Plan Review Details - Permit 20061324
Plan Review Stops For Permit 20061324
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-12 Cont ID  
Sent By rmcphers Date 2020-08-12 Time 09:39 Rev Time 0.00
Received By rmcphers Date 2020-08-12 Time 09:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-31 Cont ID  
Sent By rmcphers Date 2020-07-31 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2020-07-31 Time 14:04 Sent To  
Notes
2020-07-31 14:08:12SHUTTERS -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW - CORRECTIONS NEEDED - FBC WPB AMENDMENTS
 107
 1) WIND DESIGN PRESSURES ARE BASED ON BUILDING ROOF
 HEIGHT. THIS BUILDING IS A 10 STORY BUILDING.
 2) PLEASE SHOW THE BUILDING ROOF HEIGHT.
 3) PLEASE SHOW THE LOCATION OF THE UNIT WITHIN THE
 BUILDING FOOT PRINT (AN INTERIOR OR END OF BUILDING
 UNIT).- NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND
 ZONE 4 OR 5.
 4) IF AN END UNIT - PLEASE SHOW THE DISTANCE FROM THE
 CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS -
 NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND ZONE 4
 OR 5.
 5) PLEASE SHOW THE LENGTH AND WIDTH OF THE ENTIRE
 BUILDING - NEEDED TO DETERMINE IF THE WINDOWS ARE IN
 WIND ZONE 4 OR 5.
 5) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN
 PRESSURES FOR THE OPENINGS FROM AN ARCHITECT OR
 ENGINEER - SHOWING THE WIND DESIGN CRITERIA USED FOR
 DESIGN - FBC 1609
 6) PLEASE REVISE THE "SCHEDULE FOR INSTALLATION OF
 OPENINGS" TO REFLECT THE UPDATED WIND DESIGN PRESSURES
 TO BE PROVIDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 13:11 Sent To  
Notes
2020-07-24 13:14:29SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) WIND DESIGN PRESSURES ARE BASED ON BUILDING ROOF
 HEIGHT. THIS BUILDING IS A 10 STORY BUILDING.
 2) PLEASE SHOW THE BUILDING ROOF HEIGHT.
 3) PLEASE SHOW THE LOCATION OF THE UNIT WITHIN THE
 BUILDING FOOT PRINT (AN INTERIOR OR END OF BUILDING
 UNIT).- NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND
 ZONE 4 OR 5.
 4) IF AN END UNIT - PLEASE SHOW THE DISTANCE FROM THE
 CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS -
 NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND ZONE 4
 OR 5.
 5) PLEASE SHOW THE LENGTH AND WIDTH OF THE ENTIRE
 BUILDING - NEEDED TO DETERMINE IF THE WINDOWS ARE IN
 WIND ZONE 4 OR 5.
 5) PLEASE PROVIDE SIGNED AND SEALED WIND DESIGN
 PRESSURES FOR THE OPENINGS FROM AN ARCHITECT OR
 ENGINEER - SHOW THE WIND DESIGN CRITERIA USED FOR
 DESIGN - FBC 1609
 6) PLEASE REVISE THE "SCHEDULE FOR INSTALLATION OF
 OPENINGS" TO REFLECT THE UPDATED WIND DESIGN PRESSURES
 TO BE PROVIDED.
 7) PLEASE SHOW ON THE "SCHEDULE FOR INSTALLATION OF
 OPENINGS" THE ATTACHMENT ON CENTER SPACING.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-12 Cont ID  
Sent By rmcphers Date 2020-08-12 Time 09:43 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-07 Cont ID  
Sent By lmarchan Date 2020-08-07 Time 06:51 Rev Time 0.00
Received By lmarchan Date 2020-08-03 Time 07:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-31 Cont ID  
Sent By rmcphers Date 2020-07-31 Time 14:12 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 16:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2020-07-17 Time 09:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-12 Cont ID  
Sent By rmcphers Date 2020-08-12 Time 09:41 Rev Time 0.00
Received By rmcphers Date 2020-08-12 Time 09:41 Sent To  
Notes
2020-08-12 09:43:42EMERGENCY RULE APPLIED 61G15ER20-4

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-31 Cont ID  
Sent By rmcphers Date 2020-07-31 Time 14:10 Rev Time 0.00
Received By rmcphers Date 2020-07-31 Time 14:10 Sent To  
Notes
2020-07-31 14:11:26SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 13:34 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 13:34 Sent To  
Notes
2020-07-24 13:34:25SEE BUILDING PLAN REVIEW