Plan Review Details - Permit 20061338
Plan Review Stops For Permit 20061338
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 15:35 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By cthroop Date 2020-07-16 Time 08:18 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 15:41 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 15:34 Sent To  
Notes
2020-07-10 15:47:00PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW GROUNDING ELECTRODE SYSTEM AT SERVICE.
 PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE. NEC 250; FBC RE 3607.3.
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
  
 2. SHOW CONDUCTOR SIZES AND CABLE TYPE FOR CONTROL
 CIRCUT.
 E3601.4 OTHER CONDUCTORS IN RACEWAY OR CABLE.
 NEC 230.7 & EXHIBIT 230.16
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE CABLE.
 (230.7)
 EXCEPTIONS:
 1. 1.GROUNDING ELECTRODE CONDUCTORS AND EQUIPMENT
 BONDING JUMPERS OR CONDUCTORS.
 2. 2.LOAD MANAGEMENT CONTROL CONDUCTORS HAVING
 OVERCURRENT PROTECTION.
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-07-23 Cont ID  
Sent By cthroop Date 2020-07-16 Time 08:20 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 14:51 Sent To  
Notes
2020-07-16 08:21:36PLAN REVIEW FUEL GAS GENERATOR
 A SEPERATE GAS PERMIT IS REQUIRED. CT
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 15:35 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 15:34 Sent To  
Notes
2020-07-10 15:41:09PLAN REVIEW ? FUEL GAS GENERATOR
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1) GAS ISOMETRIC DRAWING:
 A) THE DRAWING MUST SHOW THE ENTIRE SYSTEM INCLUDING
 ALL BRANCH PIPES FROM THE METER TO THE MOST REMOTE
 OUTLET. THE BTUH LOAD OF EACH APPLIANCE AND THE
 LOCATIONS OF REGULATORS SHALL BE INDICATED ON THE
 DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3.
 B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 C) PROVIDE THE BTUH LOAD OF THE GENERATOR. THE
 SUBMITTED SPECS INDICATE 327,000 BTUH FULL LOAD-
 G2413.2 FBC RES.
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
 3.) SUBMIT SPECS FOR FEX CONNECTORS. SECTION G2421.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-16 Cont ID  
Sent By cthroop Date 2020-07-16 Time 08:22 Rev Time 0.00
Received By cthroop Date 2020-07-13 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 15:47 Rev Time 0.00
Received By cthroop Date 2020-06-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-16 Cont ID  
Sent By cthroop Date 2020-07-16 Time 08:21 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-16 Cont ID  
Sent By cthroop Date 2020-07-16 Time 08:21 Rev Time 0.00
Received By cthroop Date 2020-07-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-10 Cont ID  
Sent By cthroop Date 2020-07-10 Time 15:35 Rev Time 0.00
Received By cthroop Date 2020-07-10 Time 15:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By alexandr Date 2020-07-08 Time   Rev Time  
Received By   Date 2020-07-08 Time   Sent To I
Notes
***NONE***