Plan Review Details - Permit 20061417
Plan Review Stops For Permit 20061417
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By cpuell Date 2020-08-03 Time 10:09 Rev Time 0.00
Received By cpuell Date 2020-08-03 Time 10:09 Sent To  
Notes
2020-08-03 10:12:56THE NEW TENANT PLANTA RESTAURANT HAS TAKEN OVER 2
 SPACES THAT WERE OCCUPIED BY PANERA BREAD AND THE
 VILLAGE GOURMET CHEESE SHOPPE - SUITE ESTABLISHED AS
 140

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By jwitmer Date 2020-07-21 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2020-07-21 Time 07:29 Sent To  
Notes
2020-07-21 11:31:25IN BY MISTAKE. THE TENANT BUILD OUT NEEDS TO IDENTIFY
 THE TENANT ADDRESS TENANT ADDRESS ON THE APPLICATION.
 THE PLANS INDICATE THE ADDRESS AS 700 S. ROSEMARY
 TENANT SPACE AS B-17/ B17B. THE TENANT SUITE HAS TO
 MEET THE MAILING ADDRESS STANDARD WITH NO APHA
 (LETTERS) ONLY NUMERIC (NUMBERS), EXAMPLE SUITE 114
 FIRST FLOOR OR 214 FORTHE 2ND FLOOR.
 JIM WITMER BUILDING PLAN REVIEW.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By jwitmer Date 2020-07-21 Time 07:32 Rev Time 0.00
Received By jwitmer Date 2020-07-21 Time 07:30 Sent To  
Notes
2020-07-21 07:33:40CITY PLACE NEW BUILDINGS BUILT IN 1997-1998. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-28 Cont ID  
Sent By jwitmer Date 2020-09-28 Time 10:16 Rev Time 0.00
Received By jwitmer Date 2020-09-28 Time 09:00 Sent To  
Notes
2020-09-28 10:14:48WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061417
 ADD: 700 S. ROSEMARY AVE. UNIT: 140
 CONT: MOCCA CONSTRUCTION
 TEL: 305-964-8440
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. SEPT. 27TH/ 2020
 ACTION: BUILDING PROVISO
  
 1) BUILDING PROVISO: THE STRUCTURAL SHEETS SHOW THE USE
 OF WELDED AND BOLTED CONNECTIONS. THE SHEET S0.0
 STRUCTURAL NOTES REQUIRE SPECIAL INSPECTIONS DONE BY
 3RD PARTY CERTIFICATION, FOR WELDED & BOLTED
 CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTAL SHEET
 S0.00SPECIALTY ENGINEERING NOTE G. MECHANICAL TIE-DOWNS
 TO SUPERSTRUCTURE, MECHANICAL SUPPORT CURBS, MECHANICAL
 DUCT SUPPORTS, PIPING SUPPORTS, HANGING EQUIPMENT
 SUPPORTS AND ALL ASSOCIATED CONNECTIONS TO THE
 SUPERSTRUCTURE ARE ALL ASSIGNED TO THE SPECIALTY
 ENGINEER.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
 3) BUILDING PROVISO/ DEFERRED SUBMITTAL: THE ROOF STAND
 NOA: 17-1218.02. / SPECIALTY ENGINEER. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW. PLEASE PROVIDE THE MIAMI-DADE NOA. THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT, FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-11 Cont ID  
Sent By jwitmer Date 2020-09-11 Time 17:43 Rev Time 0.00
Received By jwitmer Date 2020-09-11 Time 16:02 Sent To  
Notes
2020-09-11 17:39:46WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061417
 ADD: 700 S. ROSEMARY AVE. UNIT: B-17
 CONT: MOCCA CONSTRUCTION
 TEL: 305-964-8440
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. SEPT.11/ 2020
 ACTION: DENIED
  
 1) BUILDING PROVISO: THE STRUCTURAL SHEETS SHOW THE USE
 OF WELDED AND BOLTED CONNECTIONS. THE SHEET S0.0
 STRUCTURAL NOTES REQUIRE SPECIAL INSPECTIONS DONE BY
 3RD PARTY CERTIFICATION, FOR WELDED & BOLTED
 CONNECTIONS. WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 2) COMPLIED. MEAN ROOF HEIGHT OF 38.5?.
  
