Plan Review Details - Permit 20070178
Plan Review Stops For Permit 20070178
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 07:58 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-01-23 Cont ID  
Sent By cthroop Date 2021-01-23 Time 09:31 Rev Time 0.00
Received By cthroop Date 2020-12-31 Time 10:38 Sent To  
Notes
2021-01-23 09:45:28PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PRODUCT APPROVALS SUBMITTED FOR REVIEW ARE NOT
 LISTED ON PRODUCT APPROVAL SCHEDULE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE PRODUCT APPROVALS LISTED ON SCHEDULE.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 3. PROVIDE WIND DESIGN PRESSURES FOR EACH WINDOW AND
 DOOR OPENING.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 4. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 5. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 6. PROVIDE ATTACHMENT DETAIL FOR WINDOW AND DOOR
 OPENING WOOD TO METAL STUD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-11-04 Cont ID  
Sent By cthroop Date 2020-11-04 Time 07:35 Rev Time 0.00
Received By cthroop Date 2020-11-04 Time 07:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-28 Cont ID  
Sent By cthroop Date 2020-09-28 Time 16:25 Rev Time 0.00
Received By cthroop Date 2020-09-28 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:08 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 13:34:57PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE HAS BEEN ADJUSTED FROM 250,000 TO 352,390
 BASED ON THE ICC BUILDING VALUATION DATA.
 CITY OF WPB CHPT. 1 ? VALUE 109.3 BUILDING PERMIT
 VALUATIONS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL
  
 2. NFIP - PROVIDE AN ELEVATION CERTIFICATE PER NOTE ON
 PLAN PAGE A-100. SEE NFIP REVIEW COMMENTS.
  
 3. PROVIDE SITE DRAINAGE PLAN.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 4. PROVIDE FINISHED FLOOR ELEVATION
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 5. PROVIDE A SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 6. PALM BEACH COUNTY IMPACT FEES MAY APPLY. SEE
 COMMENTS UNDER IMPACT FEE REVIEW.
  
 7. DESIGNER TO PROVIDE INSULATION TYPE AND R VALUE FOR
 CEILING AND WALLS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. PROVIDE A CODE COMPLIANT ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  
 9. PROVIDE PRODUCT APPROVALS FOR ROOFING EXTERIOR DOORS
 AND WINDOWS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 07:44 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 06:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-01-25 Cont ID  
Sent By cthroop Date 2021-01-25 Time 09:21 Rev Time 0.00
Received By cthroop Date 2020-12-31 Time 10:38 Sent To  
Notes
2021-01-25 09:41:47PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT
 FROM UTILITY.
  
 AIC RATING OF SERVICE DISCONNECT AND PANEL
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
 E3706.1PANELBOARD RATING.
 ALL PANELBOARDS SHALL HAVE A RATING NOT LESS THAN THAT
 OF THE MINIMUM SERVICE OR FEEDER CAPACITY REQUIRED FOR
 THE CALCULATED LOAD. (408.30)
  
 2. PROVIDE EQUIPMENT SERVICE OUTLET PER E3901.12
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 3. OUTLETS REQUIRED AT ISLAND SINK PER FIGURE 3901.4.1
 ISLAND COUNTERTOP SPACES.
 E3901.4.2 ISLAND COUNTERTOP SPACES.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF
 24 INCHES (610 MM) OR GREATER AND A SHORT DIMENSION OF
 12 INCHES (305 MM) OR GREATER. [210.52(C)(2)]
  
 4. SMOKE ALARMS
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. 1.IN EACH SLEEPING ROOM.
 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE
 IMMEDIATE VICINITY OF THE BEDROOMS.
 NOTE: ADD SMOKE ALARMS IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 10:07 Rev Time 0.00
Received By jleahy Date 2020-09-21 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 14:13 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 14:14:48PROVISO: HIGH-EFFICACY LAMPS REQUIRED PER EC R404.1.
 ELECTRICAL PLANS REQUIRE A VALID DIGITAL SIGNATURE OF
 THE DESIGN PROFESSIONAL. SEE COMMENTS UNDER DIGITAL
 SIGNATURE REVIEW. CT

