Plan Review Details - Permit 20060882
Plan Review Stops For Permit 20060882
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 15:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By rmcphers Date 2020-07-13 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2020-07-13 Time 15:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-19 Cont ID  
Sent By rmcphers Date 2020-06-19 Time 15:18 Rev Time 0.00
Received By rmcphers Date 2020-06-19 Time 15:07 Sent To  
Notes
2020-06-19 15:18:43WINDOWS, DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER. DRAWINGS NEED TO BE DIGITALLY/ELECTRONICALLY
 SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN
 ELECTRONIC PLAN REVIEW.
  
 FYI = ENGINEER CANNOT SELF-CERTIFY THE DIGITAL
 SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 15:33 Rev Time 0.00
Received By rmcphers Date 2020-07-17 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-13 Cont ID  
Sent By rmcphers Date 2020-07-13 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2020-07-06 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-19 Cont ID  
Sent By rmcphers Date 2020-06-19 Time 15:19 Rev Time 0.00
Received By rmcphers Date 2020-06-17 Time 14:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-08-31 Cont ID  
Sent By pvalenti Date 2020-08-31 Time 13:40 Rev Time 0.00
Received By pvalenti Date 2020-08-31 Time 13:40 Sent To  
Notes
2020-08-31 13:42:43PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED BY EMAILED ORIGINAL DIGITAL
 SIGNATURES SENT BY ENGINEER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-08-29 Cont ID  
Sent By pvalenti Date 2020-08-29 Time 12:16 Rev Time 0.00
Received By pvalenti Date 2020-08-29 Time 12:16 Sent To  
Notes
2020-08-29 12:29:28PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107, FS 471, FAC 6G15-23.002, SEAL, SIGNATURE AND
 DATE SHALL BE AFFIXED.
 THE PAPER COPIES THAT HAVE BEEN SUBMITTED DO NOT HAVE
 THE ENGINEER'S ORIGINAL PHYSICAL OR VERIFIED DIGITAL
 SIGNATURE. CONSIDERING THE FBPE TEMPORARY EXPANSION OF
 SIGNING SEALING RULES; THESE DOCUMENTS WOULD HAVE BEEN
 ACCEPTABLE IF THEY WERE COPIES FROM DIGITAL PLANS THAT
 HAD VERIFIED SIGNATURES. THE DOCUMENTS SUBMITTED TO
 PROJECT DOX ARE NOT VERIFIABLE.
  
 PLEASE PROVIDE ENGINEER'S SIGNATURES/SEALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 15:31 Sent To  
Notes
2020-07-24 15:32:53SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER OR ARCHITECT DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM. (AT THIS TIME DROP
 BOX ITEMS MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO
 PLAN REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-13 Cont ID  
Sent By rmcphers Date 2020-07-13 Time 15:27 Rev Time 0.00
Received By rmcphers Date 2020-07-13 Time 15:27 Sent To  
Notes
2020-07-13 15:29:35SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS - DUE TO LIMITED STAFF
 INSIDE THE BUILDING DEPT.)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-19 Cont ID  
Sent By rmcphers Date 2020-06-19 Time 15:18 Rev Time 0.00
Received By rmcphers Date 2020-06-19 Time 15:18 Sent To  
Notes
2020-06-19 15:19:16SEE BUILDING PLAN REVIEW