Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 7 Status P Date 2021-05-03 Cont ID  
Sent By jwitmer Date 2021-05-03 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2021-05-03 Time 09:42 Sent To  
Notes
2021-05-03 09:33:15BUILDING PROVISO: 2017 FBC-ACCESSIBILITY CODE. ACCESS
 SECTION 404.2.4 MANEUVERING CLEARANCES. THE MINIMUM
 MANEUVERING CLEARANCES AT THE DOOR SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND REQUIRED LATCH SIDE FOR SIDE
 CLEARANCES.
 7/03/2021 J. WITMER.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 6 Status F Date 2021-03-16 Cont ID  
Sent By jwitmer Date 2021-03-16 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2021-03-16 Time 08:15 Sent To  
Notes
2021-03-16 08:21:38CONTRACTOR PLEASE SUPPLY:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status F Date 2021-02-22 Cont ID  
Sent By jwitmer Date 2021-02-22 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2021-02-22 Time 07:56 Sent To  
Notes
2021-02-22 08:28:22CONTRACTOR PLEASE SUPPLY:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2020-12-17 Cont ID  
Sent By jwitmer Date 2020-12-17 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2020-12-17 Time 11:16 Sent To  
Notes
2020-12-17 11:43:24TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2020-12-02 Cont ID  
Sent By jwitmer Date 2020-12-02 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2020-12-02 Time 07:45 Sent To  
Notes
2020-12-02 08:16:39TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-12-02 Cont ID  
Sent By jwitmer Date 2020-10-16 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2020-10-16 Time 15:02 Sent To  
Notes
2020-10-16 16:22:06CONTRACTOR PLEASE SUPPLY:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By jwitmer Date 2020-07-20 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2020-07-20 Time 13:43 Sent To  
Notes
2020-07-20 13:45:30CONTRACTOR PLEASE SUPPLY:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2021-05-03 Cont ID  
Sent By jwitmer Date 2021-05-03 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2021-05-03 Time 09:14 Sent To  
Notes
2021-05-03 09:33:53BUILDING PROVISO: 2017 FBC-ACCESSIBILITY CODE. ACCESS
 SECTION 404.2.4 MANEUVERING CLEARANCES. THE MINIMUM
 MANEUVERING CLEARANCES AT THE DOOR SHALL COMPLY WITH
 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE FULL
 WIDTH OF THE DOORWAY AND REQUIRED LATCH SIDE FOR SIDE
 CLEARANCES.
 7/03/2021 J. WITMER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-03-16 Cont ID  
Sent By jwitmer Date 2021-03-16 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2021-03-16 Time 08:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-02-22 Cont ID  
Sent By jwitmer Date 2021-02-22 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2021-02-22 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-12-17 Cont ID  
Sent By jwitmer Date 2020-12-17 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2020-12-17 Time 11:16 Sent To  
Notes
2020-12-17 11:30:38WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: THURS. DEC. 17TH/ 2020
 ACTION: PASSED / BUILDING PROVISOS
  
 1) BUILDING PROVISO/ DEFERRED SUBMITTALS. SHEET A-3 &
 S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 1A) BUILDING PROVISO / DEFERRED SUBMITTALS. W. P. B.
 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 1B) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-12-02 Cont ID  
Sent By jwitmer Date 2020-12-02 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2020-12-02 Time 07:43 Sent To  
Notes
2020-12-02 08:15:11WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. DEC. 02ND/ 2020
 ACTION: DENIED
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
 FOR THE 3RD REVIEW THERE WAS NO UPDATED TRANSMITTAL
 LETTER. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) SEMI-COMPLIED/ DISPROPORTIONATE COST 202.4.1. THERE
 ARE STILL A FEW ACCESSIBILITY ISSUES WITH THE RESTROOMS
 SEE BELOW COMMENTS.
  
 1A) SHEET A-3. SEMI-COMPLIED. VERSION ONE OF THE PLANS
 INDICATES THE EXISTING EXECUTIVE RESTROOM. VERSION 2
 NOW STATES THAT THE CONVERTED EXECUTIVE RESTROOM IS AN
 EXISTING ADA RESTROOM, WHERE THE RESTROOM IN QUESTION
 IS THE 2ND REQUIRED ADA RESTROOM COMPLYING WITH
 FBC-ACCESSIBILITY SECTION 213.2EXCEPTION 4.
 THE FLOOR PLAN HAS THE WRITTEN WORDS TO REMOVE
 CABINETRY BUT THE PLANS DO NOT INDICATE THE CABINETS
 REMOVED.
  