 3) SEMI COMPLIED. PRESSURES USING ASCE 7-10 FIGURE
 30-5.1 @ 10 SQ. FT.:
 ROOF ZONE 1 +18.27 / -45.4
 ROOF ZONE 2 +18.7 / -76.16
 ROOF ZONE 3 +18.7 / -114.6
  
 1ST ROUND COMMENTS. THE STRUCTURAL SHEET S0.0 PROVIDE A
 COMPONENTS AND CLADDING CHART FOR ROOF ZONES 1, 2, & 3.
 THE CHART NOR THE WIND DESIGN CRITERIA DOES NOT
 INDICATE THE MEAN ROOF HEIGHT, NOR DOES THE COMPONENTS
 AND CLADDING CHART INDICATE AT WHAT SQUARE FEET THESE
 PRESSURES ARE GIVEN? PRESSURES GIVEN FOR COMPONENTS &
 CLADDING FOR ROOFING MATERIALS ARE USUALLY TAKEN FOR 10
 SQUARE FEET, WORST CASE SCENARIO.
  
 4) SHEET M7.2 :
 4A) COMPLIED.
  
 4B) BUILDING PROVISO/ DEFERRED SUBMITTAL SHEET
 S0.00SPECIALTY ENGINEERING NOTE G. MECHANICAL TIE-DOWNS
 TO SUPERSTRUCTURE, MECHANICAL SUPPORT CURBS, MECHANICAL
 DUCT SUPPORTS, PIPING SUPPORTS, HANGING EQUIPMENT
 SUPPORTS AND ALL ASSOCIATED CONNECTIONS TO THE
 SUPERSTRUCTURE ARE ALL ASSIGNED TO THE SPECIALTY
 ENGINEER.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 4C) COMPLIED.
  
 4D-F) BUILDING PROVISO/ DEFERRED SUBMITTAL: THE ROOF
 STAND NOA: 17-1218.02. / SPECIALTY ENGINEER.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW. PLEASE PROVIDE THE MIAMI-DADE NOA.
 THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT, FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. 61G1-23.015 (2)
 THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
  
 5) COMPLIED.
  
 6) SHEET A-201 & A-202:
 6A) COMPLIED.
  
 6B)COMPLIED, WILL SERVE FREE DRINKING WATER, EXEMPT
 FROM 410.4 PLUMB. CODE.
  
 7) SEMI-COMPLIED. RESPONSE NOW SHOWS A ACCESSIBLE SEAT
 AT THE OUTSIDE BAR, BUT A DETAIL IS NEEDED TO SHOW THE
 DROPPED COUNTER TOP IN COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 902.3 HEIGHT. THE TOPS
 OF DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 1ST ROUND COMMENTS. SHEET G-004/ LA001 SHOWS THE
 LOCATION OF THE ACCESSIBLE SEATING ON THE INTERIOR AND
 EXTERIOR OF THE BUILDING. IN MOST CASES THE ACCESSIBLE
 SEATING MEETS THE ACCESSIBILITY REQUIREMENT OF
 DISPERSION OF THE ACCESSIBLE SEATING EXCEPT FOR BAR 003
 SEATING ON THE EXTERIOR PORTION OF THE BAR.
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7A) SEMI-COMPLIED. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 7B) SEMI-COMPLIED. 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By jwitmer Date 2020-07-21 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2020-07-21 Time 07:29 Sent To  
Notes
2020-07-21 07:34:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061417
 ADD: 700 S. ROSEMARY AVE. UNIT: B-17
 CONT: MOCCA CONSTRUCTION
 TEL: 305-964-8440
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 21/ 2020
 ACTION: DENIED
  
