Plan Review Details - Permit 20061205
Plan Review Stops For Permit 20061205
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By pvalenti Date 2020-09-22 Time 14:56 Rev Time 0.00
Received By pvalenti Date 2020-09-22 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-19 Cont ID  
Sent By pvalenti Date 2020-08-19 Time 09:09 Rev Time 0.00
Received By pvalenti Date 2020-08-19 Time 09:08 Sent To  
Notes
2020-08-19 09:15:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2 ND BUILDING REVIEW DENIED:
  
 THE GENERATOR PAD SPECIFICATION, SUBMITTED ON PAPER, BY
 AMERICAST DOES NOT:
 1) FAILED, INDICATE COMPATIBILITY WITH PERKINS
 GENERATOR AGP56
 2) OK, WIND SPEED AND EXPOSURE SHOWN ON THE SUBMITTAL
 ARE ABOVE THE REQUIRED WIND SPEED.
 3) FAILED, HAVE AN ORIGINAL SIGNATURE AND SEAL BY
 ENGINEER
  
 PLEASE SUBMIT THE GENERATOR PAD SPECIFICATIONS WITH THE
 REQUIREMENTS NOTED ABOVE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-11 Cont ID  
Sent By pvalenti Date 2020-08-11 Time 14:44 Rev Time 0.00
Received By pvalenti Date 2020-08-11 Time 14:44 Sent To  
Notes
2020-08-11 14:53:16PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 THE GENERATOR PAD SPECIFICATION, SUBMITTED ON PAPER, BY
 AMERICAST DOES NOT:
  
 1) INDICATE COMPATIBILITY WITH PERKINS GENERATOR AGP56
 2) INDICATE THE CORRECT WIND DESIGN REQUIREMENTS
 3) HAVE AN ORIGINAL SIGNATURE AND SEAL BY ENGINEER
  
 PLEASE SUBMIT THE GENERATOR PAD SPECIFICATIONS WITH THE
 REQUIREMENTS NOTED ABOVE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 11:52 Rev Time 0.00
Received By jleahy Date 2020-10-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-08-27 Cont ID  
Sent By cthroop Date 2020-08-27 Time 15:23 Rev Time 0.00
Received By cthroop Date 2020-08-27 Time 15:19 Sent To  
Notes
2020-08-27 15:28:24PLAN REVIEW GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 SEE 1ST REVIEW COMMENTS BELOW:
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) ELECTRICAL PLAN IS NOT SIGNED PRINT NAME, SUGN NAME,
 DATE IT.
  
 2) VALUE FOR PERMIT IS TOO LOW, PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE WORK INVOLVED, MUST INCLUDE GEN SET,
 TRANSFER SWITCH, WIRE AND LABOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
  
 NEW COMMENTS:
  
 1) PROVIDE NEW LOAD CALCULATIONS.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-18 Cont ID  
Sent By jleahy Date 2020-08-18 Time 13:55 Rev Time 0.00
Received By jleahy Date 2020-08-18 Time 13:38 Sent To  
Notes
2020-08-18 13:58:27 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) ELECTRICAL PLAN IS NOT SIGNED PRINT NAME, SUGN NAME,
 DATE IT.
  
 2) VALUE FOR PERMIT IS TOO LOW, PLEASE SUBMIT A SIGNED
 CONTRACT FOR THE WORK INVOLVED, NUST INCLUDE GEN SET,
 TRAN, SWITXH, WIRE AND LABOR.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-27 Cont ID  
Sent By cthroop Date 2020-08-27 Time 15:31 Rev Time 0.00
Received By cthroop Date 2020-08-18 Time 17:55 Sent To  
Notes
2020-08-18 17:56:1708/18/2020 RESUBMITTAL SENT TO PETER VALENTI'S DESK FOR
 REVIEW & SIGNATURE. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-18 Cont ID  
Sent By hmoser Date 2020-08-18 Time 17:55 Rev Time 0.00
Received By jgomez Date 2020-07-29 Time 15:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-08-12 Cont ID  
Sent By hmoser Date 2020-08-12 Time 07:49 Rev Time 0.00
Received By hmoser Date 2020-08-05 Time 09:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By pvalenti Date 2020-09-22 Time 14:56 Rev Time 0.00
Received By pvalenti Date 2020-09-22 Time 14:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-19 Cont ID  
Sent By pvalenti Date 2020-08-19 Time 09:06 Rev Time 0.00
Received By pvalenti Date 2020-08-19 Time 09:05 Sent To  
Notes
2020-08-19 09:08:26PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, FS 471 & FAC 61G15?23.002; THE SUBMITTED
 PLANS FOR THE GENERATOR PAD NEED TO BE DIGITALLY
 SIGNED/SEALED WITH 3RD PARTY VERIFICATION OR PAPER
 ORIGINAL SIGNED AND SEALED CAN BE DELIVERED TO THE
 BUILDING DEPARTMENT?S DROP BOX LOCATED TO THE ENTRY TO
 CITY HALL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-08-11 Cont ID  
Sent By pvalenti Date 2020-08-11 Time 16:19 Rev Time 0.00
Received By pvalenti Date 2020-08-11 Time 16:19 Sent To  
Notes
2020-08-11 16:24:46PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, FS 471 & FAC 61G15-23.002; THE SUBMITTED
 PLANS FOR THE GENERATOR PAD NEED TO BE DIGITALLY
 SIGNED/SEALED WITH 3RD PARTY VERIFICATION OR PAPER
 ORIGINAL SIGNED AND SEALED CAN BE DELIVERED TO THE
 BUILDING DEPARTMENT'S DROP BOX LOCATED TO THE ENTRY TO
 CITY HALL.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-08-18 Cont ID  
Sent By kalexand Date 2020-08-18 Time 16:51 Rev Time 0.00
Received By kalexand Date 2020-08-18 Time 16:51 Sent To I
Notes
***NONE***