 1A)(1) THE NEW PROPOSED ADA RESTROOM THE DETAIL DOES
 STATE (1) TO REMOVE THE EXISTING VERTICAL CABINET AND
 (2) RECONFIGURE EXISTING CABINET/ SINK PER REQUIRED ADA
 REQUIREMENTS SEE SHEET A-5. SHEET A-5 DOES SHOW
 ACCESSIBLE DETAILS BUT THERE IS NO OVERALL FLOOR PLAN
 DETAIL SHOWING THE SIZE OF THE CABINET WITH CLEAR FLOOR
 SPACE. SHEET A-3 SHOWS CABINETRY THAT NEEDS TO BE
 REMOVED TO SHOW CODE COMPLIANCE FOR THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSET
 (CLEARANCES AT WATER CLOSETS. 604.3.1 CLEARANCE) AND
 MANEUVERING CLEARANCES OF 18 INCHES LATCH SIDE OF THE
 DOOR (ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS.)
  
 1B) SHEET A-3. COMPLIED. SHEET A-3 COMPLIES HIGH/ LOW
 DRINKING FOUNTAIN.
  
 1C) SHEET A-5 NOW SHOWS NEW ACCESSIBLE RESTROOM ELEMENT
 DETAILS, PLEASE NOTE THE GRAB BAR DETAILS ARE MEASURED
 FROM FINISH FLOOR TO CENTERLINE OF THE GRAB BAR. 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE. THERE IS A RANGE OF 3 INCHES
 THAT IS ACCEPTABLE, GRAB BARS ARE MEASURED AT TIME OF
 FINAL INSPECTIONS. WHEN GRAB BARS ARE INSTALLED AT THE
 36 INCH MEASUREMENT AND THEY ARE INSTALLED AT 36 INCHES
 TO THE CENTER LINE THEY ARE 3/4TH OF A INCH TO HIGH AND
 HAVE TO BE REINSTALLED, ON TILE WALLS WALL TILE ALSO
 HAS TO BE REPLACED BECAUSE OF THE WALL TILE WITH HOLES
 SHOWING.
  
 1D) THIS COMMENT DEALS WITH THE RESTROOMS THAT ARE
 BEING RECONFIGURED WILL NEED TO SHOW COMPLIANCE WITH:
 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN
 RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTALS. SHEET A-3 &
 S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 2A) BUILDING PROVISO / DEFERRED SUBMITTAL. W. P. B.
 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-16 Cont ID  
Sent By jwitmer Date 2020-10-16 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2020-10-16 Time 15:01 Sent To  
Notes
2020-10-16 16:20:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT.16TH/ 2020
 ACTION: DENIED
  
 1) SEMI-COMPLIED/ DISPROPORTIONATE COST 202.4.1. THERE
 ARE STILL A FEW ACCESSIBILITY ISSUES WITH THE RESTROOMS
 SEE BELOW COMMENTS.
  
 1A) SHEET A-3. SEMI-COMPLIED. VERSION ONE OF THE PLANS
 INDICATES THE EXISTING EXECUTIVE RESTROOM. VERSION 2
 NOW STATES THAT THE CONVERTED EXECUTIVE RESTROOM IS AN
 EXISTING ADA RESTROOM, WHERE THE RESTROOM IN QUESTION
 IS THE 2ND REQUIRED ADA RESTROOM COMPLYING WITH
 FBC-ACCESSIBILITY SECTION 213.2EXCEPTION 4. CORRECT
 NAME TO NEW ADA RESTROOM.
 1A)(1) NEW COMMENT. THE NEW PROPOSED ADA RESTROOM THE
 DETAIL DOES STATE (1) TO REMOVE THE EXISTING VERTICAL
 CABINET AND (2) RECONFIGURE EXISTING CABINET/ SINK PER
 REQUIRED ADA REQUIREMENTS SEE SHEET A-5. SHEET A-5 DOES
 SHOW ACCESSIBLE DETAILS BUT THERE IS NO OVERALL FLOOR
 PLAN DETAIL SHOWING THE SIZE OF THE CABINET WITH CLEAR
 FLOOR SPACE. SHEET A-3 SHOWS CABINETRY THAT NEEDS TO BE
 REMOVED TO SHOW CODE COMPLIANCE FOR THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSET
 (CLEARANCES AT WATER CLOSETS. 604.3.1 CLEARANCE) AND
 MANEUVERING CLEARANCES OF 18 INCHES LATCH SIDE OF THE
 DOOR (ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS.)
  
 1B) SHEET A-3. COMPLIED. SHEET A-3 COMPLIES HIGH/ LOW
 DRINKING FOUNTAIN.
  
