCLE OR HI-LIGHT THE SYSTEM, FASTENING OPTION AND
 DESIGN PRESSURE FOR THE PROPOSED ROOF COVERING ASSEMBLY
 ON THE PRODUCT APPROVAL. FBC 107

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-28 Cont ID  
Sent By rmcdouga Date 2020-07-28 Time 12:13 Rev Time 0.00
Received By rmcdouga Date 2020-07-21 Time 16:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-15 Cont ID  
Sent By rmcdouga Date 2020-07-15 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2020-07-10 Time 09:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-28 Cont ID  
Sent By rmcdouga Date 2020-07-28 Time 12:13 Rev Time 0.00
Received By rmcdouga Date 2020-07-28 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-15 Cont ID  
Sent By rmcdouga Date 2020-07-15 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2020-07-15 Time 15:45 Sent To  
Notes
2020-07-15 15:50:58ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15