Plan Review Details - Permit 20061411
Plan Review Stops For Permit 20061411
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By rmcphers Date 2020-08-31 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2020-08-31 Time 07:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 13:02 Rev Time 0.00
Received By rmcphers Date 2020-08-21 Time 13:02 Sent To  
Notes
2020-08-21 13:05:12SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING IN PROJECTDOX LABELED "20061411 STRUCTURAL
 CALCULATIONS.PDF" DRAWING 3.1 THAT SHOWS ALL THE
 ATTACHMENTS NEEDS TO BE SIGNED AND SEALED BY AN
 ENGINEER OR ARCHITECT. THE WIND DESIGN DATA NEEDS TO BE
 SHOWN ON THIS DRAWING (3.1).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-17 Cont ID  
Sent By rmcphers Date 2020-07-17 Time 08:30 Rev Time 0.00
Received By rmcphers Date 2020-07-17 Time 08:30 Sent To  
Notes
2020-07-17 08:34:11SIGNS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE SIGNED AND SEALED SIGN ATTACHMENT
 DETAILS FROM AN ARCHITECT OR ENGINEER SHOWING THE
 ATTACHMENTS SIZE, TYPE AND SPACING - SHOW THE WIND
 DESIGN DATA USED FBC 1609
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-21 Cont ID  
Sent By jleahy Date 2020-08-21 Time 10:59 Rev Time 0.00
Received By jleahy Date 2020-08-21 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-21 Cont ID  
Sent By jleahy Date 2020-07-21 Time 17:20 Rev Time 0.00
Received By jleahy Date 2020-07-21 Time 17:19 Sent To  
Notes
2020-07-21 17:24:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF PERMIT IS THE SIGN AND LABOR TO INSTALL
 SIGN. SIGN, FOUNDATION, LABOR (3000) PERMIT VALUE IS
 LOW.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) DISCONNECT REQUIRED FOR SIGN 600.6(A)(1)
  
 3) CIRCUIT TO SIGN COMES FROM??? SHOW SIGN BRANCH
 CIRCUIT AND LOCATION OF PANEL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 13:10 Rev Time 0.00
Received By rmcphers Date 2020-08-03 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-03 Cont ID  
Sent By lmarchan Date 2020-08-03 Time 16:20 Rev Time 0.00
Received By lmarchan Date 2020-06-30 Time 16:05 Sent To  
Notes
2020-06-30 16:06:07ROUTED TO ZONING BIN

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By rmcphers Date 2020-08-31 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2020-08-31 Time 07:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 13:07 Rev Time 0.00
Received By rmcphers Date 2020-08-21 Time 13:07 Sent To  
Notes
2020-08-21 13:07:50SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By pvalenti Date 2020-07-10 Time 15:29 Rev Time 0.00
Received By pvalenti Date 2020-07-10 Time 15:29 Sent To  
Notes
2020-07-10 15:35:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, FS 471, FS 481, & FAC 61G15-23; THE
 SUBMITTED DOCUMENTS ARE NOT SIGNED OR SEALED.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By llouie Date 2020-07-15 Time   Rev Time  
Received By llouie Date 2020-07-15 Time   Sent To  
Notes
***NONE***