 1C) NEW COMMENT. SHEET A-5 NOW SHOWS NEW ACCESSIBLE
 RESTROOM ELEMENT DETAILS, PLEASE NOTE THE GRAB BAR
 DETAILS ARE MEASURED FROM FINISH FLOOR TO CENTERLINE OF
 THE GRAB BAR. 2017 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 1D) NEW COMMENT DEALS WITH THE RESTROOMS THAT ARE BEING
 RECONFIGURED WILL NEED TO SHOW COMPLIANCE WITH: 2017
 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A
 RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN
 RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH
 HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
 2017 FBC-B 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
 2017 FBC-B 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2) BUILDING PROVISO/ DEFERRED SUBMITTALS. SHEET A-3 &
 S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING. PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 2A) BUILDING PROVISO / DEFERRED SUBMITTAL.W. P. B.
 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By jwitmer Date 2020-07-20 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2020-07-20 Time 13:43 Sent To  
Notes
2020-07-20 13:44:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20061293
 ADD: 3 HARVARD CIR.
 CONT: TBD/ TO BE DETERMINED
 TEL: 954-646-0412
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 20TH/ 2020
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE PERMIT VALUE
 FOR THIS PROJECT IS $250,000.00 DOLLARS. EXISTING BLDG.
 CODE- ACCESSIBILITY. UNDER THE 2017 EXISTING BUILDING
 CODE LEVEL II ALTERATIONS, SECTION 806.1 A BUILDING,
 FACILITY, OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 THE PROVISIONS OF THE FLORIDA BUILDING CODE-
 ACCESSIBILITY. IN THE ACCESSIBILITY CODE IT REFERS YOU
 TO DISPROPORTIONATE
  
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% ($50,000.00) DISPROPORTIONATE FUNDS LISTED
 FOR EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN
 THE ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE
 COST OF THE 2017 ACCESSIBILITY CODE.
  
 1A) SHEET A-3. PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY
 CODE SECTION 213.2 EXCEPTION 4. WHERE MULTIPLE SINGLE
 TOILET ROOMS ARE CLUSTERED AT A SINGLE LOCATION, NO
 MORE THAN 50 PERCENT OF THE SINGLE TOILET ROOMS FOR USE
 AT EACH CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603.
 ADVISORY. A CLUSTER IS A GROUP OF TOILET ROOMS
 PROXIMATE TO ONE ANOTHER. GENERALLY TOILET ROOMS IN A
 CLUSTER ARE WITHIN SIGHT OF ONE ANOTHER, OR ADJACENT
 TO, ONE ANOTHER.
  
 1B) SHEET A-3. SHEET A-3 SHOWS A SINGLE USE WATER
 FOUNTAIN NOT A HIGH/ LOW DRINKING FOUNTAIN. PLEASE SHOW
 COMPLIANCE WITH:
 DRINKING FOUNTAINS.
 1B)(1) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
  
 1B)(2) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY IN TO THE
 CIRCULATION PATH.
  
 1B)(3) 60.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 2) SHEET A-3 & S-1 BOTH SHOW NEW EXTERIOR DOOR OPENING.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS,
  
 2A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2B) IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-03-31 Cont ID  
Sent By fgiaquin Date 2021-03-31 Time 21:05 Rev Time 0.00
Received By fgiaquin Date 2021-03-31 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-02-27 Cont ID  
Sent By fgiaquin Date 2021-02-27 Time 17:50 Rev Time 0.00
Received By fgiaquin Date 2021-02-27 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 09:19 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 09:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-11-02 Cont ID  
Sent By fgiaquin Date 2020-11-02 Time 20:13 Rev Time 0.00
Received By fgiaquin Date 2020-11-02 Time 19:16 Sent To  
Notes
2020-11-02 20:13:37SEE PREVIOUS PLAN REVIEW COMMENTS. PLAN REVIEW COMMENTS
 WERE NOT ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-19 Cont ID  
Sent By fgiaquin Date 2020-08-19 Time 22:16 Rev Time 0.00
Received By fgiaquin Date 2020-08-19 Time 20:10 Sent To  
Notes
2020-08-19 22:15:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM MUST BE SUBMITTED UNDER A SEPARATE PERMIT
 WITH SEPARATE PLANS. FBC 107.2.1 FBC 105.1
  
 2. LOW VOLTAGE MUST ALSO BE A SEPARATE PERMIT BUT A LOW
 VOLTAGE REVIEW STOP CAN BE ADDED TO MASTER PERMIT FOR
 REVIEW. PLEASE REMOVE ALL FIRE ALARM FROM LV DRAWINGS.
 FBC 107.2.1 FBC 105.1
  
