| 2020-07-07 11:36:58 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: REVISION # 20061164 (TO PERMIT |
| | #17101193) |
| | ADD: 325 S. LAKESIDE CT. / 3 FLOORS OF RENOVATION |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THIS PROJECT WAS APPLIED FOR UNDER THE 2014 FLORIDA |
| | BUILDING CODE. THEREFORE, ALL REVISIONS AND SUBMITTALS |
| | SHALL SPECIFY THE 2014 FBC. SHEET T-1 SPECIFIES THE |
| | 2017 FLORIDA BUILDING CODES. PLEASE CHANGE TO THE 2014 |
| | FBC. |
| | |
| | 2) SHEET T-1 INDICATES THAT THIS BUILDING IS |
| | UNPROTECTED AND UNSPRINKLERED. THIS BUILDING IS WOOD |
| | FRAME AND IS THREE (3) STORIES. THIS MAKES IT TYPE V-B |
| | CONSTRUCTION. FBC TABLE 503, REQUIRES A THREE STORY |
| | WOOD FRAME BUILDING WITH AN R-2 OCCUPANCY TYPE TO BE |
| | TYPE V-A CONSTRUCTION. THIS MEANS THAT THE BUILDING |
| | WILL HAVE TO BE PROTECTED IN ACCORDANCE WITH FBC 601 OR |
| | BE SPRINKLERED. SHOW HOW THIS ISSUE WILL BE RESOLVED. |
| | |
| | 3) ON SHEET A-5 THE NEW GUARDS ARE SPECIED AS 14" HIGH, |
| | INSTEAD OF THE REQUIRED THE 42" THAT IS REQUIRED. FBC |
| | 1013 |
| | |
| | 4) THE PLANS DO NOT APPEAR TO SHOW THE THERMAL |
| | INSULATION UNDER THE FIRST FLOOR, IN THE EXTERIOR |
| | WALLS, IN THE FLOOR CEILING ASSEMBLIES BETWEEN THE |
| | UNITS AND IN THE CEILING OF THE THIRD FLOOR UNITS. FBC |
| | -ENERGY CONSERVATION |
| | |
| | 5) SPECIFY THE NUMBER AND TYPE OF ANCHORS THAT ARE |
| | REQUIRED TO ATTACH THE THE ROOF LADDER TO THE |
| | STRUCTURE. SPECIFY THE BACKING TO BE USED IF REQUIRED |
| | TO PROVIDE A SUBSTRATE FOR ANCHORS. FBC 107 & 1601 |
| | |
| | 6) PROVIDE THE LISTING INFORMATION FOR THE |
| | FLOOR/CEILING FIRE RATED ASSEMBLY L508 THAT IS |
| | SPECIFIED ON THE DRAWINGS. FBC 107 & 703 |
| | |
| | 7) PROVIDE FIRE STOPPING DETAILS FOR PENETRATIONS OF |
| | FIRE RATED ASSEMBLIES. FBC 107 & 701 |
| | |
| | 8) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| | COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| | PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| | WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR |
| | DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED, |
| | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED |
| | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. |
| | |
| | 9) SUBMIT THE SPECIFICATIONS AND INSTALLATION |
| | REQUIREMENTS FOR THE EPICORE FLOOR/CEILING SYSTEM. FBC |
| | 107 |
| | |
| | 10) SUBMIT THE SPECIFICATIONS AND INSTALLATION |
| | REQUIREMENTS FOR THE WATER PROOFING MEMBRANE AT THE |
| | BALCONIES. FBC 107 |
| | |
| | 11) SUBMIT SHOP DRAWING FOR THE BALCONY AND STAIR |
| | GUARDS AND HANDRAILS. FBC 107 & 1013 |
| | |
| | 12) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 13) SHOW COMPLIANCE WITH FBC 1203.3 FOR UNDER-FLOOR |
| | VENTILATION. |
| | |
| | 14) ELEVATION 1 ON SHEET A-6 HAS A NOTE FOR A |
| | PRE-ENGINEERED ALUMINIUM WALKWAY COVER. SECTION 3 ON |
| | SHEET S-5 HAS SLOPED PLYWOOD ON 2X6 WOOD RAFTERS ROOF |
| | OVER THE BALCONIES. PLEASE CLARIFY. FBC 107 |
| | |
| | 15) AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| | BE USED. |
| | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE |
| | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| | |
| | 16) SUBMIT THE COVERSHEET WITH THE FL# (FL24546.1) FOR |
| | THE ROOF STAND DOCUMENTS THAT WERE SUBMITTED. |
| | FL24546.1. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |
| | |