Plan Review Details - Permit 20061036
Plan Review Stops For Permit 20061036
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-08-02 Cont ID  
Sent By jwitmer Date 2020-08-02 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2020-08-02 Time 09:43 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By jwitmer Date 2020-07-22 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2020-06-30 Time 07:59 Sent To  
Notes
2020-06-30 08:27:27PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-02 Cont ID  
Sent By jwitmer Date 2020-08-02 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2020-08-02 Time 09:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-06-30 Cont ID  
Sent By jwitmer Date 2020-06-30 Time 08:28 Rev Time 0.00
Received By jwitmer Date 2020-06-30 Time 07:58 Sent To  
Notes
2020-06-29 22:05:10IN BUILD PLAN REVIEW. J. WITMER

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-02 Cont ID  
Sent By jleahy Date 2020-08-02 Time 15:02 Rev Time 0.00
Received By jleahy Date 2020-08-02 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-02 Cont ID  
Sent By jleahy Date 2020-07-02 Time 18:28 Rev Time 0.00
Received By jleahy Date 2020-07-02 Time 18:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By pleduc Date 2020-06-29 Time   Rev Time 0.00
Received By pleduc Date 2020-06-29 Time 11:37 Sent To  
Notes
2020-06-29 11:40:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-03 Cont ID  
Sent By lmarchan Date 2020-08-03 Time 15:40 Rev Time 0.00
Received By lmarchan Date 2020-07-29 Time 06:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-22 Cont ID  
Sent By jwitmer Date 2020-07-22 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2020-06-25 Time 14:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By medwards Date 2020-08-03 Time 15:38 Rev Time 0.00
Received By medwards Date 2020-08-03 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-09 Cont ID  
Sent By medwards Date 2020-07-09 Time 16:29 Rev Time 0.00
Received By medwards Date 2020-07-09 Time 16:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-07-31 Cont ID  
Sent By ccole Date 2020-07-31 Time 10:17 Rev Time 0.00
Received By ccole Date 2020-07-31 Time 08:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-30 Cont ID  
Sent By ccole Date 2020-06-30 Time 16:14 Rev Time 0.00
Received By ccole Date 2020-06-30 Time 15:12 Sent To  
Notes
2020-06-30 16:14:341ST REVIEW FBC-2017 PLUMBING
 PERMIT-20061036
 6/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE APPROVED DEMOLITION PLAN UNDER PERMIT #20050101
 INDICATES A TOILET ROOM WAS REMOVED, HOWEVER THE
 BUILD-OUT PLAN DOES NOT INDICATE THE ROOM AND PLUMBING
 FIXTURES ARE BEING REPLACED. PLEASE PROVIDE PLUMBING
 FIXTURE CALCULATIONS FOR THE 3RD FLOOR IN ACCORDANCE
 WITH TABLE 403.3 FBC P. PROVIDE A SCHEDULE INDICATING
 THE REQUIRED AND PROVIDED FIXTURES ON THE FLOOR-
 SECTION 213.1 FBC ACC.
  
 2) SHEET P1 & P2: SHOW THE LOCATION OF THE THERMOSTATIC
 MIXING VALVE THAT IS LISTED IN THE FIXTURE SCHEDULE-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-19 Cont ID  
Sent By medwards Date 2020-08-19 Time 11:46 Rev Time 0.00
Received By medwards Date 2020-08-19 Time 11:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-31 Cont ID  
Sent By ccole Date 2020-07-31 Time 09:48 Rev Time 0.00
Received By ccole Date 2020-07-31 Time 09:44 Sent To  
Notes
2020-07-31 09:50:46SHEETS A0.0, A1.1, A2.1, A3.1, P2, & M2 ARE NOT
 ELECTRONICALLY SIGNED AND SEALED BY THE ARCHITECT AND
 ENGINEER OF RECORD- FL. STATUTES 481.221 & 471.025, AND
 FAC SECTIONS 61G1-16.005 & 61G15.23.005.
 CCOLE- 7/31/2020
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-30 Cont ID  
Sent By ccole Date 2020-06-30 Time 16:15 Rev Time 0.00
Received By ccole Date 2020-06-30 Time 16:15 Sent To  
Notes
2020-06-30 16:24:23THE ARCHITECTURAL AND MEP PLANS ARE NOT ELECTRONICALLY
 SIGNED AND SEALED BY THE ARCHITECT AND ENGINEER OF
 RECORD- FL. STATUTES 481.221 & 471.025, AND FAC
 SECTIONS 61G1-16.005 & 61G15.23.005.
 CCOLE- 6/30/2020
  
  
  
  