Plan Review Details - Permit 20070205
Plan Review Stops For Permit 20070205
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2020-08-26 Time 09:16 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-08-24 Time 8:58 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 07:59 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-07-14 Cont ID  
Sent By jwitmer Date 2020-07-14 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2020-07-14 Time 13:31 Sent To  
Notes
2020-07-14 15:33:33ASBESTOS COMMERCIAL.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2020-08-26 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-17 Cont ID  
Sent By jwitmer Date 2020-08-17 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2020-08-17 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-14 Cont ID  
Sent By jwitmer Date 2020-07-14 Time 15:31 Rev Time 0.00
Received By jwitmer Date 2020-07-14 Time 13:31 Sent To  
Notes
2020-07-14 13:38:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20070205
 ADD: 701 S. ROSEMARY AVE. # 141
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] CONTACT: KENT FAHEY
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 14TH/ 2020
 ACTION: DENIED
  
 1) THE DEMO SHEET NOTE # 4 INDICATES THE REMOVAL OF THE
 FRONT ENTRY DOORS AND FRAME IN ITS ENTIRETY. SHEET A420
 NOTE 26 INDICATES NEW EXTERIOR ALUMINUM NARROW STILE
 TEMPERED GLASS. I?M ASSUMING THIS WOULD BE THE DOORS,
 SIDELIGHTS, VERTICAL MULLIONS AND TRANSOM? THERE HAS
 BEEN NO WIND DESIGN CRITERIA OR PRODUCT APPROVALS
 SUBMITTED FOR THIS REVIEW.
  
 1A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
  
 1A)(1). ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1A)(2). RISK CATEGORY.
  
 1A)(3). WIND EXPOSURE. APPLICABLE WIND DIRECTION IF
 MORE THAN ONE WIND EXPOSURE IS UTILIZED. TABLE
 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 1A)(4). APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1A)(5). DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 1A)(6). TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 1B) PLEASE SHOW COMPLIANCE BY PROVIDING THE PRODUCT
 APPROVALS FOR ALL ELEMENTS. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS
 (B) WINDOWS, SIDELITES, TRANSOM & MULLIONS
  
 1C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
 1D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) SHEET A540 INDICATES THIS SHEET DETAILS THE CASH
 WRAP. PLEASE SHOW HOW THE CASH WRAP IS GOING TO COMPLY
 WITH:
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES. WHERE PROVIDED, CHECK WRITING
 SURFACES SHALL COMPLY WITH 902.3. 902.3HEIGHT. THE TOPS
 OF WORK SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM
 AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR
 OR GROUND.
  
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 3A) SHEET A110 & A310 DETAIL # 7 THE ACCESSIBLE FITTING
 ROOM THERE APPEARS TO BE NO DOOR FOR ENTRY. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B ACCESS. CODE SECTION
 803.3 DOORS SHALL NOT SWING INTO THE DRESSING ROOM
 UNLESS A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH
 305.3 IS PROVIDED BEYOND THE ARC OF THE DOOR.
  
 3B) PLEASE SHOW WITHIN THE ACCESSIBLE DRESSING ROOM
 COMPLIANCE WITH SECTIONS 803.4 BENCHES AND 803.5 COAT
 HOOKS.
  
 4) THE CODE SUMMARY & EGRESS SHEET A020 STATES AN
 OCCUPANT LOAD OF 55 OCCUPANTS. THEN STATES ONLY 1 IS
 ALLOWED/ REQUIRED. THAT 2 ARE ACTUALLY PROVIDES. THEN
 IT GOES ON TO STATING THE CODE SECTION 1016.2.5
 EXCEPTION 2 EGRESS THROUGH STORAGE ROOMS OF MERCANTILE
 OCCUPANCIES 2.1-2.4.
 THE FLOOR PLAN A100 DOES NOT SHOW HOW COMPLIANCE WITH
 FBC-B EXCEPTION 2- SECTIONS 2.1-2.4 ARE BEING COMPLIED
 WITH?
  