 1) THE STRUCTURAL SHEETS SHOW THE USE OF WELDED AND
 BOLTED CONNECTIONS. THE SHEET S0.0 STRUCTURAL NOTES
 REQUIRE SPECIAL INSPECTIONS DONE BY 3RD PARTY
 CERTIFICATION, FOR WELDED & BOLTED CONNECTIONS. WELDED
 OR BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 2) THE STRUCTURAL SHEET S0.0 PROVIDES A PORTION OF THE
 WIND DESIGN CRITERIA BUT DOES NOT INCLUDE WHAT THE MEAN
 ROOF HEIGHT IS AT?
 2017 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1.
  
 3) THE STRUCTURAL SHEET S0.0 PROVIDE A COMPONENTS AND
 CLADDING CHART FOR ROOF ZONES 1, 2, & 3. THE CHART NOR
 THE WIND DESIGN CRITERIA DOES NOT INDICATE THE MEAN
 ROOF HEIGHT, NOR DOES THE COMPONENTS AND CLADDING CHART
 INDICATE AT WHAT SQUARE FEET THESE PRESSURES ARE GIVEN?
 PRESSURES GIVEN FOR COMPONENTS & CLADDING FOR ROOFING
 MATERIALS ARE USUALLY TAKEN FOR 10 SQUARE FEET, WORST
 CASE SCENARIO.
  
 4) SHEET M7.2 :
 4A) THE ROOF TOP CURB DETAIL SHOWS A STRUCTURAL
 CONCRETE ROOF DECK AND THE ANCHORING OF THE CURB WITH
 CONCRETE ANCHORS, TAPCONS. SHEET S1.01 DETAILS 1 & 2
 BOTH SHOW A COMPOSITE ROOF DECK. DISCREPANCY IN PLANS.
 107.2.1. ADDITIONAL INFORMATION IS REQUIRED.
  
 4B) SHEET M7.2 NOTE # 9 STATES FOR ANCHORING PROVIDE
 NUMBER & SIZE OF FASTENERS/ ATTACHMENTS AS RECOMMENDED
 BY THE STRUCTURAL ENGINEER. NO CALCULATIONS WERE
 PROVIDED BY THE STRUCTURAL ENGINEER FOR THE ROOF TOP
 EQUIPMENT.
  
 4C) THEE IS A SPECIAL NOTE ON THE PLANS REFERENCING
 SECTION 1620 OF THE 2017 FBC-B. THE NOTE REFERENCING TO
 CODE SECTION 1620 IS WITHIN THE HIGH VELOCITY HURRICANE
 ZONES BROWARD & MIAMI-DADE COUNTY AND UN-ENFORCEABLE
 ELSEWHERE IN FLORIDA COUNTIES. IF THE DESIGNER WISHES
 TO ENFORCE IT THAT IS FINE BUT AS THE BUILDING
 DEPARTMENT WE CANNOT REQUIRE ENFORCEMENT.
  
 4D) THE ROOF STAND IS IDENTIFIED AS NOA: 17-1218.02.
 PLEASE PROVIDE THE MIAMI-DADE NOA. THE ROOF TOP A/C
 STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE DESIGNER
 OF RECORD. PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS
 CALCULATING THE AREA (SIDE VIEW) OF THE ROOF TOP
 COMPRESSORS, CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT
 VERSES MOMENT FOR THE UNIT TO THE STAND AND THE STAND
 TO THE ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY
 THE DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4E) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4F) NOTE # 3. THE CONTRACTOR TO PROVIDE WIND LOAD
 CALCULATIONS SIGNED & SEALED BY FL. REGISTERED
 STRUCTURAL ENGINEER FOR NON-APPROVED CONFIGURATIONS.
  