 3. IS RISER DIAGRAM PROVIDED EXISTING OR PROPOSED? NO
 OCP SHOWN FOR MAINS ON RISER DIAGRAM. FBC 107.2.1
  
 4. NO EQUIPMENT GROUNDS SHOWN FOR PANELS "H" AND "A"ON
 RISER DIAGRAM?
  
 5. NO HVAC LOAD SHOWN IN LOAD CALC?
  
 6. LIGHTING MUST BE CALCULATED AT 125% IN LOAD CALC FOR
 CONTINUOUS LOADS NEC 210.19A
  
 7. VA PER SQ/FT FOR OFFICE BUILDINGS IS 3.5VA NOT 2VA
 WHICH IS WHAT IS IN LOAD CALC NOW. NEC 220.12
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 3 Status P Date 2021-03-31 Cont ID  
Sent By fgiaquin Date 2021-03-31 Time 21:05 Rev Time 0.00
Received By fgiaquin Date 2021-03-31 Time 21:05 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2021-02-27 Cont ID  
Sent By fgiaquin Date 2021-02-27 Time 17:49 Rev Time 0.00
Received By fgiaquin Date 2021-02-27 Time 17:49 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 09:21 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 09:21 Sent To  
Notes
2020-12-16 09:21:54PHONE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-10-16 Cont ID  
Sent By pleduc Date 2020-10-16 Time   Rev Time 0.00
Received By pleduc Date 2020-10-16 Time 16:29 Sent To  
Notes
2020-10-16 16:33:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) THE EXISTING FIRE ALARM SYSTEM DEVICES SHALL BE
 MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM OR DEVICES
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-07-16 Cont ID  
Sent By pleduc Date 2020-07-16 Time   Rev Time 0.00
Received By pleduc Date 2020-07-16 Time 14:38 Sent To  
Notes
2020-07-16 14:48:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COVER & A 3 SHEETS - THERE ARE REFERENCES TO
 INCORRECT EDITION OF THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE CURRENT
 ADOPTED EDITION OF THE FLORIDA FIRE PREVENTION CODE
 WHICH INCLUDES THE 2015 EDITIONS OF NFPA 1 & 101.
  
 PLEASE REVIEW THOSE EDITIONS AND ENSURE COMPLIANCE WITH
 THE PROPOSED.
  
 PLEASE CORRECT TO THE CURRENT ADOPTED EDITIONS.
  
  
 2) SHEET E 2 - THERE ARE INDICATIONS OF FIRE ALARM
 DEVICES.
  
 ANY WORK OF THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2021-05-03 Cont ID  
Sent By jwitmer Date 2021-05-03 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2021-04-08 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 13:32 Rev Time 0.00
Received By medwards Date 2021-03-15 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-03-10 Time   Rev Time 0.00
Received By lmarchan Date 2021-02-17 Time 12:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-12-30 Cont ID  
Sent By medwards Date 2020-12-30 Time 08:16 Rev Time 0.00
Received By medwards Date 2020-12-15 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-16 Cont ID  
Sent By ccarvaja Date 2020-12-02 Time 06:51 Rev Time 0.00
Received By ccarvaja Date 2020-11-28 Time 13:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-11-02 Cont ID  
Sent By fgiaquin Date 2020-11-02 Time 20:13 Rev Time 0.00
Received By fgiaquin Date 2020-10-14 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-19 Cont ID  
Sent By fgiaquin Date 2020-08-19 Time 22:16 Rev Time 0.00
Received By fgiaquin Date 2020-07-14 Time 10:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-07-20 Cont ID  
Sent By jwitmer Date 2020-07-20 Time 15:03 Rev Time 0.00
Received By jwitmer Date 2020-07-20 Time 13:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 09:18 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 09:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 13:26 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 13:26 Sent To  
Notes
2021-04-01 13:26:576TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20061293
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS THE 6TH REVIEW ON THIS PROJECT. I HAVE TRIED
 TO REACH OUT TO THE ENGINEER ADAM HART BUT HIS
 VOICEMAIL IS FULL. I WOULD LIKE TO TALK ABOUT THE
 OUTDOOR AIR CALCULATIONS FOR THIS BUILD OUT. PLEASE
 CALL ME AS WE MUST HAVE THE INFORMATION REQUESTED IN
 ALL OF THE PREVIOUS CYCLES. THE OUTDOOR AIR
 CALCULATIONS ARE AN IMPORTANT PART OF THIS DESIGN AND I
 MUST SEE THOSE CALCULATIONS BASED ON EACH USE OF SPACE
 IN THIS TENANT BUILDOUT. FBC M403.3.1.1 AND TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2021-03-05 Cont ID  
Sent By medwards Date 2021-03-05 Time 13:59 Rev Time 0.00
Received By medwards Date 2021-03-05 Time 13:43 Sent To  
Notes
2021-03-05 14:00:30COMMENT 5 OF THE 3RD CYCLE REVIEWERS COMMENT'S IS
 RELEVENT. AIR BALANCE IS NOT THE SAME THING AS OUTDOOR
 AIR CALCULATIONS. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR EACH USE OF SPACE IN THIS TENANT SPACE
 AS PER FBC M 403.3.1.1 AND TABLE 403.3.1.1.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2020-12-19 Cont ID  
Sent By hmoser Date 2020-12-19 Time 08:32 Rev Time 0.00
Received By medwards Date 2020-12-19 Time 08:32 Sent To  
Notes
2020-12-19 08:32:471ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20061293
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I DO NOT SEE THE HRCD RESPONSE THAT IS SUPPOSED TO
 BE ATTACHED. PLEASE RESPOND TO PREVIOUS REVIEW
 COMMENTS. FBC 107.2.1
 PLEASE FEEL FREE TO GIVE ME A CALL AND DISCUSS THIS
 PROJECT AS THIS IS THE 4TH CYCLE THAT HAS BEEN DENIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-12-02 Cont ID  
Sent By hmoser Date 2020-12-02 Time 14:02 Rev Time 0.00
Received By medwards Date 2020-12-02 Time 11:10 Sent To  
Notes
2021-03-05 13:58:43 
  