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status N Date 2021-01-25 Cont ID  
Sent By cthroop Date 2021-01-25 Time 09:16 Rev Time 0.00
Received By cthroop Date 2021-01-21 Time 15:25 Sent To  
Notes
2021-01-25 09:17:34NO LOW VOLTAGE SHOWN ON PLANS. CT

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:39 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 13:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 13:16 Rev Time 0.00
Received By lcrespo Date 2021-05-05 Time 08:57 Sent To  
Notes
2021-05-05 13:16:5605/05/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2021-01-25 Cont ID  
Sent By lcrespo Date 2021-01-25 Time 15:26 Rev Time 0.00
Received By lcrespo Date 2021-01-25 Time 12:52 Sent To  
Notes
2021-01-25 15:26:2401/25/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE LABEL THE GAS RANGE ON P-01 AND 02 PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. PLEASE LABEL REGULATOR, DRIP LEGS, AND VALVE PLUS
 SHOW UNION ON THE HEATERS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS), OR 2017 FBC
 RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 4. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 5. THE PLANS SHOW A GAS GRILL. PLEASE PROVIDE
 DOCUMENTATION THAT THE GAS GRILL IS LABELED FOR OUTDOOR
 USE. IT SEEMS TO BE ON A COVERED PATIO. IF SO, PLEASE
 GIVE THE MANUFACTURER'S RECOMMENDATION FOR A
 VENTILATION HOOD PER THE 2017 FBC RES. SEC. G2408.1.
  
 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE FBC RES. SEC. G2421.1.
  
 7. PLEASE SUBMIT ON HOUSE PLANS SHOWING THE LOCATION OF
 THE TANK-LESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE WATER HEATER'S LOCATION SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. PLEASE COMPLY WITH SIGNATURE REVIEW COMMENTS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-01-19 Cont ID  
Sent By abelisle Date 2021-01-19 Time 18:17 Rev Time 0.00
Received By abelisle Date 2021-01-19 Time 18:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By lcrespo Date 2020-10-28 Time 09:18 Rev Time 0.00
Received By lcrespo Date 2020-10-26 Time 06:11 Sent To  
Notes
2020-10-28 09:20:0510/28/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-09-15 Cont ID  
Sent By abelisle Date 2020-09-15 Time 21:42 Rev Time 0.00
Received By abelisle Date 2020-09-15 Time 18:46 Sent To  
Notes
2020-09-15 21:53:461ST REVIEW FBC-2017 GAS
 PERMIT-20070178
 9/15/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER
 AND THE RANGE THE 2017 FBC FUEL GAS SEC. 304.1, 614.5
 (CLOTHES DRYERS) 304.4MAKEUP AIR PROVISIONS,
 304.5INDOOR COMBUSTION AIR (RANGE)
  
 2. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1- 2ND
 REQUEST.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
2020-09-15 18:47:13IN REVIEW

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:39 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 10:31 Sent To  
Notes
2020-08-10 13:46:08PLAN REVIEW - FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. A SEPERATE FUEL GAS PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE GAS REGULATOR SPECIFICATIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE APPLIANCE SPECIFICATIONS. CLEARLY IDENTIFY
 EQUIPMENT TO BE INSTALLED AND THE TOTAL GAS DEMAND OF
 EACH APPLIANCE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. GAS RISER PLAN REQUIRES A VALID DIGITAL SIGNATURE OF
 DESIGN PROFESSIONAL. SEE COMMENTS UNDER DIGITAL
 SIGNATURE REVIEW.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 13:17 Rev Time 0.00
Received By lcrespo Date 2021-04-12 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-02-04 Cont ID  
Sent By lmarchan Date 2021-02-04 Time 14:55 Rev Time 0.00
Received By lmarchan Date 2020-12-30 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-11-04 Cont ID  
Sent By cthroop Date 2020-11-04 Time 07:36 Rev Time 0.00
Received By cthroop Date 2020-10-14 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-28 Cont ID  
Sent By cthroop Date 2020-09-28 Time 16:26 Rev Time 0.00
Received By cthroop Date 2020-09-09 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-11 Cont ID  
Sent By lmarchan Date 2020-08-11 Time 15:57 Rev Time 0.00
Received By lmarchan Date 2020-07-20 Time 16:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-05-05 Cont ID  
Sent By lmarchan Date 2021-05-05 Time 16:18 Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 08:09 Sent To  
Notes
2021-05-05 15:18:56RECEIPT MU 2020-48557 - $9785.26 - PAID
  