 5) WITH THE ADDITIONAL ROOF TOP EQUIPMENT BEING ADDED
 TO THE ROOF HOW WILL ACCESS BE GAINED TO THE EQUIPMENT,
 ALL ABOVE 16 FEET ABOVE GRADE? 2017 FBC-M 306.5
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE
 LOCATED ON AN ELEVATED STRUCTURE OR THE ROOF OF A
 BUILDING SUCH THAT PERSONNEL WILL HAVE TO CLIMB HIGHER
 THAN 16 FEET (4877 MM) ABOVE GRADE TO ACCESS SUCH
 EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR MEANS
 OF ACCESS SHALL BE PROVIDED. SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30
 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS HAVING A
 SLOPE GREATER THAN 4 UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT
 REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 6) SHEET G-004:
 6A) BOTH DETAILS 604.5.1 SIDEWALL GRAB BARS & 604.5.2
 DETAIL REAR WALL GRAB BAR DETAIL DO NOT PROVIDE
 COMPLIANCE WITH THE VERTICAL HEIGHT REQUIREMENT. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE. SHEETS A-201 WOMENS RESTROOM &
 SHEET A-202 MENS RESTROOM BOTH SHOW THE GRAB BARS
 MEASURED TO THE CENTERLINE NOT THE TOP OF THE BAR THE
 GRASPING SURFACE.
  
 6B) DRINKING FOUNTAIN DETAIL FIG. 602.5 AND SECTION
 502.5 SPOUT LOCATION / HEIGHT DETAIL. THERE ARE NO
 DETAILS FOR COMPLIANCE WITH:
  
 6B)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 6B)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY IN TO THE
 CIRCULATION PATH.
  
 6B)(3) 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 7) SHEET LA001 SHOWS THE LOCATION OF THE ACCESSIBLE
 SEATING ON THE INTERIOR AND EXTERIOR OF THE BUILDING.
 IN MOST CASES THE ACCESSIBLE SEATING MEETS THE
 ACCESSIBILITY REQUIREMENT OF DISPERSION OF THE
 ACCESSIBLE SEATING WITH THE EXCEPTION OF BAR 003
 SEATING ON THE EXTERIOR PORTION OF THE BAR.
 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 7A) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 7B) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 16:17 Rev Time 0.00
Received By jleahy Date 2020-09-21 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-17 Cont ID  
Sent By jleahy Date 2020-08-17 Time 12:30 Rev Time 0.00
Received By jleahy Date 2020-08-17 Time 12:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-14 Cont ID  
Sent By jleahy Date 2020-08-14 Time 16:25 Rev Time 0.00
Received By jleahy Date 2020-08-14 Time 16:00 Sent To  
Notes
2020-08-14 16:25:56PAGES E02 AND EO3 ARE NOT ABLE TO BE OPENED JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-15 Time 10:44 Sent To  
Notes
2020-07-17 12:33:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET QF 703 - THERE ARE INDICATIONS OF A HOOD
 SYSTEM. THE INSTALL OF THE HOOD SYSTEM ON THIS PERMIT
 IS FOR REFERENCE PURPOSES AND IS NOT APPROVED FOR
 INSTALL UNDER THIS PERMIT.
  
 THE HOOD SYSTEM SHALL BE SUBMITTED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 2) SHEET QF 705 - THERE ARE INDICATIONS OF A FIRE
 SUPPRESSION SYSTEM. THE INSTALL OF THE FIRE SUPPRESSION
 SYSTEM ON THIS PERMIT IS FOR REFERENCE PURPOSES AND IS
 NOT APPROVED FOR INSTALL UNDER THIS PERMIT.
  
 THE FIRE SUPPRESSION SYSTEM SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By lcrespo Date 2020-09-17 Time 09:11 Rev Time 0.00
Received By lcrespo Date 2020-09-17 Time 09:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-08-17 Cont ID  
Sent By lcrespo Date 2020-08-17 Time 16:36 Rev Time 0.00
Received By lcrespo Date 2020-08-17 Time 16:36 Sent To  
Notes
2020-08-17 17:19:0308/17/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON ISOMETRIC LABEL CLEARLY AND SHOW THE LENGTH OF
 ALL CUT SECTIONS OF PIPE, FOR EACH PIPE SIZE PER THE
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 2. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE AND GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2017 FBC FG SECS. 402.2 AND 301.3.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS PER THE 2017 FBC FG SEC. 410.1.
  
