Plan Review Details - Permit 20070175
Plan Review Stops For Permit 20070175
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By pvalenti Date 2020-07-24 Time 08:48 Rev Time 0.00
Received By pvalenti Date 2020-07-24 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By rmcphers Date 2020-07-16 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2020-07-16 Time 08:45 Sent To  
Notes
2020-07-16 08:53:27ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ROOFING SYSTEM TO BE USED ON THE PROVIDED PRODUCT
 APPROVAL REQUIRES ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE
 THAN THE MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) -
 SEE NOTE NUMBER 9 OR GENERAL LIMITATION NUMBER 7 ON THE
 PRODUCT APPROVAL. SIGNED AND SEALED DRAWINGS OR
 DOCUMENTS WILL NEED TO BE DIGITALLY SIGNED AND SEALED
 TO BE USED IN ELECTRONIC PLAN REVIEW. SHOW THE WIND
 DESIGN DATA USED PER 2017 FBC AND ASCE 7-10 - WIND
 SPEED - EXPOSURE - RISK CATEGORY - ETC.
 2) YOU HAVE 2 PRODUCT APPROVALS FOR THE FLAT DECK -
 PLEASE REMOVE 1 OF THEM FROM THE FOLDERS (FL 2533-R21)
 AND (MIAMI DADE 20-0131.01) OR STATE ON THE PRODUCT
 APPROVAL WHAT EACH ONE IS FOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By pvalenti Date 2020-07-24 Time 08:49 Rev Time 0.00
Received By pvalenti Date 2020-07-21 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-16 Cont ID  
Sent By rmcphers Date 2020-07-16 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 11:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-24 Cont ID  
Sent By pvalenti Date 2020-07-24 Time 08:47 Rev Time 0.00
Received By pvalenti Date 2020-07-24 Time 08:25 Sent To  
Notes
2020-07-24 08:48:45PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURES APPROVED BY SUBMITTED ORIGINAL PAPER
 ENGINEERING LETTER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By rmcphers Date 2020-07-16 Time 08:53 Rev Time 0.00
Received By rmcphers Date 2020-07-16 Time 08:53 Sent To  
Notes
2020-07-16 08:55:20ANY ADDED SIGNED AND SEALED DOCUMENTS = SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)