2020-12-02 14:01:53PLAN DENIED
 1) DUCT SIZE REQUIRED
 OFFICE ROOM A - 106 RETURN AIR DUCT
 OFFICE ROOM A - 101 RETURN AIR AND SUPPLY DUCT
 CONTROL ROOM A - 105 RETURN AIR DUCT
 SECTION 107 FBC 2017
 2) PROVIDE MODEL NUMBER OF AIR CONDITIONING UNIT
 ON EQUIPMENT SCHEDULE SECTION 107 FBC 2017
 3) REFER TO SECTION 606.2.1 FBC(M) AND PROVIDE
 MANUFACTURES
 INSTALLATION INSTRUCTIONS FOR AIR CONDITIONING UNIT AT
 FIRST INSPECTION.
 4) PROVIDE CFM ON BATHROOM EXHAUST FAN SCHEDULE PER
 TABLE
 403.3.1.1 FBC(M)
 5) PROVIDE FRESH AIR CALCULATIONS ON PLAN.
 PER TABLE 403.3.1.1 FBC(M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 16:39 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 16:18 Sent To  
Notes
2020-10-28 16:21:15PLEASE SEE NOTE 2 OF THE ORIGINAL REVIEWERS COMMENTS.
 THERE ARE SEVERAL RETURN AND SUPPLY DUCTS THAT STIL DO
 NOT PROVIDE THE SIZE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-08-07 Cont ID  
Sent By hmoser Date 2020-08-07 Time 09:48 Rev Time 0.00
Received By hmoser Date 2020-08-07 Time 09:04 Sent To  
Notes
2020-08-07 09:48:20PLAN DENIED
 1) PROVIDE SUITE NUMBER ON APPLICATION AND PLAN
 SECTION 107 FBC 2017
 2) PROVIDE DUCT SIZE ON ALL DUCT. RETURN AIR ROOMS 105,
 106.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 6 Status P Date 2021-03-16 Cont ID  
Sent By ccole Date 2021-03-16 Time 17:25 Rev Time 0.00
Received By jwitmer Date 2021-05-03 Time 09:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2021-03-10 Cont ID  
Sent By ccole Date 2021-03-10 Time 13:56 Rev Time 0.00
Received By ccole Date 2021-03-09 Time 15:50 Sent To  
Notes
2021-03-10 13:56:235TH REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 3/10/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0 & P1: THE REVISED PLUMBING PLANS ARE NOT
 MEETING COMPLIANCE WITH SECTION AND TABLE C404.5.1 FBC
 EC. ACCORDING TO THE TABLE THE MAXIMUM ALLOWABLE PIPING
 LENGTH FROM THE NEAREST SOURCE OF HEATED WATER TO THE
 TERMINATION OF THE FIXTURE SUPPLY PIPE AT THE
 LAVATORIES IS 2 FT. FOR 1/2 IN WATER SUPPLY LINES. IT
 APPEARS THAT EITHER A RECIRCULATION PUMP WILL BE
 REQUIRED FOR THE HOT WATER SYSTEM, OR POINT OF USE
 WATER HEATERS MUST BE INSTALLED AT THE LAVATORIES.
 PLEASE NOTE THAT TEMPERED WATER IS ALSO REQUIRED AT THE
 LAVATORIES IN ACCORDANCE WITH SECTIONS 419.5 AND
 607.1.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-12-29 Cont ID  
Sent By ccole Date 2020-12-29 Time 20:33 Rev Time 0.00
Received By abelisle Date 2020-12-29 Time 18:23 Sent To I
Notes
2020-12-29 21:02:204TH REVIEW FBC-2017 PLUMBING
 PERMIT-20061293
  
 CODES IN EFFECT:
  
