Plan Review Details - Permit 20060902
Plan Review Stops For Permit 20060902
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-25 Cont ID  
Sent By rmcphers Date 2020-08-25 Time 15:19 Rev Time 0.00
Received By rmcphers Date 2020-08-25 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By rmcphers Date 2020-07-27 Time 12:17 Rev Time 0.00
Received By rmcphers Date 2020-07-27 Time 12:06 Sent To  
Notes
2020-07-27 12:16:13POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 - FBC
 R4501.6
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER.
 2) PLEASE SHOW THE CONCRETE STEEL REINFORCING SIZE AND
 LAP REQUIREMENTS.
 3) PLEASE UPDATE OR CORRECT THE CODE SECTIONS
 REFERENCED IN THE GENERAL NOTES ON THE DRAWINGS
 (BARRIER REQUIREMENTS FBC 4501.17)
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM. (AT THIS TIME DROP
 BOX ITEMS MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO
 PLAN REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-25 Cont ID  
Sent By fgiaquin Date 2020-08-25 Time 23:42 Rev Time 0.00
Received By fgiaquin Date 2020-08-25 Time 23:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-29 Cont ID  
Sent By fgiaquin Date 2020-07-29 Time 22:31 Rev Time 0.00
Received By fgiaquin Date 2020-07-29 Time 22:02 Sent To  
Notes
2020-07-29 22:31:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALC FOR EXISTING SERVICE WITH NEW POOL
 LOADS ADDED. NEC 220 FBC 107.2.1
  
 2. SHOW WIRE SIZE, CONDUIT SIZE, OCP FOR FEEDER TO POOL
 PANEL FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-07-28 Cont ID  
Sent By jesmith Date 2020-07-28 Time 16:10 Rev Time 0.00
Received By jesmith Date 2020-07-28 Time 16:08 Sent To  
Notes
2020-07-28 16:10:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060902 509 33RD ST
  
 A SEPARATE GAS PERMIT IS REQUIRED
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 ALL PLANS NOT SIGNED AND SEALED BY A PROFESSIONAL
 ENGINEER OR ARCHITECT, THE GAS/PLUMBING PLAN IN
 ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE
 PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE; PROVIDE PROPERLY SIGNED PAPER
 DOCUMENT IN ACCORDANCE WITH FAC AND FS PRIOR TO PERMIT
 ISSUANCE. CALL 561-805-6724 FOR ADDITIONAL INFORMATION.
  
 END OF COMMENTS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-14 Cont ID  
Sent By pvalenti Date 2020-09-14 Time 16:15 Rev Time 0.00
Received By pvalenti Date 2020-09-11 Time 07:16 Sent To  
Notes
2020-09-11 07:17:11ROUTED TO S4 INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-25 Cont ID  
Sent By fgiaquin Date 2020-08-25 Time 23:43 Rev Time 0.00
Received By fgiaquin Date 2020-08-11 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-29 Cont ID  
Sent By fgiaquin Date 2020-07-29 Time 22:31 Rev Time 0.00
Received By fgiaquin Date 2020-07-07 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-08-13 Cont ID  
Sent By lcrespo Date 2020-08-13 Time 13:30 Rev Time 0.00
Received By lcrespo Date 2020-08-12 Time 15:20 Sent To  
Notes
2020-08-13 13:31:0508/13/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By jesmith Date 2020-07-28 Time 16:11 Rev Time 0.00
Received By jesmith Date 2020-07-28 Time 15:43 Sent To  
Notes
2020-07-28 16:11:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060902 509 33RD ST
  
 A SEPARATE GAS PERMIT IS REQUIRED
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. ALL PLANS NOT SIGNED AND SEALED BY A PROFESSIONAL
 ENGINEER OR ARCHITECT, THE GAS/PLUMBING PLAN IN
 ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE
 PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE; PROVIDE PROPERLY SIGNED PAPER
 DOCUMENT IN ACCORDANCE WITH FAC AND FS PRIOR TO PERMIT
 ISSUANCE. CALL 561-805-6724 FOR ADDITIONAL INFORMATION.
 2. PER WPB FBC 107.2.1, PROVIDE A PIPING RISER DIAGRAM
 OF DISTRIBUTION PIPING, VALVES AND EQUIPMENT.
 3. PROVIDE HYDRAULIC (TDH) CALCULATIONS; PER WPB FBC
 107.2. 1 AND APSP-7-2013, SHALL INCLUDE THE HEAD LOSS
 FOR THE POOL HEATER, FILTER AND ALL OTHER INLINE
 APPURTENANCES AS WELL AS THE VALVES AND FITTINGS. PUMP
 IS NOT INCLUDED IN CALCULATIONS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ALL PLANS TO BE SIGNED BY THE DESIGNER AS REQUIRED BY
 WPB FBC 107.3.4.3, FAC AND FS. PLEASE SEE COMMENT #1
 ABOVE.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-14 Cont ID  
Sent By pvalenti Date 2020-09-14 Time 16:12 Rev Time 0.00
Received By pvalenti Date 2020-09-14 Time 16:12 Sent To  
Notes
2020-09-14 16:14:56PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY COPIES OF DIGITAL
 SIGNATURES, AS PER THE TEMPORARY RULING BY THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-08-25 Cont ID  
Sent By rmcphers Date 2020-08-25 Time 15:19 Rev Time 0.00
Received By rmcphers Date 2020-08-25 Time 15:19 Sent To  
Notes
2020-08-25 15:20:40SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-27 Cont ID  
Sent By rmcphers Date 2020-07-27 Time 12:18 Rev Time 0.00
Received By rmcphers Date 2020-07-27 Time 12:18 Sent To  
Notes
2020-07-27 12:18:31SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2020-07-10 Cont ID  
Sent By rthermid Date 2020-07-10 Time   Rev Time  
Received By rthermid Date 2020-07-10 Time   Sent To I
Notes
***NONE***