Plan Review Details - Permit 20061126
Plan Review Stops For Permit 20061126
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 10:45 Rev Time 0.00
Received By rmcphers Date 2020-07-09 Time 10:42 Sent To  
Notes
2020-07-09 10:45:47FOR MASTER PERMIT - 19070081

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-07-31 Cont ID  
Sent By hmoser Date 2020-07-31 Time 09:41 Rev Time 0.00
Received By hmoser Date 2020-07-27 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-23 Cont ID  
Sent By lmarchan Date 2020-07-23 Time 13:35 Rev Time 0.00
Received By lmarchan Date 2020-07-16 Time 15:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-15 Cont ID  
Sent By lmarchan Date 2020-07-15 Time 09:26 Rev Time 0.00
Received By lmarchan Date 2020-07-09 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-09 Cont ID  
Sent By rmcphers Date 2020-07-09 Time 10:46 Rev Time 0.00
Received By rmcphers Date 2020-06-23 Time 13:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-07-31 Cont ID  
Sent By hmoser Date 2020-07-31 Time 11:42 Rev Time 0.00
Received By hmoser Date 2020-07-30 Time 14:02 Sent To  
Notes
2020-07-31 09:32:59IF WALK IN COOLER IS OUTSIDE WIND LOADS ON COOLER WILL
 BE REQUIRED
 FOR FINAL INSPECTION,
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-07-23 Time 11:54 Rev Time 0.00
Received By medwards Date 2020-07-22 Time 10:37 Sent To  
Notes
2020-07-23 11:54:223RD REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MECHANICAL ENGINEER MUST PROVIDE INFORMATION FROM
 CHAPTER 11 OF THE FBC M SEE BELOW.
  
 SECTION1102
 SYSTEM REQUIREMENTS
 1102.1GENERAL.
 THE SYSTEM CLASSIFICATION, ALLOWABLE REFRIGERANTS,
 MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, LOCATION
 LIMITATIONS, AND FIELD PRESSURE TEST REQUIREMENTS SHALL
 BE DETERMINED AS FOLLOWS:
 1. 1.DETERMINE THE REFRIGERATION SYSTEM'S
 CLASSIFICATION, IN ACCORDANCE WITH SECTION 1103.3.
 2. 2.DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
 3. 3.DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
 4. 4.DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
 5. 5.REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
 6. 6.NONFACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
 1104.4VOLUME CALCULATIONS.
 VOLUME CALCULATIONS SHALL BE IN ACCORDANCE WITH
 SECTIONS 1104.4.1 THROUGH 1104.4.3.
 1104.4.1NONCOMMUNICATING SPACES.
 WHERE THE REFRIGERANT-CONTAINING PARTS OF A SYSTEM ARE
 LOCATED IN ONE OR MORE SPACES THAT DO NOT COMMUNICATE
 THROUGH PERMANENT OPENINGS OR HVAC DUCTS, THE VOLUME OF
 THE SMALLEST, ENCLOSED OCCUPIED SPACE SHALL BE USED TO
 DETERMINE THE PERMISSIBLE QUANTITY OF REFRIGERANT IN
 THE SYSTEM.
 1104.4.2COMMUNICATING SPACES.
 WHERE AN EVAPORATOR OR CONDENSER IS LOCATED IN AN AIR
 DUCT SYSTEM, THE VOLUME OF THE SMALLEST, ENCLOSED
 OCCUPIED SPACE SERVED BY THE DUCT SYSTEM SHALL BE USED
 TO DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN THE SYSTEM.
 EXCEPTION: IF AIRFLOW TO ANY ENCLOSED SPACE CANNOT BE
 REDUCED BELOW ONE-QUARTER OF ITS MAXIMUM, THE ENTIRE
 SPACE SERVED BY THE AIR DUCT SYSTEM SHALL BE USED TO
 DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF REFRIGERANT
 IN THE SYSTEM.
 1104.4.3PLENUMS.
 WHERE THE SPACE ABOVE A SUSPENDED CEILING IS CONTINUOUS
 AND PART OF THE SUPPLY OR RETURN AIR PLENUM SYSTEM,
 THIS SPACE SHALL BE INCLUDED IN CALCULATING THE VOLUME
 OF THE ENCLOSED SPACE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-14 Time 10:15 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 09:51 Sent To  
Notes
2020-07-14 10:18:592ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20061126
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE NOTE 3 OF ORIGINAL REVIEW. PLEASE SHOW
 WHERE THE CONDENSING UNIT WILL BE LOCATED ON PROPERTY.
 IF IT WILL BE LOCATED ON THE ROOF OF THE STRUCTURE
 PLEASE PROVIDE DETAIL DRAWING OF THE ANCHORAGE IN THE
 WIND ZONE. FBC FS 107.2.1
  
 2) PLEASE PROVIDE SPECS ON THE REFRIGERANT TYPE AND
 AMOUNT USED IN THIS COOLER. SEE FBC M 1102
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By medwards Date 2020-07-08 Time 10:25 Rev Time 0.00
Received By medwards Date 2020-07-08 Time 10:04 Sent To  
Notes
2020-07-08 10:26:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20061126
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS PROJECT WILL ALSO REQUIRE A BUILDING PERMIT AND
 A BUILDING PLAN REVIEW.
  
 2) PLEASE PROVIDE A SURVEY INDICATING WHERE ON THE
 PROPERTY THIS NEW COOLER WILL BE LOCATED. FBC FS
 107.2.1
 3) PLEASE PROVIDE A DETAIL DRAWING SHOWING THE LOCATION
 OF THE COMPRESSOR. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-07-31 Cont ID  
Sent By hmoser Date 2020-07-31 Time 09:41 Rev Time 0.00
Received By hmoser Date 2020-07-31 Time 09:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-07-23 Time 12:01 Rev Time 0.00
Received By medwards Date 2020-07-23 Time 11:55 Sent To  
Notes
2020-07-23 12:01:26PLEASE SEE 2ND CYCLE REVIEW COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-14 Cont ID  
Sent By medwards Date 2020-07-14 Time 10:41 Rev Time 0.00
Received By medwards Date 2020-07-14 Time 10:19 Sent To  
Notes
2020-07-14 10:41:30DESIGNER OF RECORD MUST SIGN AND SEAL SHEETS: Q-01,
 QE-01 AND SPEC SHEET. FBC FS 471.025

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By medwards Date 2020-07-08 Time 10:26 Rev Time 0.00
Received By medwards Date 2020-07-08 Time 10:26 Sent To  
Notes
2020-07-08 10:27:38ENGINEER MUST DIGITALLY SIGN AND SEAL EACH SHEET. FS
 417.025
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  