Plan Review Details - Permit 20061444
Plan Review Stops For Permit 20061444
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2020-10-21 Cont ID  
Sent By rmcdouga Date 2020-10-21 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2020-10-21 Time 09:08 Sent To  
Notes
2020-10-21 09:17:15APPROVED WITH EXCEPTIONS. BUILDING PROVISO.
  
 1) A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR THE FABRIC AND ITS ATTACHMENT TO THE THE
 METAL FRAMES. THE FABRIC SCEEN MEMBRANE SHALL BE
 DESIGNED FOR QUICK REMOVAL OR BREAKAWAY AT WIND
 VELOCITIES OF 75 MPH. FBC 107 & 3105.4
  
 2) WORKING CLEARANCES SHALL BE MAINTAINED AROUND THE
 EQUIPMENT THAT IS BEING SCREENED. FBCM 303.12 & FBC 107
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-08-20 Cont ID  
Sent By rmcdouga Date 2020-08-20 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2020-08-20 Time 15:18 Sent To  
Notes
2020-08-20 15:22:29PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 PREVIOUS COMMENT WAS NOT ADDRESSED. THE DRAWINGS NEED
 TO BE SIGNED AND SEALED BY THE DELEGATED ENGINEER AND
 THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED TO
 REVIEW AND APPROVE THE DESIGN AND PLACE THEIR SHOP
 DRAWING REVIEW STAMP ON THE DRAWINGS. SHEETS S-1, S-2,
 S-3 & S-4 ARE NOT SIGNED BY THE ENGINEER WHOSE NAME,
 MILTON CUBAS P.E., APPEARS ON THE DRAWINGS.
  
 1) THE WIND SCREEN DRAWINGS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT
 (SHOP DRAWING REVIEW). FBC CITY AMENDMENTS 107.3.4
  
 2) THIS PERMIT IS FOR THE INSTALLATION OF THE METAL
 FARMES ONLY. NO INFORMATION HAS BEEN PROVIDED FOR THE
 FABRIC COVERING AND IT'S ATTACHMENT OR REMOVAL. A
 SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR THE FABRIC AND ITS ATTACHMENT TO THE THE
 METAL FRAMES. FBC 107
  
 3) IT WILL BE HELPFUL TO PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-07-31 Cont ID  
Sent By rmcdouga Date 2020-07-31 Time 16:00 Rev Time 0.00
Received By rmcdouga Date 2020-07-31 Time 15:35 Sent To  
Notes
2020-07-31 16:04:44PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 PREVIOUS COMMENT WAS NOT ADDRESSED. THE DRAWINGS NEED
 TO BE SIGNED AND SEALED BY THE DELEGATED ENGINEER AND
 THE DESIGNER OF RECORD FOR THE PROJECT IS REQUIRED TO
 REVIEW AND APPROVE THE DESIGN AND PLACE THEIR SHOP
 DRAWING REVIEW STAMP ON THE DRAWINGS.
  
 1) THE WIND SCREEN DRAWINGS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 FBC CITY AMENDMENTS 107.3.4
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By rmcdouga Date 2020-07-17 Time 13:12 Rev Time 0.00
Received By rmcdouga Date 2020-07-17 Time 13:12 Sent To  
Notes
2020-07-17 13:13:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND SCREEN DRAWINGS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 FBC CITY AMENDMENTS 107.3.4
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-07 Cont ID  
Sent By rmcdouga Date 2020-07-07 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2020-07-07 Time 08:02 Sent To  
Notes
2020-07-07 08:18:57APPROVED WITH EXCEPTIONS. BUILDING PROVISO.
  
 1) A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR THE FABRIC AND ITS ATTACHMENT TO THE THE
 METAL FRAMES. FBC 107
  
 2) WORKING CLEARANCES SHALL BE MAINTAINED AROUND THE
 EQUIPMENT THAT IS BEING SCREENED. FBCM 303.12 & FBC 107
  
 WELDING COMMENTS
  
 AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S.
 SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING:
 BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO
 BE USED.
  
 AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE
 PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE
 W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO
 VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS
 IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-10-21 Cont ID  
Sent By rmcdouga Date 2020-10-21 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2020-10-14 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-20 Cont ID  
Sent By rmcdouga Date 2020-08-20 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2020-08-10 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-31 Cont ID  
Sent By rmcdouga Date 2020-07-31 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2020-07-29 Time 09:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-20 Cont ID  
Sent By shill Date 2020-07-20 Time 09:25 Rev Time 0.00
Received By shill Date 2020-07-13 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-07 Cont ID  
Sent By lmarchan Date 2020-07-07 Time 10:20 Rev Time 0.00
Received By lmarchan Date 2020-06-30 Time 12:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-10-21 Cont ID  
Sent By rmcdouga Date 2020-10-21 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2020-10-21 Time 09:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-08-20 Cont ID  
Sent By rmcdouga Date 2020-08-20 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2020-08-20 Time 15:18 Sent To  
Notes
2020-08-20 15:21:14THE 4 PAGES OF STRUCTURAL DRAWINGS FROM MILTON CUBAS
 P.E. ARE NOT SIGNED AS REQUIRED BY FS 471 & FAC 61G-15.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-07-31 Cont ID  
Sent By rmcdouga Date 2020-07-31 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2020-07-31 Time 16:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By rmcdouga Date 2020-07-17 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2020-07-17 Time 13:05 Sent To  
Notes
2020-07-17 13:06:29THE ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 BE DIGITALLY SIGNED BY THE ENGINEER. FS 471 AND FAC
 61G15
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By rmcdouga Date 2020-07-07 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2020-07-07 Time 08:02 Sent To  
Notes
2020-07-07 08:05:18THE ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 BE DIGITALLY SIGNED BY THE ENGINEER. FS 471 AND FAC
 61G15

Review Stop Z ZONING
Rev No 4 Status P Date 2020-08-19 Cont ID  
Sent By aaponte Date 2020-08-19 Time 09:29 Rev Time 0.00
Received By aaponte Date 2020-08-19 Time 09:29 Sent To  
Notes
2020-08-19 09:29:43PROVISO: SCREEN SHALL FULLY OBSCURE ANY MECHANICAL
 EQUIPMENT LOCATED ON THE ROOF FROM ANY SURROUNDING
 VIEW.
 SCREEN SHALL BE AS TALL AS THE EQUIPMENT.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-08-13 Cont ID  
Sent By aaponte Date 2020-08-13 Time 15:57 Rev Time 0.00
Received By aaponte Date 2020-08-13 Time 15:57 Sent To  
Notes
2020-08-13 15:58:00PROVISO: SCREEN SHALL FULLY OBSCURE ANY MECHANICAL
 EQUIPMENT LOCATED ON THE ROOF FROM ANY SURROUNDING
 VIEW.
 SCREEN SHALL BE AS TALL AS THE EQUIPMENT.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By aaponte Date 2020-07-17 Time 14:49 Rev Time 0.00
Received By aaponte Date 2020-07-17 Time 14:49 Sent To  
Notes
2020-07-17 14:54:27PROVISO: 1. ALL MECHANICAL EQUIPMENT SHALL BE SCREENED
 FROM VIEW FROM SURROUNDING BUILDINGS WITH A SCREEN AS
 TALL AS THE EQUIPMENT.
 2. SCREEN SHALL BE SUFFICIENTTLY OPAQUE NOT TO ALLOW
 THE VIEW OF THE EQUIPMENT BEHIND. IF PROPOSED SCREEN
 STILL ALLOWS THE VIEW OF THE EQUIPMENT, SCREEN SHALL BE
 REPLACED FOR A MORE SOLID MATERIAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-01 Cont ID  
Sent By aaponte Date 2020-07-01 Time 15:21 Rev Time 0.00
Received By aaponte Date 2020-07-01 Time 15:21 Sent To  
Notes
2020-07-01 15:25:241.PLEASE SUBMIT BUILDING ELEVATIONS THAT INCLUDE THE
 EXISTING MECHANICAL EQUIPMENT TO BE SCREENED. INDICATE
 THE HEIGHT OF THE MECHANICAL EQUIPMENT AND THE LOCATION
 OF THE SCREEN.
 2. PLEASE PROVIDE PICTURES AND A SAMPLE OF PROPOSED
 SCREEN.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.