 5. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC FG SEC
 410.2.
  
 6. LABEL SHUTOFF VALVE ON GAS ISOMERIC PER THE 2017 FBC
 FG SEC. 409.4.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC FG SEC. 304.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
  
 8. SHOW UNIONS ON EMERGENCY HOOD SHUT DOWN SHUTOFF
 VALVE, UNION TO BE DOWNSTREAM OF MANUAL VALVE. SECS.
 10.4, 10.5 OF NFPA 96-08.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-02 Cont ID  
Sent By lmarchan Date 2020-10-02 Time 11:21 Rev Time 0.00
Received By lmarchan Date 2020-09-25 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-21 Cont ID  
Sent By ccarvaja Date 2020-09-21 Time 16:18 Rev Time 0.00
Received By jleahy Date 2020-09-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By lcrespo Date 2020-08-18 Time 17:03 Rev Time 0.00
Received By lcrespo Date 2020-08-18 Time 17:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-09-25 Cont ID  
Sent By lmarchan Date 2020-09-25 Time 09:39 Rev Time 0.00
Received By lmarchan Date 2020-09-24 Time 07:33 Sent To  
Notes
2020-09-25 09:39:53NO FEES DUE - PLANS STAMPED
2020-09-24 07:33:339/24/20 EMAILED IMPACT OFFICE FOR REVIEW WITHOUT
 QUESTIONNAIRE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By jwitmer Date 2020-07-21 Time 11:31 Rev Time 0.00
Received By lcrespo Date 2020-08-18 Time 17:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By hmoser Date 2020-09-21 Time 11:23 Rev Time 0.00
Received By hmoser Date 2020-09-21 Time 10:36 Sent To  
Notes
2020-09-21 11:22:51SEPARATE PERMITS REQUIRED FOR KITCHEN HOODS
 AND WALK IN COOLERS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-85-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-07 Cont ID  
Sent By hmoser Date 2020-08-07 Time 08:59 Rev Time 0.00
Received By hmoser Date 2020-08-06 Time 12:36 Sent To  
Notes
2020-08-07 08:59:24PLAN DENIED
 1) PROVIDE SUITE NUMBER ON PLAN AND APPLICATION
 SECTION 107 FBC 2017
 2) SEPARATE APPLICATION, PLANS AND PERMITS REQUIRED
 FOR HOODS AND REFRIGERATION. SECTION 107 FBC 2017
 3) HEATING COOLING LOAD CALCULATIONS REQUIRED
 REFER TO SECTION 312.1 LOAD CALCULATIONS FBC (M) 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-09-17 Cont ID  
Sent By lcrespo Date 2020-09-17 Time 09:13 Rev Time 0.00
Received By lcrespo Date 2020-09-17 Time 09:13 Sent To  
Notes
2020-09-17 09:14:2309/17/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By lcrespo Date 2020-08-18 Time 16:41 Rev Time 0.00
Received By lcrespo Date 2020-08-14 Time 16:03 Sent To  
Notes
2020-08-18 16:43:4808/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. IN SHEET 001 COVER UNDER APPLICABLE CODES PLEASE
 REFER TO THE 6TH EDITION 2017 FBC FUEL GAS CODE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION.
  
 3. SHEET G-004, G005 AND G-006 ON ADA GUIDELINE;
  
 A. ITEM 1, IT REFERS TO 2014, PLEASE CORRECT AND CHANGE
 TO 2017.
  
 B. ITEM 2, REFERS TO FFPC 5TH EDITION PLEASE CHANGE TO
 THE 6TH EDITION.
  
 C. ITEM 7, SHOULD REFERENCE TEMPERED WATER REQUIRED OF
 110 DEGREES WITH AN ASSE 1070 DEVICE IN ACCORDANCE WITH
 THE 2017 FBC SEC. FBC P 607.1.2.
  
