Plan Review Details - Permit 20060969
Plan Review Stops For Permit 20060969
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By rmcphers Date 2020-08-03 Time 12:37 Rev Time 0.00
Received By rmcphers Date 2020-08-03 Time 12:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-07 Cont ID  
Sent By rmcphers Date 2020-07-07 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2020-07-07 Time 13:52 Sent To  
Notes
2020-07-07 14:20:15REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SIZE OF THE EXTERIOR FRONT DOOR TO
 BE REPLACED.
 2) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE NEW EXTERIOR DOOR.
 3) PLEASE SHOW THE WIND DESIGN PRESSURES AND THE WIND
 DESIGN CRITERIA FOR THE EXTERIOR DOOR OPENING. FBC
 R301.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-07 Cont ID  
Sent By jleahy Date 2020-07-07 Time 12:31 Rev Time 0.00
Received By jleahy Date 2020-07-07 Time 12:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-03 Cont ID  
Sent By jesmith Date 2020-08-03 Time 15:35 Rev Time 0.00
Received By jesmith Date 2020-08-03 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-20 Cont ID  
Sent By shill Date 2020-07-20 Time 09:12 Rev Time 0.00
Received By shill Date 2020-06-23 Time 11:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-27 Cont ID  
Sent By medwards Date 2020-07-27 Time 12:13 Rev Time 0.00
Received By medwards Date 2020-07-27 Time 12:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-07-08 Cont ID  
Sent By medwards Date 2020-07-08 Time 11:46 Rev Time 0.00
Received By medwards Date 2020-07-08 Time 10:43 Sent To  
Notes
2020-07-08 11:47:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060969
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1 NOTE (1) INDICATES THE MECHANICAL
 CONTRACTOR TO INSTALL A COMPLETE OPERATING SYSTEM. THE
 DRAWINGS DO NOT SHOW THIS SYSTEM, IT ONLY SHOWS DUCT
 WORK FOR NEW MASTER CLOSET AND MASTER BATH AREA. WHERE
 IS THE DUCTWORK FOR THE REST OF THE 2ND STORY? IF THIS
 IS A NEW SYSTEM PLEASE PROVIDE ENERGY CALCULATIONS
 ALONG WITH THE MANUAL J CALCULATIONS FOR THE NEW
 SYSTEM. FBC EC R4.3.7.1
  
 2) PLEASE PROVIDE SPECS FOR THE BATH EXHAUST FAN AND
 SHOW IT ON THE DRAWING, ALONG WITH THE EXHAUST
 TERMINATION LOCATION. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By jesmith Date 2020-08-03 Time 15:34 Rev Time 0.00
Received By jesmith Date 2020-08-03 Time 09:24 Sent To  
Notes
2020-08-03 15:34:3820060969 231 PALMETTO LN
  
  
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20060969 231 PALMETTO LN
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 08:52 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 07:30 Sent To  
Notes
2020-07-06 08:53:25PLUMBING 1ST REVIEW COMMENTS**20060969
 1) PROVIDE A WATER ISOMETRIC. WPB AD 107.3.5
  
 2) PROVIDE NOTE THAT THE TUB WILL BE LIMITED TO 120
 DEGREES MAX TEMP BY AN APPROVED ASSE 1070 DEVICE OR 1
 WILL BE BUILT INTO SUCH VALVE. FBC-PLB 424.5
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 (CAP GOVERNMENT)
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-27 Cont ID  
Sent By medwards Date 2020-07-27 Time 12:22 Rev Time 0.00
Received By medwards Date 2020-07-27 Time 12:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-07 Cont ID  
Sent By rmcphers Date 2020-07-07 Time 14:22 Rev Time 0.00
Received By rmcphers Date 2020-07-07 Time 14:22 Sent To  
Notes
***NONE***