2020-12-09 08:09:3612/9/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 14:23 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 14:23:46IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2021-04-21 Cont ID  
Sent By medwards Date 2021-04-21 Time 10:44 Rev Time 0.00
Received By medwards Date 2021-04-21 Time 10:07 Sent To  
Notes
2021-04-21 10:45:15PRIVISO:
 THE DRYER DUCT TERMINATION SHALL HAVE NO INSECT
 SCREENS. FBC M 504.4
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2021-01-25 Cont ID  
Sent By medwards Date 2021-01-25 Time 06:18 Rev Time 0.00
Received By medwards Date 2021-01-25 Time 06:18 Sent To  
Notes
2021-01-25 06:18:231ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20070178
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ALL BATH EXHAUST FANS MUST HAVE AN EXHAUST CAPACITY
 OF 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS. FBC RES
 TABLE M1507.4
  
 2) PLEASE SHOW THE RANGE HOOD AND THE EXHAUST
 TERMINATION LOCATION. FBC RES M1503.1, 1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2021-01-22 Cont ID  
Sent By medwards Date 2021-01-22 Time 08:42 Rev Time 0.00
Received By medwards Date 2021-01-22 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2021-01-04 Cont ID  
Sent By medwards Date 2021-01-04 Time 08:05 Rev Time 0.00
Received By medwards Date 2021-01-04 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 09:24 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-16 Cont ID  
Sent By medwards Date 2020-09-16 Time 16:18 Rev Time 0.00
Received By medwards Date 2020-09-16 Time 09:07 Sent To  
Notes
2020-09-16 16:19:262ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20070178
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2: PLEASE MODIFY NOTE 7 (C) AS THE DUCT WORK
 FOR SUPPLY AND RETURN LEAVING THE AHU LOCATED IN THE
 GARAGE MUST BE A MINIMUM 26GA METAL DUCT. FBC RES
 R302.5.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 12:06 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 10:55 Sent To  
Notes
2020-08-03 12:06:341ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20070178
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE ENERGY SUBMITTAL. FBC EC 101.5.1.1.2
  
 2) PROVIDE MECHANICAL EQUIPMENT SIZING CALCULATIONS.
 FBC EC R403.7 & FBC RES M1401.3
  
 3) ALL DUCTWORK IN THE GARAGE FOR AHU-1 SHALL BE METAL
 AND 26 GAUGE. FBC RES R302.5.2
  
 4) THE PIPING FOR NOTE 10 ON SHEET M-1 MUST BE METAL 26
 GAUGE AND MUST TERMINATE IN THE RETURN DUCTWORK, NOT
 TERMINATE UNDER THE AHU. FBC RES R302.5.2
  
 5) PLEASE SHOW DUCTWORK FOR RETURN AIR FOR AHU-1 AT
 GARAGE IS METAL 26GAUGE. FBC RES R302.5.2
  
 6) PLEASE PROVIDE INFORMATION FOR THE XVENT AT THE
 DRYER DUCT TERMINATION POINT MEETS SECTION; FBC RES
 M1502.3 ( THE TERMINATION POINT CAN NOT HAVE A SCREEN)
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2021-01-21 Cont ID  
Sent By cthroop Date 2021-01-21 Time 17:02 Rev Time 0.00
Received By cthroop Date 2020-12-31 Time 10:40 Sent To  
Notes
2021-04-30 06:58:54THIS STRUCTURE IS NOT LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE CITY DOES NOT REVIEW ELEVATION
 CERTIFICATES (EC) NOT IN A SFHA. YOU MAY SUBMIT EC TO
 INSURANCE COMPANY. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2020-09-28 Cont ID  
Sent By cthroop Date 2020-09-28 Time 16:14 Rev Time 0.00
Received By cthroop Date 2020-09-28 Time 14:09 Sent To  
Notes
2020-09-28 16:16:00STRUCTURE IS NOT LOCATED IN A SFHA. EC IS OPTIONAL.
 SUBMIT EC FOR REVIEW UPON PLACEMENT OF LOWEST FLOOR PER
 DESIGNER OF RECORD, SEE SHEET A-100. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:35 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 07:36 Sent To  
Notes
2020-08-10 13:39:11PLAN REVIEW - NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE AN ELEVATION CERTIFICATE PER NOTE ON PLAN
 PAGE A-100.
  