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I DO NOT SEE THE HRCD RESPONSE THAT IS SUPPOSED TO
 BE ATTACHED. PLEASE RESPOND TO PREVIOUS REVIEW
 COMMENTS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 2) SHOWER IN RESTROOM A-116 SHALL COMPLY WITH FBC ACC
 213.1, 608.1
 3) PLAN PAGE P-1 AND A104 INDICATES A DIFFERENT
 RESTROOM LAYOUT AND DOES NOT MATCH THE RESTROOMS ON ON
 A-3A. PLEASE REMOVE/ REVISE THE PLAN TO SHOW THE
 PROPOSED NEW RESTROOM FLOOR PLANS.WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1
 4) PLEASE SHOW ALL INTERIOR RESTROOM DIMENTIONS
 REQUIRED FOR A-108. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1
 5) WATER ISOMETRIC ON P-1 SHALL INDICATE ALL PIPE SIZES
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 6) COUNTERTOP IN OFFICE A-106 SHALL HAVE A MAX HEIGHT
 OF 34" ABOVE FINISHED FLOOR FBC ACC 606.3
 NO FURTHER PLAN REVIEW WILL BE DONE ON THIS PERMIT
 APPLICATION UNTIL THE QUALIFIER OF THE COMPANY CONTACTS
 THE PLUMBING PLANS EXAMINER AND MEETS WITH THE PLUMBING
 PLANS EXAMINER TO REVIEW AND DISCUSS THESE PLAN REVIEW
 COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-12-02 Cont ID  
Sent By ccole Date 2020-12-02 Time 08:38 Rev Time 0.00
Received By ccole Date 2020-12-01 Time 16:44 Sent To  
Notes
2020-12-02 08:39:073RD REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 12/2/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST AND 2ND REVIEW PRINTED BELOW
 STILL EXIST. PLEASE NOTE A CORRECTED P1 PLAN SHEET AND
 UPDATED RESPONSE NARRATIVES FROM THE AOR AND EOR WERE
 NOT SUBMITTED. NOTES IN CAPS HAVE BEEN ADDED TO FAILED
 COMMENTS.
  
 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY
 THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 SERVICE SINK ON THE FLOOR PLAN. NOT PROVIDED. THE
 ARCHITECT AND ENGINEER OF RECORD SHALL PLEASE PROVIDE
 THE CALCULATIONS AND ADD INSTALLATION OF PRIVATE
 RESTROOMS TO THE SCOPE OF WORK FOR THE PROJECT.
  
 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE
 OR FEMALE- SECTION 403.2. NOT PROVIDED- SEE COMMENT #1.
  
 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE
 CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE
 AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED
 IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2. NO
 CHANGES WERE MADE TO THE PLUMBING PLAN- PLANS REMAIN
 NON-COMPLIANT.
  
 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE
 A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION
 TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER
 CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN
 COMPLIANCE WITH SECTION 912.1. NO CHANGES WERE MADE TO
 THE PLUMBING PLANS- THE PLAN DEPICTS A NON-COMPLIANT
 HORIZONTAL WET VENT FOR THE RESTROOM A-108.
  
 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER
 RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED-
 SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5 FBC P. NO CHANGES WERE
 MADE TO THE PLUMBING PLANS- PLANS REMAIN NON-COMPLIANT.
  
 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P. NO CHANGES
 WERE MADE TO THE PLUMBING PLANS- PLANS REMAIN
 NON-COMPLIANT.
  
 9) A3: ITEMS A, B, C, D, I NON-COMPLIANT.
  
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3. DIMENSIONS OF
 CLEAR FLOOR SPACES NOT SHOWN.
  
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2. DIMENSIONS OF CLEAR
 FLOOR SPACES NOT SHOWN.
  
 C) FAILED. ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES. PLEASE NOTE THAT DOOR A-10 SHALL
 NOT SWING INTO REQUIRED CLEAR FLOOR SPACES FOR THE
 LAVATORY. PLEASE SEE SECTION 603.2.3 EXCEPTIONS #1 & #2
 AND SHOW COMPLIANCE.
  
 D) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 DIAMETERS NOT PROVIDED.
  
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 & 609.4. GRAB BAR HEIGHTS ARE
 MEASURED FROM THE FINISHED FLOORS TO THE TOP OF THE
 GRIPPING SURFACES.
  
 J) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6. NOT PROVIDED.
 L) FAILED. HEIGHTS OF THE MIRROR FROM THE FINISHED
 FLOORS TO THE BOTTOMS OF THE REFLECTIVE SURFACES-
 SECTION 603.3. THE DRAWING SHOWS THE MEASUREMENT TO THE
 BOTTOM OF THE FRAME NOT THE REFLECTIVE SURFACE.
  
 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
 NOT PROVIDED.
  
