Plan Review Details - Permit 20061453
Plan Review Stops For Permit 20061453
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By jleahy Date 2020-08-20 Time 17:08 Rev Time 0.00
Received By jleahy Date 2020-08-20 Time 17:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By jleahy Date 2020-08-05 Time 14:08 Rev Time 0.00
Received By jleahy Date 2020-08-05 Time 14:08 Sent To  
Notes
2020-08-05 14:09:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT CUT SHEETS FOR ACCESS CONTROL SYSTEM.
  
 PLANS NOT SIGNED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By pleduc Date 2020-08-14 Time   Rev Time 0.00
Received By pleduc Date 2020-08-14 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By pleduc Date 2020-07-16 Time   Rev Time 0.00
Received By pleduc Date 2020-07-16 Time 13:00 Sent To  
Notes
2020-07-16 13:10:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS THAT THERE ARE CARD READERS
 BEING INSTALLED ON EGRESS DOORS: HOWEVER, THERE ARE NO
 INDICATIONS THAT THE INSTALL WILL COMPLY WITH THE
 REQUIRMENTS OF NFPA 101, CH 7 MEANS OF EGRESS.
  
 PER NFPA 01 CH 7
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 2) THERE APPEARS TO BE A KEYPAD (KP) AT THE EXIT DOORS.
  
 PLEASE PROVIDE A DETAILED NARRATIVE ABOUT THIS THIS KP
 IS TO FUNCTION IN THE PATH OF EGRESS AND HOW THAT IT
 WILL COMPLY WITH NFPA 101 CH 7
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR
 ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE
 ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED
 HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN
 THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY IN
 THE DIRECTION OF EGRESS.
 (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF
 EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PLEASE REVIEW AND PROVIDE COMPLIANT DETAILLS
  
  
  
  
 3) THERE ARE NO INDICATIONS OF MANUFACTURE
 SPECIFICATION SHEETS.
  
 PLEASE PROVIDE
  
  
  
 4) THERE ARE NO INDICATIONS OF WIRING
  
 PLEASE PROVIDE
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By jleahy Date 2020-08-20 Time 17:08 Rev Time 0.00
Received By jleahy Date 2020-08-13 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-05 Cont ID  
Sent By jleahy Date 2020-08-05 Time 14:11 Rev Time 0.00
Received By jleahy Date 2020-07-15 Time 17:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-20 Cont ID  
Sent By jleahy Date 2020-08-20 Time 17:08 Rev Time 0.00
Received By jleahy Date 2020-08-20 Time 17:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By jleahy Date 2020-08-05 Time 14:09 Rev Time 0.00
Received By jleahy Date 2020-08-05 Time 14:09 Sent To  
Notes
2020-08-05 14:10:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED.
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. FS
 471.003(2)(H); 471.025; FBC 107.2.1