 NOTE: THIS PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. THE STRUCTURE IS LOCATED IN FLOOD ZONE X
 WITH NO BASE FLOOD ELVATION REQUIREMENTS. AN ELEVATION
 CERTIFICATE IS NOT REQUIRED BUT MAY BE SUBMITTED FOR
 FUTURE INSURANCE CONSIDERATIONS.

Review Stop P PLUMBING
Rev No 6 Status P Date 2021-05-05 Cont ID  
Sent By lcrespo Date 2021-05-05 Time 13:15 Rev Time 0.00
Received By lcrespo Date 2021-05-05 Time 08:57 Sent To  
Notes
2021-05-05 13:16:2405/05/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 5 Status F Date 2021-01-25 Cont ID  
Sent By lcrespo Date 2021-01-25 Time 12:52 Rev Time 0.00
Received By lcrespo Date 2021-01-25 Time 12:52 Sent To  
Notes
2021-01-25 12:52:0401/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-01:
 A. UNDER THE PLUMBING NOTE, FBC PLUMBING 2010 REFERS TO
 THE CHANGE TO THE CURRENT YEAR PER THE WPB AMENDMENTS
 TO THE FBC SEC. 101.4 REFERENCED CODES.
  
 B. PLEASE PROVIDE A NOTE THE HOT WATER LINE, NOT IN
 CONDITION SPACE, SHALL BE INSULATED WITH AN R-3 FACTOR
 PER THE 2017 F FBC RE 403.5.3.
  
 C. THERE APPEAR TO BE TWO ISOMETRIC DRAWINGS. THIS
 REVIEW WILL BE DONE ON P-01, SO PLEASE REMOVE THE P-01
 ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET P-02;
 A. THE CLEANOUT SHALL BE NO MORE THAN 10? FROM THE
 BUILDING ENTRANCE. PLEASE PROVIDE A DISTANCE ON THE
 FLAT DRAWING TO COMPLY WITH 201 FBC SEC. R P3005.2.3
 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 B. ON THE WASHING MACHINE STACK, PLEASE SHOW THE P-TRAP
 ABOVE GROUND AND A VENT ( A.A.V. OR VTR) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THE WATER CLOSET IN THE POWDER ROOM IS NOT VENTED.
 PLEASE VENT WITH LAV PER THE 2017 FBC SEC R 3101.2.1
 VENTING REQUIRED.
  
 D. THE KITCHEN IS SHOWN AS AN UNDER THE GROUND P-TRAP
 AND NOT VENTED CORRECTLY; PLEASE CHANGE TO ABOVE GROUND
 AND VENT TO COMPLY WITH THE 2017 FBC SEC R 3101.2.1
 VENTING REQUIRED.
  
 C. THE PATIO SIN IS ON A WENT VENT BATHROOM GROUP.
 PLEASE MOVE DOWNSTREAM PER THE 2017 FBC SECTION R3108.1
 HORIZONTAL WET VENT PERMITTED.
  