 5) SHEET A030 ACCESSIBILITY DETAILS:
 5A) THE WATER CLOSET GRAB BARS IS GIVEN WITH THE HEIGHT
 AT THE CENTERLINE OF THE GRAB BARS, NOT AT THE TOP OF
 THE BAR OR GRASPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 5B) THE WORDING ON THE PLAN IS CORRECT FOR MIRRORS BUR
 DEPICTED CORRECTLY. 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5C) THE DETAILS SHOW THE LOCATION OF THE TOILET PAPER
 DISPENSER BUT THE DISTANCE FORM IN FRONT OF THE WATER
 CLOSET.
 TOILET PAPER DISPENSERS. 604.7. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED
 BEHIND THE GRAB BARS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-21 Cont ID  
Sent By fgiaquin Date 2020-08-21 Time 22:28 Rev Time 0.00
Received By fgiaquin Date 2020-08-21 Time 22:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By fgiaquin Date 2020-07-30 Time 21:46 Rev Time 0.00
Received By fgiaquin Date 2020-07-30 Time 20:23 Sent To  
Notes
2020-07-30 20:46:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ON SHEET E110 THE ELECTRICAL CONNECTION SCHEDULE
 SHOWS #'8'S FOR AHU#2 AND MCA IS SHOWN AS 78.5AMPS.
 #8'S ARE INSUFFICIENT FOR REQUIRED MCA. PROVIDE
 CORRECTION. NEC 310.15B16
  
 2. PROVIDE NOTE ON PLAN THAT ALL LOW VOLTAGE WILL
 REQUIRE SEPARATE PERMITS CAMERA'S, SPEAKERS, DATA, EAS
 ETC. FBC 105.1 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-10-07 Cont ID  
Sent By jleahy Date 2020-10-07 Time 11:55 Rev Time 0.00
Received By jleahy Date 2020-10-07 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-26 Cont ID  
Sent By pleduc Date 2020-08-26 Time   Rev Time 0.00
Received By pleduc Date 2020-08-26 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-08-10 Cont ID  
Sent By pleduc Date 2020-08-10 Time   Rev Time 0.00
Received By pleduc Date 2020-08-10 Time 14:45 Sent To  
Notes
2020-08-10 14:51:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS AN INDICATION OF OPPOSING EXIT SIGNS AT THE
 REAR STOREROOM DOOR. THIS COMMENT IS RELATED TO # 3 OF
 THE PREVIOUS FIRE COMMENTS(ATTACHED BELOW FOR
 REFERENCE).
  
 THERE SHALL NOT BE OPPOSING EXIT SIGNS AT THIS
 LOCATION. EXIT SHALL BE IN ONE DIRECTION.
  
 ONE EXIT FROM THE STOREROOM IS PERMISSSIBLE AND IT IS
 LOCATED AT THE REAR EXTERIOR DOOR.
  
 THE EXIT PATH THROUGH THE STOREROOM SHALL BE 44" WIDE
 AND IDENTIFIED(MARKED) ON THE FLOOR(36.2.5.11)
  
 PLEASE CORRECT
  
  
 *****************3) SHEET A 020 - THERE IS AN
 INDICATION OF AN EXIT SIGN OVER THE REAR DOOR LEADING
 FROM THE SALES AREA TO AND THROUGH THE
 STOCKROOM.***************
  
 EXITING THROUGH THE STOCKROOM IS NOT ALLOWED PER FFPC,
 NFPA 101 CH 7 MEANS OF EGRESS.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C MERCANTILE
 OCCUPANCIES,
 SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED
 THROUGH THE STOREROOM.
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM) WIDE.
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 ADDITIONALLY, ONE EXIT FROM THE SALES AREA MAY BE
 APPLICABLE PER NFPA 101, CH 38 (TYPO) 36
  
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY AS APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By pleduc Date 2020-07-08 Time   Rev Time 0.00
Received By pleduc Date 2020-07-08 Time 10:18 Sent To  
Notes
2020-07-08 11:21:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 020 - UNDER APPLICABLE CODES ON THE
 FIRE/LIFE SAFETY LINE THERE IS AN INDICATION OF THE
 BUILDING CODE.
  
