Plan Review Details - Permit 20061252
Plan Review Stops For Permit 20061252
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By cthroop Date 2020-10-21 Time 11:30 Rev Time 0.00
Received By cthroop Date 2020-10-21 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By cthroop Date 2020-08-05 Time 14:25 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 11:07 Sent To  
Notes
2020-08-05 14:49:35PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SITE DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
  
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 2. PROVIDE FINISHED FLOOR ELEVATION.
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 3. PALM BEACH COUNTY IMPACT FEES ARE REQUIRED. SEE
 COMMENTS UNDER IMPACT FEE REVIEW.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS, EXTERIOR
 DOORS AND PRE-CAST LINTELS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 DEFERRAL OPTION
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. DESIGNER OF RECORD SHALL SPECIFY ROOF/CEILING
 INSULATION R VALUE.
 107.2 CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC
 EC.
  
 7. PROVIDE THE ICC ES EVALUATION REPORT FOR THE
 PROPOSED ICYNENE SPRAY FOAM INSULATION. DESIGNER SHALL
 INDICATE SYSTEM TO BE INSTALLED. A COPY OF THE REPORT
 SHALL BE ON SITE FOR INSPECTION.
 107.2 CONSTRUCTION DOCUMENTS.
  
 8. A SEPERATE GAS PERMIT AND PLANS ARE REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By cthroop Date 2020-08-05 Time 15:17 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 11:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-08-05 Cont ID  
Sent By tklarge Date 2020-08-05 Time 09:57 Rev Time 0.00
Received By tklarge Date 2020-08-05 Time 09:57 Sent To  
Notes
2020-08-05 09:58:47A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 09:56 Rev Time 0.00
Received By medwards Date 2020-10-22 Time 16:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-21 Cont ID  
Sent By cthroop Date 2020-10-21 Time 11:30 Rev Time 0.00
Received By cthroop Date 2020-10-06 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-11 Cont ID  
Sent By lmarchan Date 2020-08-11 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2020-07-16 Time 14:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-12-04 Cont ID  
Sent By lmarchan Date 2020-12-04 Time 08:47 Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 10:55 Sent To  
Notes
2020-12-04 08:47:41MU-2020-047235 - $0.00 DUE
2020-11-06 10:55:1411/6/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By cthroop Date 2020-08-05 Time 14:02 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 11:06 Sent To  
Notes
2020-08-05 14:02:34IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 09:51 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 09:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-10-07 Cont ID  
Sent By medwards Date 2020-10-07 Time 14:56 Rev Time 0.00
Received By medwards Date 2020-10-07 Time 09:18 Sent To  
Notes
2020-10-07 14:57:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20061252
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE LABEL DRAWINGS AS TO WHICH FLOOR IT APPLIES
 TO. FBC 107.2.1
  
 2) PLEASE IDENTIFY EACH ROOM ON THE MECHANICAL
 DRAWINGS. FBC 107.2.1
  
 3) IS THE LOCATION OF AHU-1 IN THE ATTIC? FBC EC
 R403.3.6
  
 4) PLEASE SHOW RETURN AIR DUCT SIZE FOR AHU-1 THAT IS
 RETURNING AIR FROM WHAT APPEARS TO BE A BEDROOM, AND
 THE RETURN AIR DUCT FROM AHU-3 FOR BEDROOM. FBC 107.2.1
  
 5) PLEASE SHOW THAT THE RETURN AIR PATH MEETS FBC RES
 M1602.3
  
 6) PLEASE SHOW BATHROOM EXHAUST FAN TERMINATIONS. FBC
 107.2.1
  
 7) PROVIDE SPECS FOR THE BATHROOM EXHAUST FANS. FBC RES
 M1507.4
  
 8) PLEASE SHOW DRYER DUCTS AND TERMINATION. FBC 107.2.1
  
 9) PLEASE SHOW CONDENSATE DISPOSAL. FBC RES M1411.3
  
 10) THE SUPPLY DUCT FEEDING THE OPPOSITE SIDE OF HOUSE
 FROM AHU-1 IS TIED INTO THE RETURN BOX.
  
 11) PLEASE SHOW HOW THE CONDENSING UNITS WILL BE
 SECURED. FBC RES M1307.
  
 12) PROVIDE INFORMATION ON THE RANGE. IS A HOOD GOING
 TO BE USED? IF SO PROVIDE CFM?S. FBC RES M1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By hmoser Date 2020-07-28 Time 11:27 Rev Time 0.00
Received By hmoser Date 2020-07-28 Time 10:57 Sent To  
Notes
2020-07-28 11:27:28PLAN DENIED
 NO ENERGY CALCULATIONS OR PLAN SUBMITTED WITH PLANS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By tklarge Date 2020-08-05 Time 09:57 Rev Time 0.00
Received By tklarge Date 2020-08-05 Time 08:42 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-10-21 Cont ID  
Sent By cthroop Date 2020-10-21 Time 10:45 Rev Time 0.00
Received By cthroop Date 2020-10-21 Time 10:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By cthroop Date 2020-08-05 Time 14:21 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 11:07 Sent To  
Notes
2020-08-05 14:25:11PLAN REVIEW - ROOFING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 DEFERRAL OPTION
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-10-28 Cont ID  
Sent By medwards Date 2020-10-28 Time 09:56 Rev Time 0.00
Received By medwards Date 2020-10-28 Time 09:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-07 Cont ID  
Sent By medwards Date 2020-10-07 Time 15:09 Rev Time 0.00
Received By medwards Date 2020-10-07 Time 15:04 Sent To  
Notes
2020-10-07 15:08:58THE DESIGNER OF THE MECHANICAL SHEETS MUST SIGN THE
 DRAWINGS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-05 Cont ID  
Sent By cthroop Date 2020-08-05 Time 13:02 Rev Time 0.00
Received By cthroop Date 2020-08-05 Time 11:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-11 Cont ID  
Sent By kalexand Date 2020-08-11 Time 13:01 Rev Time 0.00
Received By kalexand Date 2020-08-11 Time 12:30 Sent To I
Notes
***NONE***