| 2020-07-08 11:21:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 020 - UNDER APPLICABLE CODES ON THE |
| | FIRE/LIFE SAFETY LINE THERE IS AN INDICATION OF THE |
| | BUILDING CODE. |
| | |
| | THERE IS NO INDICATION OF THE FLORIDA FIRE PREVENTION |
| | CODE ON THIS LINE OR ANY OTHER SECTION. |
| | |
| | THE PROPOSED PROJUECT SHALL COMPLY WITH THE 6TH ED OF |
| | THE FLORIDA FIRE PREVENTION CODE AND ALL ASSOCIATED |
| | NFPA CODES. |
| | |
| | PLEASE REVIEW AND CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 000 & A 020 - FIRE SPRINKLER AND FIRE ALARM |
| | WORK IS REQUIRED; HOWEVER, THERE ARE NO INDICATIONS |
| | THAT WORK WILL BE DONE UNDER SEPARATE PERMITS AND SHOP |
| | DRAWING. |
| | |
| | UNDER DEFERRED SUBMITTALS THERE ARE NO ENTRIES. FIRE |
| | SPRINKLER SHOP DRAWINGS AND FIRE ALARM SHOP DRAWINGS |
| | SHOULD BE UNDER THIS HEADING. |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 3) SHEET A 020 - THERE IS AN INDICATION OF AN EXIT SIGN |
| | OVER THE REAR DOOR LEADING FROM THE SALES AREA TO AND |
| | THROUGH THE STOCKROOM. |
| | |
| | EXITING THROUGH THE STOCKROOM IS NO ALLOWED PER FFPC, |
| | NFPA 101 CH 7 MEANS OF EGRESS. |
| | |
| | 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND |
| | 7.2.1.5. |
| | 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH |
| | KITCHENS, |
| | STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS 36 AND |
| | 37, |
| | RESTROOMS, CLOSETS, BEDROOMS OR SIMILAR SPACES, OR |
| | OTHER ROOMS OR |
| | SPACES SUBJECT TO LOCKING, UNLESS PASSAGE THROUGH SUCH |
| | ROOMS OR |
| | SPACES IS PERMITTED FOR THE OCCUPANCY BY CHAPTER 18, |
| | 19, 22, OR 23. |
| | |
| | |
| | 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE |
| | OCCUPANCIES THAT ARE PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C MERCANTILE |
| | OCCUPANCIES, |
| | SHALL BE PERMITTED TO PASS THROUGH STOREROOMS, PROVIDED |
| | THAT ALL OF |
| | THE FOLLOWING CONDITIONS ARE MET: |
| | (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE |
| | PROVIDED |
| | THROUGH THE STOREROOM. |
| | (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING. |
| | (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT |
| | LESS THAN |
| | 44 IN. (1120 MM) WIDE. |
| | (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE |
| | DEFINED, DIRECT, |
| | AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED |
| | CONDITION. |
| | |
| | ADDITIONALLY, ONE EXIT FROM THE SALES AREA MAY BE |
| | APPLICABLE PER NFPA 101, CH 38 |
| | |
| | 36.2.4.2 EXIT ACCESS, AS REQUIRED BY 36.2.4.1(3), SHALL |
| | BE PERMITTED |
| | TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS |
| | COMMON PATHS OF TRAVEL BY 36.2.5.3. |
| | 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN |
| | A CLASS C |
| | MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE |
| | TO THE EXIT |
| | OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT |
| | EXCEED 75 FT |
| | (23 M). |
| | |
| | PLEASE REVIEW AND CORRECT OF JUSTIFY AS APPLICABLE. |
| | |
| | |
| | |
| | 4) SHEET A 180 - THE DOOR SCHEDULE INDICATES "STANDARD |
| | THUMB TURNS (AT INTERIOR) FOR THE STOREFRONT DOOR # 55 |
| | |
| | PER NFPA 101 |
| | |
| | 36.2.2.2 DOORS. |
| | 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE REVIEW AND CORRECT AS APPLICABLE |
| | |
| | |
| | |
| | |
| | 5) SHEET A 180 - THE DOOR SCHEDULE INDICATES A |
| | STOREFRONT GRILLE , OVERHEAD ROLLING DOOR. |
| | |
| | THERE IS LIMITED DETAIL ON THE ROLLING DOOR |
| | |
| | PER NFPA 101 |
| | |
| | 36.2.2.2.7 HORIZONTAL OR VERTICAL SECURITY GRILLES OR |
| | DOORS |
| | COMPLYING WITH 7.2.1.4.1(3) SHALL BE PERMITTED TO BE |
| | USED AS A PART |
| | OF THE REQUIRED MEANS OF EGRESS FROM A TENANT SPACE. |
| | |
| | (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| | HORIZONTALSLIDING |
| | OR VERTICAL-ROLLING SECURITY GRILLES OR DOOR ASSEMBLIES |
| | THAT ARE PART OF THE REQUIRED MEANS OF EGRESS SHALL BE |
| | PERMITTED, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA |
| | ARE MET: |
| | (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN |
| | SECURED IN |
| | THE FULLY OPEN POSITION DURING THE PERIOD OF OCCUPANCY |
| | BY THE GENERAL PUBLIC. |
| | (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE |
| | SHALL |
| | BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN |
| | 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT |
| | READS AS FOLLOWS: THIS DOOR TO REMAIN OPEN |
| | WHEN THE SPACE IS OCCUPIED. |
| | (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE |
| | CLOSED |
| | POSITION WHEN THE SPACE IS OCCUPIED. |
| | (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM |
| | WITHIN THE |
| | SPACE WITHOUT THE USE OF ANY SPECIAL KNOWLEDGE OR |
| | EFFORT. |
| | (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| | MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED |
| | WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR |
| | DOOR |
| | ASSEMBLIES. |
| | |
| | PLEASE REVIEW AND CORRECT AS APPLICABLE |
| | |
| | |
| | |
| | 6) SHEET A 180 - THE DOOR SCHEDULE INDICATES "EMERGENCY |
| | LOCK" DOOR # D2A, WITH NO DETAIL ON WHAT THIS IS OR |
| | WHAT IT MEANS IN FUNCTIONALITY. |
| | |
| | PER NFPA 101 |
| | |
| | 36.2.2.2 DOORS. |
| | 36.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 36.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| | PERMITTED |
| | ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE REVIEW AND CORRECT AS APPLICABLE |
| | |
| | |
| | |
| | 7) SHEET A 110 - THERE IS NO INDICATION OF THE DOOR # |
| | OF THE REAR EGRESS DOOR THAT CAN BE CONFIRMED WITH ANY |
| | IN THE DOOR SCHEDULE. |
| | |
| | PLEASE REVIEW AND CORRECT AND ENSURE ALL EGRESS |
| | HARDWARE MEETS THE REQUIRMENTS AS NOTED ABOVE. |
| | |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |