Plan Review Details - Permit 20060789
Plan Review Stops For Permit 20060789
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-21 Cont ID  
Sent By shill Date 2020-08-21 Time 09:57 Rev Time 0.00
Received By shill Date 2020-08-21 Time 09:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 15:06 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 11:49 Sent To  
Notes
2020-07-20 15:07:57PLAN REVIEW - BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW LOCATION OF PROPOSED GENERATOR ON SURVEY/SITE
 PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-24 Cont ID  
Sent By cthroop Date 2020-08-24 Time 10:26 Rev Time 0.00
Received By cthroop Date 2020-08-24 Time 10:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 15:36 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 11:49 Sent To  
Notes
2020-07-20 15:51:12PLAN REVIEW ? GENERATOR - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE SPECIFICATIONS FOR AUTOMATIC TRANSFER
 SWITCH. ? ATS
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) ELCTRICAL RISER DIAGRAHM. NEC 215.5; WPB FBC 107.2.1
 2A) INCLUDE MAIN DISCONNECT AND ANY SUB PANELS.
 2B) RISER SHOWS ONLY ONE #14 CONTROL WIRE. IS THIS
 CORRECT?
 2C) SHOW GROUNDING ELECTROCDE AT SERVICE.
  
 3) LOAD CALCULATIONS. IDENTIFY PANEL EACH LOAD CALC.
 REPRESENTS.
 PROVIDE LOAD CALCULATION FOR SERVICE,OR SERVICES,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-17 Cont ID  
Sent By lcrespo Date 2020-08-17 Time 08:48 Rev Time 0.00
Received By lcrespo Date 2020-08-17 Time 08:48 Sent To  
Notes
2020-08-17 08:49:2808/17/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-11 Cont ID  
Sent By lcrespo Date 2020-08-11 Time 16:08 Rev Time 0.00
Received By lcrespo Date 2020-08-11 Time 15:30 Sent To  
Notes
2020-08-11 16:56:2108/11/20 2ND GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. YOU CANNOT
 SUBMIT AN OLD DRAWING OF A PAST PERMIT REVIEW DOCUMENT
 WITH A STAMPED OF AN OLD PERMIT ON AND REDLINE IT.
 PLEASE REDRAW WITH CLARITY AND ANSWER COMMENT AS BEST
 AS YOU CAN, YOU CAN USE ALL THE INFORMATION ON THE OLD
 PERMIT REVIEW. THERE IS A DRAWING UPLOADED BUT SOME OF
 THESE COMMENTS YOU MAY HAVE DONE ALREADY ON IT.
  
 A. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 C. CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF THE
 PIPE OF THE NEW SYSTEM PER THE 2017 FBC RES. SECS.
 G2413.4.1, G2413.4.2.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2.
  
 E. LIST THE BTU LOAD OF EACH APPLIANCE OF THE OLD AND
 ADD THE TOTAL BTU LOADS ON THE NEW SYSTEM WITH A TOTAL
 PER THE 2017 FBC RES. SEC. G2413.
  
 F. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
  
 G. PLACE A NOTE ON PLANS LISTING THE SIZING TABLES FROM
 GAS CODES OR ANOTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS SYSTEM PER THE 2017 FBC RES. SEC.
 G2413.3.
  
 H. PLEASE SHOW AND LABEL UNIONS IN FRONT OF REGULATOR
 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2.
  
 I. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 J. SHOW DRIP LEG AND LABEL ON EQUIPMENT INSTALLED PER
 THE 2017 FBC RES. SEC. G2419.2.
  
 K. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES PER THE 2017 FBC RES. SEC. G2413.4.1,
 G2413.4.2 & G2413.4.3.
  
