Plan Review Details - Permit 20061422
Plan Review Stops For Permit 20061422
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 12:42 Rev Time 0.00
Received By cthroop Date 2020-07-30 Time 12:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By cthroop Date 2020-07-17 Time 15:26 Rev Time 0.00
Received By cthroop Date 2020-07-17 Time 15:19 Sent To  
Notes
2020-07-17 15:36:49PLAN REVIEW ? GENERATOR - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD. PROVIDE
 RE-INFORCING DETAILS OR AT A MINIMUM, PROVIDE CRACK
 CONTROL METHOD.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 12:43 Rev Time 0.00
Received By cthroop Date 2020-07-30 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By cthroop Date 2020-07-17 Time 15:40 Rev Time 0.00
Received By cthroop Date 2020-07-17 Time 15:19 Sent To  
Notes
2020-07-17 15:43:08PLAN REVIEW ? GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE CABLE SIZES AND TYPE OF ATS CONTROL CIRCUT
 ON ELECTRICAL RISER.
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 11:21 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 11:21 Sent To  
Notes
2020-07-30 11:22:02GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By cthroop Date 2020-07-17 Time 15:30 Rev Time 0.00
Received By cthroop Date 2020-07-17 Time 15:19 Sent To  
Notes
2020-07-17 15:31:54PLAN REVIEW ? GENERATOR - ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) GAS ISOMETRIC DRAWING:
  
 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH APPLIANCE AND THE
 LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE
 DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3. PROVIDED
 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC
 RES.
  
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1. SHOW THAT THIS REGULATOR MEETS
 ANSI Z21.80. FBC RES G2421.1
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 12:43 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-20 Cont ID  
Sent By shill Date 2020-07-20 Time 09:23 Rev Time 0.00
Received By shill Date 2020-07-01 Time 11:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By lcrespo Date 2020-07-30 Time 11:22 Rev Time 0.00
Received By lcrespo Date 2020-07-30 Time 11:22 Sent To  
Notes
2020-07-30 11:23:50ELECTRICAL CONTRACTOR SAID A SEPERATE PERMIT WILL BE
 APPIED FOR FROM A PLUMBING CONTRATOR NOT KNOWN YET

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-17 Cont ID  
Sent By cthroop Date 2020-07-17 Time 15:43 Rev Time 0.00
Received By cthroop Date 2020-07-17 Time 15:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 12:43 Rev Time 0.00
Received By cthroop Date 2020-07-30 Time 12:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By cthroop Date 2020-07-17 Time 15:37 Rev Time 0.00
Received By cthroop Date 2020-07-17 Time 15:19 Sent To  
Notes
2020-07-17 15:40:13PLAN REVIEW ? GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONTRACTORS SHALL PRINT NAME AND SIGN PLANS.
  
 NON-DESIGN PROFESSIONALS
  
 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON PLAN SHEETS UNDER THEIR
 AUTHORITY ?
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-07-17 Time   Rev Time  
Received By   Date 2020-07-17 Time   Sent To I
Notes
***NONE***