 THERE IS NO INDICATION OF THE FLORIDA FIRE PREVENTION
 CODE ON THIS LINE OR ANY OTHER SECTION.
  
 THE PROPOSED PROJUECT SHALL COMPLY WITH THE 6TH ED OF
 THE FLORIDA FIRE PREVENTION CODE AND ALL ASSOCIATED
 NFPA CODES.
  
 PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE.
  
  
  
  
 2) SHEET A 000 & A 020 - FIRE SPRINKLER AND FIRE ALARM
 WORK IS REQUIRED; HOWEVER, THERE ARE NO INDICATIONS
 THAT WORK WILL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWING.
  
 UNDER DEFERRED SUBMITTALS THERE ARE NO ENTRIES. FIRE
 SPRINKLER SHOP DRAWINGS AND FIRE ALARM SHOP DRAWINGS
 SHOULD BE UNDER THIS HEADING.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 3) SHEET A 020 - THERE IS AN INDICATION OF AN EXIT SIGN
 OVER THE REAR DOOR LEADING FROM THE SALES AREA TO AND
 THROUGH THE STOCKROOM.
  
 EXITING THROUGH THE STOCKROOM IS NO ALLOWED PER FFPC,
 NFPA 101 CH 7 MEANS OF EGRESS.
  
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS,
 STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND
 37,
 RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR
 OTHER ROOMS OR
 SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH
 ROOMS OR
 SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18,
 19, 22, OR 23.
  
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES THAT ARE PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C MERCANTILE
 OCCUPANCIES,
 SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CONDITIONS ARE MET:
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED
 THROUGH THE STOREROOM.
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN
 44 IN. (1120 MM) WIDE.
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 ADDITIONALLY, ONE EXIT FROM THE SALES AREA MAY BE
 APPLICABLE PER NFPA 101, CH 38
  
 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 36.2.5.3.
 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN
 A CLASS C
 MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE
 TO THE EXIT
 OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT
 EXCEED 75 FT
 (23 M).
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY AS APPLICABLE.
  
  
  
 4) SHEET A 180 - THE DOOR SCHEDULE INDICATES "STANDARD
 THUMB TURNS (AT INTERIOR) FOR THE STOREFRONT DOOR # 55
  
 PER NFPA 101
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
  
 5) SHEET A 180 - THE DOOR SCHEDULE INDICATES A
 STOREFRONT GRILLE , OVERHEAD ROLLING DOOR.
  
 THERE IS LIMITED DETAIL ON THE ROLLING DOOR
  
 PER NFPA 101
  
 36.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR
 DOORS
 COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE
 USED AS A PART
 OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE.
  
 (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 HORIZONTALSLIDING
 OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES
 THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE
 PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN
 SECURED IN
 THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY
 BY THE GENERAL PUBLIC.
 (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE
 SHALL
 BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN
 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT
 READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN
 WHEN THE SPACE IS OCCUPIED.
 (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE
 CLOSED
 POSITION WHEN THE SPACE IS OCCUPIED.
 (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM
 WITHIN THE
 SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR
 EFFORT.
 (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT
 MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED
 WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR
 DOOR
 ASSEMBLIES.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
 6) SHEET A 180 - THE DOOR SCHEDULE INDICATES "EMERGENCY
 LOCK" DOOR # D2A, WITH NO DETAIL ON WHAT THIS IS OR
 WHAT IT MEANS IN FUNCTIONALITY.
  
 PER NFPA 101
  
 36.2.2.2 DOORS.
 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE
 PERMITTED
 ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY
 TO DOOR
 LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO
 ELEVATED
 TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON
 LABORATORY
 FIRE TEST PROCEDURES.
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3
 SHALL NOT
 APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH
 23.
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
 PLEASE REVIEW AND CORRECT AS APPLICABLE
  
  
  
 7) SHEET A 110 - THERE IS NO INDICATION OF THE DOOR #
 OF THE REAR EGRESS DOOR THAT CAN BE CONFIRMED WITH ANY
 IN THE DOOR SCHEDULE.
  
 PLEASE REVIEW AND CORRECT AND ENSURE ALL EGRESS
 HARDWARE MEETS THE REQUIRMENTS AS NOTED ABOVE.
  
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-08-27 Time   Rev Time 0.00
Received By lmarchan Date 2020-08-25 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-24 Cont ID  
Sent By jwitmer Date 2020-08-24 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2020-08-07 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-30 Cont ID  
Sent By fgiaquin Date 2020-07-30 Time 21:46 Rev Time 0.00
Received By fgiaquin Date 2020-07-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-07-14 Cont ID  
Sent By jwitmer Date 2020-07-14 Time 15:32 Rev Time 0.00
Received By jwitmer Date 2020-07-14 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-11 Cont ID  
Sent By hmoser Date 2020-08-11 Time 13:47 Rev Time 0.00
Received By hmoser Date 2020-08-11 Time 13:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By medwards Date 2020-07-22 Time 08:56 Rev Time 0.00
Received By medwards Date 2020-07-22 Time 07:26 Sent To  
Notes
2020-07-22 08:57:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20070205
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THIS
 PROJECT. PLEASE INCLUDE THE DRESSING ROOM AREA IN THESE
 CALCULATIONS. FBC M 403
  
 2) PLEASE PROVIDE INFORMATION FOR THE AHU?S OR SHOW
 PROJECT NUMBER THAT THE INFORMATION IS LOCATED TO
 VERIFY INFORMATION ABOUT THE RTU?S. FBC FS 107.2.1
  
 3) PLEASE REMOVE THE ELECTRICAL LAYER FROM THE
 MECHANICAL SHEET FOR CLARITY. FBC FS 107.2.1
  
 4) PLEASE SHOW THE SMOKE DETECTORS ON THE DRAWINGS FOR
 EACH AHU. FBC M 606.2
  
 5) PLEASE EXPLAIN HOW THE DUCTWORK FOR THE DRESSING
 ROOMS EXHAUST ARE EXISTING. FBC FS 107.2.1
  
 6) PLEASE SHOW A MECHANICAL DEMO SHEET TO PLAINLY SHOW
 THE EXISTING MECHANICAL SYSTEMS. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-27 Cont ID  
Sent By ccole Date 2020-08-27 Time 15:20 Rev Time 0.00
Received By ccole Date 2020-08-27 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By ccole Date 2020-08-11 Time 10:59 Rev Time 0.00
Received By ccole Date 2020-08-10 Time 08:02 Sent To  
Notes
2020-08-11 11:04:152ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20070205
 8/11/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL
 EXISTS:
 1) SHEET A020 AND OTHER ARCHITECTURAL PLANS SHOW ACCESS
 TO THE PUBLIC RESTROOM IS THROUGH THE STORAGE ROOM
 WHICH IS NOT PERMITTED PER SECTION 403.3.1 FBC P.
 THE ARCHITECT HAS REVISED SHEET A-020 TO SHOW A 438'-0"
 PATH OF TRAVEL FROM THE ENTRANCE TO THE NEW TENANT
 SPACE TO THE PUBLIC RESTROOM FACILITIES. IN THE
 NARRATIVE RESPONSE THE ARCHITECT IS CITING SECTION
 403.3.3 FBC P WHICH APPEARS NOT TO BE RELEVANT BECAUSE
 THE SECTION REFERS TO "OCCUPANCIES" OTHER THAN MALLS.
 THE DEFINITION OF OCCUPANCY- THE PURPOSE FOR WHICH A
 BUILDING OR PORTION THEREOF IS UTILIZED OR OCCUPIED.
 THE CITY PLACE COMMON AREA DOES NOT APPEAR TO BE AN
 "OCCUPANCY". IF CITY PLACE IS IDENTIFIED AS AN "OPEN
 MALL" THEN THE ALLOWABLE TRAVEL DISTANCE IS 300 FT. PER
 SECTION 403.3.4 FBC P.
 PLEASE NOTE THAT THE DRAWING DOES NOT CLEARLY INDICATE
 THAT THE PATH TO THE RESTROOM FACILITIES IS AN
 ACCESSIBLE ROUTE- SEE SECTION 403.3.1.
 REFER TO SECTION 403.3 REQUIRED PUBLIC TOILET
 FACILITIES.
 CUSTOMERS, PATRONS AND VISITORS SHALL BE PROVIDED WITH
 PUBLIC TOILET FACILITIES IN STRUCTURES AND TENANT
 SPACES INTENDED FOR PUBLIC UTILIZATION. THE NUMBER OF
 PLUMBING FIXTURES LOCATED WITHIN THE REQUIRED TOILET
 FACILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 403 FOR ALL USERS. EMPLOYEES SHALL BE PROVIDED WITH
 TOILET FACILITIES IN ALL OCCUPANCIES. EMPLOYEE TOILET
 FACILITIES SHALL BE EITHER SEPARATE OR COMBINED
 EMPLOYEE AND PUBLIC TOILET FACILITIES.
  
