| 2020-08-06 09:20:55 | 08/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. THE SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW PER THE |
| | 61G15-23.005. |
| | |
| | 2. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| | PALM BEACH ORD #2853-95. A DUAL CHECK VALVE MAY BE USED |
| | IF NO POOL FILL IS INSTALLED AT THE METER AND INSTALLED |
| | BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO PLEASE |
| | CONTACT THE CITY OF WPB UTILITIES AT 561-822-2240 FOR |
| | FURTHER DIRECTIONS. |
| | |
| | 3. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM |
| | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. PLEASE SHOW YOUR CALCULATED WORK. |
| | |
| | 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMP |
| | AND THE FILTER PER THE WPB AMENDMENTS TO FBC SEC. |
| | 107.2.1. |
| | |
| | 5. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 6. ON SHEET 06 YOU HAVE INFORMATION ON A HEATER IF |
| | THERE IS NOT ONE PLEASE DELETE THIS INFORMATION BUT |
| | THAT BE THE CASE THAT THEY WILL PUT ON IN PLEASE |
| | PROVIDE MANUFACTURES SPECIFICATION PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |