| Plan Review Stops For Permit 20060751 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-07-13 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-07-13 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-06-26 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-06-26 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2020-06-26 14:18:28 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | 561 805 6673 | | | [email protected] | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107, SUBMIT TWO COPIES OF AN INSTALLATION | | | SCHEDULE AND KEY PLAN FOR THE STORM PANELS. SPECIFY THE | | | OPENING SIZE, THE WIND PRESSURES, TYPE OF ANCHOR, | | | ANCHOR SPACING, EDGE DISTANCE, PANEL LENGTH, PANEL | | | SPAN, SEPARATION DISTANCE FROM PANEL TO GLASS AND THE | | | APPLICABLE SECTION NUMBER FROM THE INSTALLATION | | | DRAWINGS. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-26 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-06-26 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-06-25 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2020-06-25 15:54:58 | ROUTED TO BLDG<$5K |
|
|
|