Plan Review Details - Permit 20060751
Plan Review Stops For Permit 20060751
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By pvalenti Date 2020-07-13 Time 08:59 Rev Time 0.00
Received By pvalenti Date 2020-07-13 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-26 Cont ID  
Sent By pvalenti Date 2020-06-26 Time 14:14 Rev Time 0.00
Received By pvalenti Date 2020-06-26 Time 14:01 Sent To  
Notes
2020-06-26 14:18:28PETER E VALENTI
 BUILDING PLANS EXAMINER II
 561 805 6673
 [email protected]
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, SUBMIT TWO COPIES OF AN INSTALLATION
 SCHEDULE AND KEY PLAN FOR THE STORM PANELS. SPECIFY THE
 OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR,
 ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL
 SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE
 APPLICABLE SECTION NUMBER FROM THE INSTALLATION
 DRAWINGS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-26 Cont ID  
Sent By pvalenti Date 2020-06-26 Time 14:18 Rev Time 0.00
Received By pvalenti Date 2020-06-25 Time 15:54 Sent To  
Notes
2020-06-25 15:54:58ROUTED TO BLDG<$5K