 D. ITEM 10, DOOR HANDLE HARDWARE SHOULD BE NOTED ON
 BOTH SIDES OF THE DOOR PER THE 2017 FBC ACC SEC.
 404.2.7.
  
 E. ITEM 11, SHOULD BE REFERENCED TO 2017 FBC ACC SEC.
 604.4.
  
 F. ITEM 12 AND 13, PLEASE PROVIDE CODE REFERENCE THAT
 APPLIES TO WHAT IS BEING REFERRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. ITEM 18, REFERS TO S.F.B.C. PLEASE CHANGE TO 2017
 FBC BUILDING SEC. 1210.2.2.
  
 H. PLEASE NOTE THAT OTHER ITEMS MAY NEED TO BE
 ADDRESSED AS THE LIST IS MANY TO MENTION.
  
 4. SHEET 201 WOMAN'S RESTROOM;
  
 A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL
 AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC
 SEC. 608.1.2.
  
 B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEEDS TO SHOW
 THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC
 SEC. 305.3.
  
 C. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB
 BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE
 ACCORDING TO 2017 FBC ACC.
  
 D. IN DETAIL 4, THE TOILET IN THE STALL NEEDS TO BE 17"
 TO 19" INCHES PER 2017 FBC ACC SEC. 604.4.
  
 E. IN DETAIL 4, OPEN FLOOR LAV THE MIRRORS NEED TO AT
 LEAST 40" PER THE 2017 FBC ACC SEC. 603.3.
  
 F. IN DETAIL B, THE REFLECTIVE PART OF THE MIRROR NEEDS
 TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017
 FBC ACC SEC. 603.3.
  
 G. PLEASE SHOW ALL DIMENSIONS FOR ALL DETAIL OF CLEAR
 FLOOR SPACE ON ALL DETAILS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. SHEET 202 MEN?S RESTROOM;
  
 A. IN DETAIL A, THE DOOR IS SWINGING INSIDE THE STALL
 AND IT WILL NEEDS TO SWING OUTWARDS PER THE 2017 FC ACC
 SEC. 608.1.
  
 B. IN DETAIL A, THE LAV ON THE OPEN FLOOR NEED TO SHOW
 THE CLEAR FLOOR SPACE OF 30" X 48" PER THE 2017 FBC
 SEC. 305.3.
  
 C. IN DETAIL 2, THE TOILET IN THE STALL NEEDS TO BE 17"
 TO 19" INCHES PER 2017 FBC ACC SEC. 604.4.
  
 D. IN DETAIL 2, AT LEAST ONE OF THE TWO URINALS SHALL
 BE 17" MIN PLEASE SHOW DIMENSION PER THE 2017 FBC ACC.
 SEC. 605.2.
  
 E. IN DETAIL 2, THE REFLECTIVE PART OF THE MIRROR NEEDS
 TO BE THE OF 40" TO THE REFLECTIVE SIDE PER THE 2017
 FBC ACC SEC. 603.3.
  
 F. IN DETAIL 2, SHOW THE HEIGHT FOR ALL PARTITIONS IN
 BETWEEN THE 2017 FBC SEC. P 405.3.5.
  
 G. IN DETAIL 5, THE HEIGHT OF TOILET OF, MIRROR, GRAB
 BARS AND UNDER LAV ARE MISSING DIMENSIONS PLEASE PROVE
 ACCORDING TO 2017 FBC ACC.
  
 6. SHEET 043 P-1;
  
 A. TEMPERED WATER DETAIL FOR LAV IS SAYING WATER AT 105
 DEGREES PLEASE CHANGE TO 110 PER THE 2017 FBC SEC. P
 607.1.2.
  
 B. IN TYPICAL PLUMBING FIXTURES UNDER COFFEE MAKER/ICE
 MAKER REQUIRES AN INLINE VACUUM BREAKER THAT COMPLIES
 WITH THE ASSE 1024 NON-CARBONATED.
  