 3. PLEASE COMPLY WITH SIGNATURE REVIEW COMMENTS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P-04, THE DRAIN LINE ON THE TANKLESS WATER
 HEATER MAY BE A CONDENSATE LINE AND, IF SO, WILL BE
 REQUIRED TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017
 FBC SEC. R318.5.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-01-19 Cont ID  
Sent By abelisle Date 2021-01-19 Time 18:17 Rev Time 0.00
Received By abelisle Date 2021-01-19 Time 18:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By lcrespo Date 2020-10-28 Time 09:19 Rev Time 0.00
Received By lcrespo Date 2020-10-28 Time 09:19 Sent To  
Notes
2020-10-28 09:24:4910/28/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-15 Cont ID  
Sent By abelisle Date 2020-09-15 Time 21:42 Rev Time 0.00
Received By abelisle Date 2020-09-15 Time 18:46 Sent To  
Notes
2020-09-15 18:46:59IN REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:46 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 13:47:00PLUMBING PLANS REQUIRE A VALID DIGITAL SIGNATURE OF
 DESIGN PROFESSIONAL. CT

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 07:58 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 06:54 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-01-23 Cont ID  
Sent By cthroop Date 2021-01-23 Time 08:39 Rev Time 0.00
Received By cthroop Date 2021-01-21 Time 15:25 Sent To  
Notes
2021-01-23 08:41:53PLAN REVIEW / ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PRODUCT APPROVALS SUBMITTED FOR REVIEW DO NOT MATCH
 PRODUCT APPROVALS ON SCHEDULE, PLAN PAGE G-01.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-09-28 Cont ID  
Sent By cthroop Date 2020-09-28 Time 16:17 Rev Time 0.00
Received By cthroop Date 2020-09-28 Time 14:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 14:22:13PLAN REVIEW - ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 ASSYMBLY COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2021-04-30 Cont ID  
Sent By cthroop Date 2021-04-30 Time 07:45 Rev Time 0.00
Received By cthroop Date 2021-04-30 Time 06:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-04-12 Cont ID  
Sent By medwards Date 2021-04-12 Time 11:22 Rev Time 0.00
Received By medwards Date 2021-04-12 Time 11:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-01-23 Cont ID  
Sent By cthroop Date 2021-01-23 Time 08:42 Rev Time 0.00
Received By cthroop Date 2021-01-23 Time 08:42 Sent To  
Notes
2021-01-23 08:45:30PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-12-31 Cont ID  
Sent By medwards Date 2020-12-31 Time 09:59 Rev Time 0.00
Received By medwards Date 2020-12-31 Time 09:58 Sent To  
Notes
2020-12-31 09:59:27ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-16 Cont ID  
Sent By medwards Date 2020-10-16 Time 09:26 Rev Time 0.00
Received By medwards Date 2020-10-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-28 Cont ID  
Sent By cthroop Date 2020-09-28 Time 16:25 Rev Time 0.00
Received By cthroop Date 2020-09-28 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By cthroop Date 2020-08-10 Time 13:47 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 06:08 Sent To  
Notes
2020-08-10 13:50:16PLAN REVIEW - DIGITAL SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 A VALID DIGITAL SIGNATURE IS REQUIRED ON THE MECHANICAL
 ELECTRICAL PLUMBING AND FUEL GAS PLANS.
  
  
 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
 3. FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  
 OPTION
  
 YOU MAY ELECT TO PROVIDE A HARD COPY OF PLANS WITH WET
 SEAL AND SIGNATURE OF DESIGN PROFESSIONAL PRIOR TO
 PERMIT. A DROP BOX HAS BEEN INSTALLED OUTSIDE CITY HALL
 FOR THIS PURPOSE. CONTACT THE OFFICE OF DEVELOPMENT
 SERVICES @ 561-805-8700 OR [email protected] TO STATE YOUR
 INTENTIONS. CITY STAFF WILL REVIEW YOUR DOCUMENTS AND
 IF APPROVED YOU WILL RECIEVE AN E-MAIL INSTRUCTING YOU
 TO DOWNLOAD AND PRINT YOUR PERMIT AND PLANS.
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-02-02 Cont ID  
Sent By kalexand Date 2021-02-02 Time 09:08 Rev Time 0.00
Received By kalexand Date 2021-02-02 Time 09:08 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By kalexand Date 2020-09-21 Time 10:28 Rev Time 0.00
Received By kalexand Date 2020-09-21 Time 10:28 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-11 Cont ID  
Sent By kalexand Date 2020-08-11 Time 13:59 Rev Time 0.00
Received By kalexand Date 2020-08-11 Time 13:59 Sent To I
Notes
***NONE***