 NEW COMMENTS.
  
 11) SHEET P1: PLEASE PROVIDE A PLUMBING RISER DRAWING
 FOR THE NEW HI-LO DRINKING FOUNTAIN- SECTION
 107.3.5.1.3 WPB.
  
 12) A3 & A5: REFER TO BUILDING REVIEW COMMENT #1A
 CONCERNING THE NEW LAVATORY CABINET IN THE ADA
 RESTROOM. IN ADDITON PLEASE PROVIDE THE DIMENSIONS OF
 THE CLEAR FLOOR SPACE DIAGRAMS FPOR THE WATER CLOSET
 AND LAVATORY, AND TURNING CIRCLE DIAMETER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-10-15 Cont ID  
Sent By ccole Date 2020-10-15 Time 14:58 Rev Time 0.00
Received By ccole Date 2020-10-15 Time 10:58 Sent To  
Notes
2020-10-15 14:58:532ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 10/15/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW PRINTED BELOW WERE NOT
 ADDRESSED. PLEASE NOTE THE CORRECTED P1 PLAN AND THE
 RESPONSE NARRATIVE FROM THE ENGINEER OF RECORD- HRCD
 WERE NOT SUBMITTED. PLEASE SEE ADDITIONAL NOTES IN CAP
 LETTERS UNDER COMMENT 9.
  
 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY
 THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 SERVICE SINK ON THE FLOOR PLAN.
  
 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE
 OR FEMALE- SECTION 403.2.
  
 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE
 CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE
 AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED
 IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2.
  
 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE
 A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION
 TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER
 CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN
 COMPLIANCE WITH SECTION 912.1.
  
 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER
 RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED-
 SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5 FBC P.
  
 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 8) SHEET A1: PLEASE UPDATE THE 2012 FL. ACCESSIBILITY
 CODE REFERENCE TO THE 2017 SIXTH EDITION.
  
 9) A3 & P1: THE NEW TOILETS ROOMS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE
 ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING: THE
 REQUESTED ENLARGED DRAWINGS WERE NOT PROVIDED. COMMENTS
 (A- L ) ARE MARKED PASSED, FAILED, OR NOT REQUIRED.
 A) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE WATER CLOSETS- SECTION 604.3.
 B) FAILED. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS
 FOR THE LAVATORIES- SECTION 606.2.
 C) FAILED. ENTRY DOOR WIDTHS, DOOR SWING, AND
 WHEELCHAIR APPROACHES- SECTION 604.8.1.2 & 604.8.1.3.
 PLEASE NOTE THAT DOORS SHALL NOT SWING INTO REQUIRED
 CLEAR FLOOR SPACES FOR FIXTURES. DOOR A-10 MUST BE
 REVERSABLE.
 D) FAILED. TURNING SPACE DIAMETERS- SECTION 304.3.
 E) PASSED. CENTERLINES OF THE WATER CLOSETS FROM THE
 SIDE WALL- SECTION 604.2.
 F) NOT REQUIRED FOR PRIVATE TOILET FOOMS. HEIGHTS OF
 THE WATER CLOSET SEATS FROM THE FINISHED FLOORS-
 SECTION 604.4.
 G) NOT REQUIRED FOR PRIVATE TOILET ROOMS. HEIGHTS OF
 THE FRONT RIM OF THE LAVATORIES FROM THE FINISHED
 FLOORS- SECTION 606.3
 H) NOT REQUIRED FOR PRIVATE TOILET ROOMS. KNEE AND TOE
 CLEARANCES FOR THE LAVATORIES- SECTION 306.
 I) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS- SECTION 604.5 & 609.4
 J) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROLS-
 SECTION 604.6.
 K) FAILED. LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS
 FOR THE TOILET PAPER DISPENSERS- SECTION 604.7.
 L) FAILED. HEIGHTS OF THE MIRROR FROM THE FINISHED
 FLOORS TO THE BOTTOMS OF THE REFLECTIVE SURFACES-
 SECTION 603.3.
  
 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 11) PROVIDE FINISH MATERIAL SCHEDULES FOR THE TOILET
 ROOM FLOORS AND WALLS- SECTION 310.3 FBC P AND SECTION
 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-08-14 Cont ID  
Sent By ccole Date 2020-08-13 Time 07:27 Rev Time 0.00
Received By ccole Date 2020-08-13 Time 12:44 Sent To  
Notes
2020-08-14 07:28:111ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20061293
 8/13/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: REFER TO TABLE 403.3 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR THE OCCUPANCY.
 PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED PLUMBING FIXTURES, AND IDENTIFY
 THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS AND
 SERVICE SINK ON THE FLOOR PLAN.
  
 2) P1: PLEASE LABEL THE NEW TOILET ROOMS AS EITHER MALE
 OR FEMALE- SECTION 403.2.
  