 COMMENTS #5 AND #6 FROM THE 1AST REVIEW PRINTED BELOW
 ARE NOT COMPLETELY ADDRESSED.
 5) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 DRINKING FOUNTAINS NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
 6) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 BOTTLE FILLER NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 C) REACH RANGES TO FILLER- SECTIONS 308 & 309.
 THE DETAILS PROVIDED FOR THE DRINKING FOUNTAIN AND
 BOTTLE FILLER ARE LABELED AS A KEY PLAN AND FITTING
 ROOM ELEVATION VIEWS. PLEASE LABEL THE DETAILS
 CORRECTLY. PLEASE NOTE THAT THE MEASUREMENTS SHOWN ON
 THESE DETAILS ARE THE MAXIMUM ALLOWABLE TO BE IN
 COMPLIANCE WITH THE ALLOWABLE REACH RANGE TO THE BOTTLE
 FILLER OVER THE DRINKING FOUNTAIN.
  
 COMMENT 7E BELOW STILL EXISTS.
 7E) VENT CONTINUATION TO THE EXTERIOR OF THE BUILDING
 NOT SHOWN- SECTION 904.1.
 PLEASE CLARIFY THAT THE 2? VENT CONNECTION SHOWN IS THE
 CONNECTION TO THE MAIN VENT THAT IS TERMINATING TO THE
 OUTDOORS- SECTION 904.1 FBC P.
  
 NEW COMMENTS.
 1) SHEET P-520: INCLUDE THE RPZ IN THE FIXTURE
 SCHEDULE. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR WATER SERVICE BACKFLOW PREVENTERS- SECTION
 107.2.1 WPB
 2) P-520: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER PER TABLE C404.2 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By ccole Date 2020-07-28 Time 11:39 Rev Time 0.00
Received By ccole Date 2020-07-28 Time 07:15 Sent To  
Notes
2020-07-28 11:40:121ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20070205
 7/28/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A020 AND OTHER ARCHITECTURAL PLANS SHOW ACCESS
 TO THE PUBLIC RESTROOM IS THROUGH THE STORAGE ROOM
 WHICH IS NOT PERMITTED PER SECTION 403.3.1 FBC P.
  
 2) SHEET A030 ACCESSIBILITY: THE SINGLE OCCUPANCY
 TOILET DETAIL IS NOT IN COMPLIANCE FOR REQUIRED CLEAR
 FLOOR SPACES AND DOES NOT MATCH THE FLOOR PLANS.
 PROVIDE AN FBC ACC COMPLIANT, ENLARGED, SITE SPECIFIC,
 DIMENSIONED REST ROOM DRAWING INDICATING:
 A) CLEAR FLOOR SPACE DIMENSION FOR THE WATER CLOSET-
 SECTION 604.3
 B) CLEAR FLOOR SPACE DIMENSION FOR THE LAVATORY-
 SECTION 606.2
 C) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL -
 SECTION 604.2.
 D) TURNING CIRCLE DIAMETER- SECTION 304.3.
 E) DOOR OPENING DIMENSION AND DOOR SWING INTO THE ROOM-
 SECTION 603.2.3.
 F) GRAB LOCATIONS AND LENGTHS- SECTION 604.5
  
 3) SHEET A030: CORRECT THESE ELEVATION DRAWING DETAILS
 PER FBC ACC:
 A) GRAB BAR HEIGHTS FROM THE FINISHED FLOOR ARE SHOWN
 TO THE CENTERLINES OF THE GRAB BARS INSTEAD OF THE TOPS
 OF THE GRIPPING SURFACES- SECTION 609.4 FBC ACC.
 B) LAVATORY KNEE CLEARANCE DIMENSION TO THE UNDERSIDE
 OF THE FIXTURE NOT SHOWN- SECTION 306.3.3.
 WHERE KNEE CLEARANCE IS REQUIRED UNDER AN ELEMENT AS
 PART OF A CLEAR FLOOR SPACE, THE KNEE CLEARANCE SHALL
 BE 11 INCHES DEEP MINIMUM AT 9 INCHES ABOVE THE FINISH
 FLOOR OR GROUND, AND 8 INCHES DEEP MINIMUM AT 27 INCHES
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 STAFF SINK NOT SHOWN INCLUDING-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS- SECTIONS
 606.2, 305 & 306.
 B) MOUNTING HEIGHT OF THE SINK RIM OR COUNTER FROM THE
 FINISHED FLOOR- 606.3.
 C) REACH RANGE TO FAUCET AND COUNTER DEPTH- 606.4, 308
 & 309.
  
 5) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 DRINKING FOUNTAINS NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 B) KNEE AND TOE CLEARANCES- SECTION 306.
 C) SPOUT HEIGHT AND SPOUT LOCATION- SECTION 602.4 AND
 602.5.
  
 6) A030: SITE SPECIFIC ACCESSIBILITY DETAILS FOR THE
 BOTTLE FILLER NOT SHOWN INCLUDING-
 A) THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR
 FORWARD WHEELCHAIR APPROACH- SECTION 602.2. FBC ACC.
 C) REACH RANGES TO FILLER- SECTIONS 308 & 309.
  
 7) P-510 RISERS:
 A) SHOW THE TRAP PRIMER CONNECTION- SECTION 1002.4.1
 FBC P
 B) PLEASE NOTE THAT TEMPERED WATER IS REQUIRED AT THE
 LAVATORY PER SECTION 416.5 SHOW THE LOCATION OF THE
 TEMPERATURE LIMITING DEVICE- SECTION 607.1.2.
 C) SHOW THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS TO THE FIXTURES- SEE SECTION 604.9.
 D) SHOW THE REQUIRED BACKFLOW PREVENTER AT THE REMOTE
 CHILLER- SECTION 608.3
 E) VENT CONTINIUATION TO THE EXTERIOR OF THE BUILDING
 NOT SHOWN- SECTION 904.1.
  
 8) 5-520: PLEASE ADD THE REQUIRED DEVICES LISTED ABOVE
 IN COMMENT 7 TO THE PLUMBING FIXTURE SCHEDULE- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-26 Cont ID  
Sent By jwitmer Date 2020-08-26 Time 09:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-24 Cont ID  
Sent By jwitmer Date 2020-08-24 Time 09:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-22 Cont ID  
Sent By medwards Date 2020-07-22 Time 09:31 Rev Time 0.00
Received By medwards Date 2020-07-22 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By eschneid Date 2020-07-30 Time 17:06 Rev Time 0.50
Received By eschneid Date 2020-07-30 Time 16:44 Sent To  
Notes
2020-07-30 17:05:56FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL WAS NOT
 PROVIDED. THIS MAY BE STAMPED ON THE PLANS OR SEPARATE
 LETTER WHICH REFERENCES THE SPECIFIC PLANS THEY HAVE
 APPROVED.
  
 2) ALL SIGNAGE REQUIRES A SEPARATE PERMIT WITH PLANS,
 TO INCLUDE THE WINDOW VINYL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]