Plan Review Details - Permit 20070187
| Plan Review Stops For Permit 20070187 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2020-07-22 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2020-07-22 |
Time |
00:00 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2020-07-13 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
sathomas |
Date |
2020-07-13 |
Time |
00:00 |
Sent To |
M |
|
| Notes |
| 2020-07-13 15:52:24 | ACCORDING TO PAGE 48 OF MANUFACTURER SPEC SHEET, BOTTOM | | | RIGHT CORNER L4600 "...180ML AND TWO (2) FLOW NUMBERS | | | MUST BE UTILIZED AT OR BEFORE THE RANGE, WOK, OR | | | FRYER." | | | | | | ACCORDING TO NFPA 96: | | | | | | 12.1.2.3.1 AN APPROVED METHOD SHALL BE PROVIDED THAT | | | WILL | | | ENSURE THAT THE APPLIANCE IS RETURNED TO AN APPROVED | | | DESIGN | | | LOCATION. | | | 12.1.2.4 ALL DEEP-FAT FRYERS SHALL BE INSTALLED WITH AT | | | LEAST A | | | 406 MM (16 IN.) SPACE BETWEEN THE FRYER AND SURFACE | | | FLAMES | | | FROM ADJACENT COOKING EQUIPMENT. | | | | | | ACCORDING TO NFPA 17A: | | | | | | 4.4.4.1 ON ACTUATION OF ANY COOKING EQUIPMENT | | | FIREEXTINGUISHING | | | SYSTEM, ALL SOURCES OF FUEL AND ELECTRIC POWER | | | THAT PRODUCE HEAT TO ALL EQUIPMENT PROTECTED BY THE | | | SYSTEM | | | SHALL BE SHUT DOWN. | | | | | | 4.4.4.2 GAS APPLIANCES NOT REQUIRING PROTECTION BUT | | | LOCATED | | | UNDER THE SAME VENTILATION EQUIPMENT SHALL ALSO BE SHUT | | | OFF. | | | | | | S. THOMAS | | | 561-804-4728 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-07-28 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-07-16 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-07-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-07-15 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-07-09 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2020-07-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-07-27 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-07-27 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2020-07-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-07-15 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-07-15 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2020-07-15 12:58:00 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | AT TIME OF INSPECTION THE HOOD MUST BE TESTED AS PER | | | SECTIONS M 507.6 (PERFORMANCE TEST) & M 507.6.1 | | | (CAPTURE & CONTAINMENT TESTS). | | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL. | | | | | | NOTE: THE FIRE REVIEW NEEDS TO BE APPROVED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-07-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-07-29 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-07-29 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-07-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-07-27 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-07-27 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2020-07-27 13:52:51 | PLEASE SEE ORIGINAL REVIEWER NOTES FOR REQUIRED | | | INFORMATION NEEDED. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-07-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-07-15 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-07-15 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2020-07-15 13:31:24 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | SIGNATURE REVIEW DENIED: | | | | | | FBC B AND WPB AMENDMENTS 107.2.1, ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL | | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. |
|
|
|