 C. IN THAT SAME DETAIL, IT CALLS OUT A WASHING MACHINE
 WHICH WILL REQUIRE A LINT TRAP PLEASE SUPPLY DETAILS OR
 NOTE PER THE 2017 FBC SEC. 1003.6.
  
 D. SODA DRINKING BEVERAGE MACHINES SHALL BE PROTECTED
 WITH A DEVICE THAT COMPLIES WITH ASSE 1022 SHALL HAVE
 CARBONATED DISCHARGED TO A SAFE LOCATION PER THE 2017
 FBC SEC. P 608.16.1.
  
 7. SHEET 044 P2-1;
 A. SERVICE SINK (MOP SINK) SURROUNDING WALL SHALL BE IN
 ACCORDANCE WITH A NON-ABSORBENT SURFACE IN ACCORDANCE
 WITH THE 2017 FBC BUILDING SEC. 1210.2.2. PLEASE MAKE A
 NOTE ON THIS SHEET.
  
 8. SHEET 045 P3-1;
  
 A. ON KEYNOTES 1, PLEASE ADD THAT IT SHALL CONFORM ASSE
 1070 ON THE MIXING VALVE.
  
 B. ALL SINKS IN KITCHEN AREA HAVE NOTE 1 ON THEM, THESE
 SINKS REQUIRE HOT WATER AND NEED TO BE NOTED AS SO, NOT
 WITH THE TEMPERED NOTE 1, PLEASE MAKE A NEW NOTE OR
 DELETE NUMBER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. SHEET 044 P2-1;
  
 A. IT SHOWS A GREASE CALCULATION, PLEASE PROVIDE THE
 CAPACITY OF THE EXISTING INTERCEPTOR IN GALLONS.
  
 B. IS IT SHARED WITH OTHER RESTAURANTS AND IF SO, WHAT
 IS THEIR VOLUME.
  
 C. IS IT A PASSIVE HYDROMECHANICAL - OR GRAVITY-TYPE
 GREASE INTERCEPTORS MADE OF CONCRETE STEEL OR
 FIBERGLASS.
  
 D. IN THE KITCHEN AREA THERE IS A THREE-COMPARTMENT
 SINK PLEASE PROVIDE DETAIL ON THE DRAINS TO AN INDIRECT
 WASTE INDEPENDENTLY FORM EACH OTHER PER THE 2017 FBC
 SEC. P 802.1.1.
  
 E. THESE TWO GAS HEATER DISCHARGING CONDENSATION WILL
 NEED A NEUTRALIZING DEVICE THAT WILL BE REQUIRED,
 PLEASE PROVIDE SPECIFICATIONS TO DETERMINE THE PH LEVEL
 PER THE 2017 FBC SEC. P 803.1.
  
 10. PLEASE PROVIDE A DETAIL DRAWING OF THE EMPLOYEE
 ACCESSIBLE RESTROOM IN WITH DIMENSIONS AND HEIGHT
 ELEVATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 11. PLEASE SHOW ISOLATION BACKFLOW DEVICE AT ISOMETRIC
 DRAWING AND PUT A NOT ON ITS LOCATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2020-09-24 Cont ID  
Sent By rgathrig Date 2020-09-24 Time 17:38 Rev Time 0.00
Received By rgathrig Date 2020-09-24 Time 17:37 Sent To  
Notes
2020-09-24 17:39:25PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
 PLANNING & BUILDING CONSULTANTS, LLC STEVE KENNEDY
  
 RICHARD GATHRIGHT
 5618056679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-28 Cont ID  
Sent By jwitmer Date 2020-09-28 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2020-09-28 Time 09:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By jleahy Date 2020-09-21 Time 16:17 Rev Time 0.00
Received By jleahy Date 2020-09-21 Time 16:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-18 Cont ID  
Sent By lcrespo Date 2020-08-18 Time 17:03 Rev Time 0.00
Received By lcrespo Date 2020-08-18 Time 17:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-10-02 Cont ID  
Sent By eschneid Date 2020-10-02 Time 10:23 Rev Time 0.25
Received By eschneid Date 2020-10-02 Time 09:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-09-21 Cont ID  
Sent By eschneid Date 2020-09-21 Time 14:39 Rev Time 0.50
Received By eschneid Date 2020-09-21 Time 11:35 Sent To  
Notes
2020-09-21 14:14:51FAILED
  
