| 2020-07-22 14:57:59 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20070386 |
| | 7/22/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PLAN SHOWS A RELOCATED SINK IN THE MIDDLE OF THE |
| | FLOOR WITH NO PLUMBING DETAILS. PLEASE PROVIDE SANITARY |
| | ISOMETRIC AND WATER RISER DRAWINGS, AND A FLAT LINE |
| | PLAN SHOWING THE POINTS OF CONNECTIONS TO THE EXISTING |
| | DRAIN, VENT AND WATER LINES- SECTION 107.2.1 WPB. |
| | |
| | 2) THERE IS NO SIGNATURE, SEAL, OR TITLE BLOCK ON THE |
| | PLAN. IF THE CORRECTED PLUMBING PLAN IS PREPARED BY AN |
| | ENGINEER, IT SHALL BEAR THE ELECTRONIC SEAL AND |
| | SIGNATURE OF THE ENGINEER OF PER FL. STATUTE 471.025 |
| | AND SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE. |
| | IF THE CONTRACTOR OR QUALIFIER PREPARES THE CORRECTED |
| | DRAWING, THEN IT SHALL BEAR THE SIGNATURE OF THE |
| | CONTRACTOR OR QUALIFIER- SECTION 107.2.1 WPB, AND |
| | FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |