Plan Review Details - Permit 20061168
Plan Review Stops For Permit 20061168
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By cthroop Date 2020-07-01 Time 09:00 Rev Time 0.00
Received By cthroop Date 2020-06-30 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 10:35 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jpearson Date 2020-07-02 Time 17:43 Rev Time 0.00
Received By jleahy Date 2020-07-02 Time 17:36 Sent To  
Notes
2020-07-02 17:47:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 REVISION IS NOT CLOUDED TO MUCH TO LOOK AT TO FIGURE
 OUT WHAT HAS BEEN CHANGED ON PLAN, PLEASE CLOUD THE
 REVISIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By pleduc Date 2020-06-29 Time   Rev Time 0.00
Received By pleduc Date 2020-06-29 Time 10:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-07 Cont ID  
Sent By abelisle Date 2020-08-07 Time 17:52 Rev Time 0.00
Received By abelisle Date 2020-08-07 Time 17:05 Sent To  
Notes
2020-08-07 17:53:578/7/2020 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-28 Cont ID  
Sent By abelisle Date 2020-07-28 Time 17:59 Rev Time 0.00
Received By abelisle Date 2020-07-28 Time 16:17 Sent To  
Notes
2020-07-28 18:05:30CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 7/28/2020 2ND GAS REVIEW **DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1-SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 PIPE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC
 FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS
 RES SECS. G2413.4.1, G2413.4.2.
  
 2- SUBMIT A DETAIL SHOWING THE TYPE OF MATERIAL, SIZE,
 TERMINATION POINTS OF THE GAS SLEEVES PER 2017 FBC FUEL
 GAS SEC 404.4
  
 3- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-01 Cont ID  
Sent By tklarge Date 2020-07-01 Time 14:20 Rev Time 0.00
Received By abelisle Date 2020-06-30 Time 18:43 Sent To  
Notes
2020-07-01 14:36:38CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 7/1/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS NOTE -
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1-SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 2- EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF
 VALVE IN ACCORDANCE WITH SECTION 409.5.1, 409.5.2 OR
 409.5.3.
  
 3- SEPERATE PERMIT REQUIRED FOR LP TANK
  
 4- SUBMIT A DETAIL SHOWING THE TYPE OF MATERIAL, SIZE,
 TERMINATION POINTS OF THE GAS SLEEVES PER 2017 FBC FUEL
 GAS SEC 404.4
  
 5- SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 6- INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF. WPB AMEND. TO FBC SEC. 107.2.1.
  
 7- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 8- WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-08 Cont ID  
Sent By cthroop Date 2020-08-08 Time 07:07 Rev Time 0.00
Received By cthroop Date 2020-08-04 Time 13:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By shill Date 2020-07-30 Time 10:06 Rev Time 0.00
Received By shill Date 2020-07-24 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-02 Cont ID  
Sent By jleahy Date 2020-07-02 Time 17:47 Rev Time 0.00
Received By jleahy Date 2020-06-24 Time 08:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 07:46 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 07:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-07 Cont ID  
Sent By abelisle Date 2020-08-07 Time 17:58 Rev Time 0.00
Received By abelisle Date 2020-08-07 Time 17:58 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-28 Cont ID  
Sent By abelisle Date 2020-07-28 Time 17:58 Rev Time 0.00
Received By abelisle Date 2020-07-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-06-30 Cont ID  
Sent By tklarge Date 2020-06-30 Time 18:39 Rev Time 0.00
Received By abelisle Date 2020-06-30 Time 16:36 Sent To  
Notes
2020-06-30 18:43:246/30/2020 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-08 Cont ID  
Sent By cthroop Date 2020-08-08 Time 07:06 Rev Time 0.00
Received By cthroop Date 2020-08-08 Time 07:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By shill Date 2020-07-30 Time 10:06 Rev Time 0.00
Received By shill Date 2020-07-30 Time 10:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By cthroop Date 2020-07-01 Time 08:14 Rev Time 0.00
Received By cthroop Date 2020-06-30 Time 07:48 Sent To  
Notes
***NONE***