 1) THANK YOU FOR PROVIDING PHOTOS OF THE EXISTING ROOF
 TO VERIFY THAT THERE IS A PARAPET; HOWEVER, NO
 INFORMATION WAS PROVIDED AS TO THE HEIGHT OF THE
 PARAPET AND THE HEIGHT OF THE NEW OARTU-1. BASED ON THE
 SHOP DRAWINGS, THE MAU-1 APPEARS TO BE OVER 8 FEET IN
 HEIGHT WITH THE CURB, WHICH WOULD TAKE A TALL PARAPET
 TO SCREEN. THE CU-3 HEIGHT (BUT WITHOUT THE CURB) AND
 EF-1 HEIGHT WERE PROVIDED. WITHOUT THE HEIGHT OF THE
 PARAPET, STAFF CANNOT VERIFY SCREENING. A CROSS SECTION
 DRAWING, WITH DIMENSIONS, WOULD BE VERY HELPFUL. -----
 IN ACCORDANCE WITH THE CITYPLACE DRI, PLEASE PROVIDE
 VERIFICATION THAT ALL ROOFTOP MECHANICAL EQUIPMENT,
 INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND
 PRIVATE UTILITY SERVICE CONNECTIONS; HEATING,
 VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW.
 IF VERIFICATION THAT THE NEW ROOFTOP MECHANICAL
 EQUIPMENT IS NOT SCREENED, ZONING WILL NOT APPROVE THIS
 INTERIOR BUILD OUT PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By eschneid Date 2020-08-18 Time 15:14 Rev Time 1.00
Received By eschneid Date 2020-08-18 Time 13:39 Sent To  
Notes
2020-08-18 15:14:18FAILED
  
 1) THE CITYPLACE MANAGEMENT STAMP NEEDS TO BE PROVIDED
 ON THE PLANS. ALTERNATIVELY, THEY MAY PROVIDE A LETTER
 LISTING THE SPECIFIC PLANS THAT THEY HAVE APPROVED.
  
 2) THE SEATING, PLANTERS AND LIGHTING IN THE PLANTERS
 SHOWN IN LINE WITH THE EXISTING TREES ARE IN THE
 HIBISCUS STREET RIGHT-OF-WAY. THESE REQUIRE THE
 APPROVAL OF A SIDEWALK CAFE PERMIT AND ARE NOT APPROVED
 AS PART OF THE BUILDING PERMIT PROCESS. THESE FEATURES
 NEED TO BE REMOVED FROM THE PLANS.
  
 3) THE ROOF PLAN INCLUDES A NOTE THAT THE ROOF TOP
 EQUIPMENT IS UNDER A SEPARATE PERMIT. NO PERMIT HAS
 BEEN SUBMITTED FOR THIS EQUIPMENT. IN ACCORDANCE WITH
 THE CITYPLACE DRI, PLEASE PROVIDE VERIFICATION THAT ALL
 ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT NOT LIMITED
 TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY SERVICE
 CONNECTIONS; HEATING, VENTILATING, AND AIR CONDITIONING
 SYSTEMS; COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT,
 SHALL BE SCREENED FROM PUBLIC VIEW THROUGH ANY
 COMBINATION OF LANDSCAPING, WALLS AND EQUIPMENT
 LOCATION. PLEASE PROVIDE PLANS OR OTHER EVIDENCE THAT
 THE NEW ROOFTOP MECHANICAL EQUIPMENT WILL BE SCREENED
 FROM PUBLIC VIEW. IF VERIFICATION THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT IS NOT SCREENED, ZONING WILL NOT
 APPROVE THIS INTERIOR BUILD OUT PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  