 3) P1: THE 4" SANITARY DRAIN FROM RR A-104 CANNOT MAKE
 CONNECTION INTO THE 3" SANITARY DRAIN SERVING OFFICE
 AND RR A-106 BECAUSE DRAINAGE PIPES CANNOT BE REDUCED
 IN SIZE IN THE DIRECTION OF FLOW- SECTION 704.2.
  
 4) P1: INDICATE THE SIZE OF THE SINK DRAIN FROM OFFICE
 A-106. PLEASE NOTE THAT THE DRAIN MUST MAKE CONNECTION
 TO THE MAIN DRAIN AT A POINT DOWNSTREAM OF THE WATER
 CLOSET IN ORDER FOR THE WET VENT IN RR-106 TO BE IN
 COMPLIANCE WITH SECTION 912.1.
  
 5) P1: A NEW BACKFLOW PREVENTER IS SHOWN ON THE WATER
 RISER PLEASE NOTE A SEPARATE PERMIT IS REQUIRED-
 SECTION 107.2.1. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC, 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 6) P1: INDICATE HOW TEMPERED WATER WILL BE PROVIDED TO
 THE LAVATORIES- SECTION 416.5 FBC P.
  
 7) P1: PROVIDE A PLUMBING FIXTURE AND DEVICE SCHEDULE-
 SECTION 107.2.1 WPB & SECTION 405.9 FBC P.
  
 8) SHEET A1: PLEASE UPDATE THE 2012 FL. ACCESSIBILITY
 CODE REFERENCE TO THE 2017 SIXTH EDITION.
  
 9) A3 & P1: THE NEW TOILETS ROOMS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FLORIDA ACCESSIBILITY CODE- 2017
 SIXTH EDITION. REFER TO SECTION 213 AND PROVIDE
 ENLARGED, DIMENSIONED TOILET ROOM DRAWINGS SHOWING:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) ENTRY DOOR WIDTHS, DOOR SWING, AND WHEELCHAIR
 APPROACHES- SECTION 604.8.1.2 & 604.8.1.3. PLEASE NOTE
 THAT DOORS SHALL NOT SWING INTO REQUIRED CLEAR FLOOR
 SPACES FOR FIXTURES.
 D) TURNING SPACE DIAMETERS- SECTION 304.3.
 E) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
 F) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 G) HEIGHTS OF THE FRONT RIM OF THE LAVATORIES FROM THE
 FINISHED FLOORS- SECTION 606.3
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4
 J) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SECTION
 604.6.
 K) LOCATION, CLEARANCE, AND MOUNTING HEIGHTS FOR THE
 TOILET PAPER DISPENSERS- SECTION 604.7.
 L) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO
 THE BOTTOMS OF THE REFLECTIVE SURFACES- SECTION 603.3.
  
 10) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 11) PROVIDE FINISH MATERIAL SCHEDULES FOR THE TOILET
 ROOM FLOORS AND WALLS- SECTION 310.3 FBC P AND SECTION
 1210.2.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2021-04-28 Cont ID  
Sent By medwards Date 2021-04-28 Time 09:19 Rev Time 0.00
Received By medwards Date 2021-04-28 Time 09:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2021-04-01 Cont ID  
Sent By medwards Date 2021-04-01 Time 13:32 Rev Time 0.00
Received By medwards Date 2021-04-01 Time 13:27 Sent To  
Notes
2021-04-01 13:32:45SEE PROVIOUS COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-03-05 Cont ID  
Sent By medwards Date 2021-03-05 Time 14:02 Rev Time 0.00
Received By medwards Date 2021-03-05 Time 14:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-12-30 Cont ID  
Sent By medwards Date 2020-12-30 Time 08:15 Rev Time 0.00
Received By medwards Date 2020-12-30 Time 08:15 Sent To  
Notes
2020-12-30 08:15:47PLEASE SEE ORIGINAL SIGNATURE REVIEW COMMENTS. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-23 Cont ID  
Sent By equinone Date 2020-10-23 Time 14:26 Rev Time 0.00
Received By equinone Date 2020-10-23 Time 09:07 Sent To  
Notes
2020-10-23 09:12:23ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 DIGITAL SIGNATURE FOR ELECTRICAL, MECHANICAL, PLUMBING
 AND STRUCTURAL DRAWINGS IS EXPIRED. PLEASE RESUBMIT
 THESE DRAWINGS WITH AND UNEXPIRED AND VALID DIGITAL
 CERTIFICATE.
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-19 Cont ID  
Sent By fgiaquin Date 2020-08-19 Time 22:16 Rev Time 0.00
Received By fgiaquin Date 2020-08-19 Time 22:16 Sent To  
Notes
***NONE***