 L. PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR PER THE 2017 FBC RES. SEC.
 G2421.1.
  
 M. PROVIDE THE BTU'S LOAD OF THE GENERATOR NOT KW PER
 THE 2017 FBC RES. SEC. G2413.2.
  
 N. ON THE EXISTING GAS SHOW THE SIZE TO THE MAIN BRANCH
 AND PUT NOT ON IT SAYING EXISTING GAS AND TO A TOTAL OF
 ALL FIXTURE. YOU DON'T NEED TO SHOW PIPES, FITTING AND
 OTHER APERTURES, JUST MAKE SURE THE SCHEDULE IS NOTED
 ON A LIST AS ASKED ON ITEM E.
  
 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR GAS EQUIPMENT FROM
 GENERAC, THERE IS A VERSION IN 2020 AS THE NEW SPEC
 CALL OUT THE GENERATOR AT 309 BTU'S TO VERIFY
 COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE FBC RES. SEC. G2421.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 15:08 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 11:49 Sent To  
Notes
2020-07-20 15:30:20PLAN REVIEW ? GENERATOR - ? FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 OUR RECORDS INDICATE AN EXISTING FUEL GAS SYSTEM
 INSTALLED AT THIS RESIDENCE.
  
 1) GAS ISOMETRIC DRAWING:
 1A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 ALL EXISTING APPLIANCES MAY BE REPRESENTED ON THE GAS
 RISER AS EXISTING LOAD.
 1B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND BRANCH
 LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 &
 G2413.4.3. PROVIDED
 1B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE
 OUTLET OF THE REGULATOR- SECTION G2421.1
 1C) PROVIDE THE BTUH LOAD OF THE GENERATOR. G2413.2 FBC
 RES.
  
 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH
 MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET
 AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION
 G2421.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-15 Cont ID  
Sent By shill Date 2020-09-15 Time 14:45 Rev Time 0.00
Received By shill Date 2020-08-28 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-24 Cont ID  
Sent By cthroop Date 2020-08-24 Time 10:27 Rev Time 0.00
Received By cthroop Date 2020-08-10 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-08 Cont ID  
Sent By lmarchan Date 2020-08-08 Time 06:47 Rev Time 0.00
Received By lmarchan Date 2020-07-02 Time 14:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-08-17 Cont ID  
Sent By lcrespo Date 2020-08-17 Time 08:49 Rev Time 0.00
Received By lcrespo Date 2020-08-17 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-08-11 Cont ID  
Sent By lcrespo Date 2020-08-11 Time 16:08 Rev Time 0.00
Received By lcrespo Date 2020-08-11 Time 15:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 15:51 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 11:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-24 Cont ID  
Sent By cthroop Date 2020-08-24 Time 10:27 Rev Time 0.00
Received By cthroop Date 2020-08-24 Time 10:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-20 Cont ID  
Sent By cthroop Date 2020-07-20 Time 15:30 Rev Time 0.00
Received By cthroop Date 2020-07-20 Time 11:50 Sent To  
Notes
2020-07-20 15:31:30PLAN REVIEW ? GENERATOR - DIGITAL SIGNATURES AND SEALS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GENERATOR PAD DESIGN WIND LOADS
  
 1) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DRAWINGS. FS 471 & FAC 61G15
  
 2) DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH
 FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE
 NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 3) UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.
  
  
 4) FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGATURES AND SEALS PER FS 668.003.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-15 Cont ID  
Sent By rthermid Date 2020-09-15 Time   Rev Time 0.00
Received By rthermid Date 2020-09-15 Time   Sent To I
Notes
2020-09-15 09:58:49GENERATOR IS A MINIMUM OF 4 FEET FROM THE SIDE PROPERTY
 LINE

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-14 Cont ID  
Sent By rthermid Date 2020-08-14 Time   Rev Time 0.00
Received By rthermid Date 2020-08-14 Time   Sent To I
Notes
2020-08-14 08:45:58ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/14/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By rthermid Date 2020-08-05 Time   Rev Time  
Received By rthermid Date 2020-08-05 Time   Sent To I
Notes
2020-08-05 11:51:36ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 8/5/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A MARKED SURVEY OF THE PROPERTY WITH
 THE LOCATION OF THE PROPOSED GENERATOR INDICATING THE
 SETBACKS TO ALL PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved