Plan Review Details - Permit 20070419
Plan Review Stops For Permit 20070419
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-09-08 Cont ID  
Sent By ccole Date 2020-09-08 Time 17:22 Rev Time 0.00
Received By ccole Date 2020-09-08 Time 07:33 Sent To  
Notes
2020-09-08 17:22:57 
 2ND REVIEW FBC-2017 RES.
 PERMIT- 20070419
 9/8/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE
 MARKED AS PASSED OR FAILED. ADDITIONAL COMMENTS IN
 CAPITOL LETTERS WILL BE ADDED TO FAILED COMMENTS.
  
 1) GAS ISOMETRIC:
  
 A) FAILED. PLEASE IDENTIFY THE REGULATOR AS EITHER NEW
 OR EXISTING. A SPEC SHEET FOR AN ITRON B42 REGULATOR
 HAS BEEN SUBMITTED, HOWEVER WHICH MODEL AND WHERE IT
 WILL BE INSTALLED NEEDS TO BE SHOWN ON THE DRAWING-
 SECTIONS G2421.1 & G2421.2 FBC RES. THE ITRON B42 HAS
 MANY DIFFERENT MODELS AND SIZES. PLEASE INDICATE THE
 MODEL NUMBER ON THE DRAWING AND SUBMIT SPECS FOR THAT
 MODEL INDICATING GAS PRESSURE RANGES AND ORIFICE SIZE.
 PLEASE COMPLY.
  
 B) FAILED. SHOW THE TOTAL LENGTH OF THE INTERIOR PIPING
 RUN FROM THE METER TO THE MOST REMOTE OUTLET. INDICATE
 THE BTUH LOAD OF EACH APPLIANCE TO CLARIFY HOW THE
 TOTAL 180,000 BTUH LOAD WAS DETERMINED- SECTIONS
 G2413.2, G2413.3, G2413.4.1, G2413.4.2. BECAUSE THE
 MAIN GAS PIPE FROM THE METER IS SUPPLYING THE NEW BBQ
 AND THE EXISTING SYSTEM A COMPLETE GAS PIPING REVIEW IS
 REQUIRED IN ORDER TO ENSURE A SAFE OPERATING SYSTEM FOR
 THE RESIDENCE- SEE SECTION G2412.4 FBC RES. PLEASE NOTE
 I WAS NOT ABLE TO LOCATE A PERMIT FOR THE EXISTING GAS
 APPLIANCES. IN ORDER TO ISSUE THE PERMIT FOR THE BBQ,
 ANY UNPERMITTED GAS PIPING AND APPLIANCE INSTALLATIONS
 MUST BE LEGALLY PERMITTED AND INSPECTED- SECTION 105
 WPB. PROVIDE A COMPLETE ISOMETRIC DRAWING THAT INCLUDES
 BRANCH LINES TO ALL THE APPLIANCES AND EQUIPMENT IN THE
 RESIDENCE. PLEASE IDENTIFY THE APPLIANCES AND LIST THE
 BTUH CAPACITIES OF EACH. PLEASE NOTE THAT COMBUSTION
 AIR AND VENTING SYSTEMS SHALL BE REVIEWED AS PART OF
 THE APPROVAL PROCESS.
  
 C) FAILED. PROVIDE THE CORRECT PIPE SIZING TABLE- SEE
 SECTION G2413.4. PLEASE NOTE THAT LOW PRESSURE PIPING
 SYSTEMS FOR RESIDENTIAL APPLIANCE INSTALLATIONS ARE
 TYPICALLY SIZED USING TABLE G2413.4(1) FBC RES OR
 402.4(2) FBC FG. PLEASE LIST THE CORRECT PIPE SIZING
 TABLE ON THE DRAWING.
  
 2) FAILED. SUBMIT COMPLETE SPECS FOR THE BBQ SHOWING
 BTUH LOAD, GAS INPUT PRESSURE, AND INSTALLATION
 GUIDELINES INDICATING REQUIRED CLEARANCES TO
 COMBUSTIBLES, AND ANCHORING DETAILS- SECTION G2447.1.
  
 3) PASSED. THE CONTRACTOR OR QUALIFIER WHO PREPARED THE
 DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
 4) FAILED. THE $1500.00 PROJECT COST ON THE APPLICATION
 DOES NOT APPEAR TO INCLUDE THE BBQ GAS GRILL. PLEASE
 ADJUST THE VALUE TO INCLUDE THE COST OF THE GRILL-
 SECTION 109.3 WPB. THE PROJECT VALUE MAY INCREASE BASED
 ON COMMENT 1B LISTED ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 16:26 Rev Time 0.00
Received By ccole Date 2020-07-22 Time 15:21 Sent To  
Notes
2020-07-22 16:26:571ST REVIEW FBC-2017 RES.
 PERMIT- 20070419
 7/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC:
 A) PLEASE IDENTIFY THE REGULATOR AS EITHER NEW OR
 EXISTING. A SPEC SHEET FOR AN ITRON B42 REGULATOR HAS
 BEEN SUBMITTED, HOWEVER WHICH MODEL AND WHERE IT WILL
 BE INSTALLED NEEDS TO BE SHOWN ON THE DRAWING- SECTIONS
 G2421.1 & G2421.2 FBC RES. THE ITRON B42 HAS MANY
 DIFFERENT MODELS AND SIZES. PLEASE INDICATE THE MODEL
 NUMBER ON THE DRAWING AND SUBMIT SPECS FOR THAT MODEL
 INDICATING GAS PRESSURE RANGES AND ORIFICE SIZE.
 B) SHOW THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 FROM THE METER TO THE MOST REMOTE OUTLET. INDICATE THE
 BTUH LOAD OF EACH APPLIANCE TO CLARIFY HOW THE TOTAL
 180,000 BTUH LOAD WAS DETERMINED- SECTIONS G2413.2,
 G2413.3, G2413.4.1, G2413.4.2.
 C) PROVIDE THE CORRECT PIPE SIZING TABLE- SEE SECTION
 G2413.4. PLEASE NOTE THAT LOW PRESSURE PIPING SYSTEMS
 FOR RESIDENTIAL APPLIANCE INSTALLATIONS ARE TYPICALLY
 SIZED USING TABLE G2413.4(1) FBC RES OR 402.4(2) FBC
 FG.
  
 2) SUBMIT COMPLETE SPECS FOR THE BBQ SHOWING BTUH LOAD,
 GAS INPUT PRESSURE, AND INSTALLATION GUIDELINES
 INDICATING REQUIRED CLEARANCES TO COMBUSTIBLES, AND
 ANCHORING DETAILS- SECTION G2447.1.
  
 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.
  
 4) THE $1500.00 PROJECT COST ON THE APPLICATION DOES
 NOT APPEAR TO INCLUDE THE BBQ GAS GRILL. PLEASE ADJSUT
 THE VALUE TO INCLUDE THE COST OF THE GRILL- SECTION
 109.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-09-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-09-02 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-07-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-07-10 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-09-08 Cont ID  
Sent By ccole Date 2020-09-08 Time 17:31 Rev Time 0.00
Received By ccole Date 2020-09-08 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 16:27 Rev Time 0.00
Received By ccole Date 2020-07-22 Time 15:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-07-22 Cont ID  
Sent By ccole Date 2020-07-22 Time 16:27 Rev Time 0.00
Received By ccole Date 2020-07-22 Time 15:21 Sent To  
Notes
2020-07-22 16:29:38) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING
 SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1
 WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025.


Account Summary | Usage Policy | Privacy Policy