| 2020-07-16 13:10:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS THAT THERE ARE CARD READERS |
| | BEING INSTALLED ON EGRESS DOORS: HOWEVER, THERE ARE NO |
| | INDICATIONS THAT THE INSTALL WILL COMPLY WITH THE |
| | REQUIRMENTS OF NFPA 101, CH 7 MEANS OF EGRESS. |
| | |
| | PER NFPA 01 CH 7 |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 2) THERE APPEARS TO BE A KEYPAD (KP) AT THE EXIT DOORS. |
| | |
| | PLEASE PROVIDE A DETAILED NARRATIVE ABOUT THIS THIS KP |
| | IS TO FUNCTION IN THE PATH OF EGRESS AND HOW THAT IT |
| | WILL COMPLY WITH NFPA 101 CH 7 |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR |
| | ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO |
| | BE |
| | ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, LISTED |
| | HARDWARE, |
| | PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO |
| | THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS |
| | READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN |
| | THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY |
| | DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR |
| | ASSEMBLY IN |
| | THE DIRECTION OF EGRESS. |
| | (5) *LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF |
| | EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | |
| | PLEASE REVIEW AND PROVIDE COMPLIANT DETAILLS |
| | |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF MANUFACTURE |
| | SPECIFICATION SHEETS. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 4) THERE ARE NO INDICATIONS OF WIRING |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |