| 2020-06-24 15:21:25 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20060739 |
| | ADD: 701 S. OLIVE AVE. SUITE # 1501 |
| | CONT: FLORIDA STATE RESTORATION SERVICES |
| | TEL: 954-426-9494 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 24TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE 3 ARCHITECTURAL SHEETS APPEAR TO BE PAPER PLANS |
| | THAT WERE SCANNED AND UPLOADED TO BEING ELECTRONIC |
| | VERSIONS. THE ARCHITECT MARINA N. LLORENE DOES NOT |
| | APPEAR TO HAVE SIGNED THE PLANS DIGITALLY. |
| | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 |
| | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR |
| | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING |
| | PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER |
| | DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY |
| | THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE |
| | CHARGE. |
| | (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT |
| | BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE. |
| | (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS |
| | CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE |
| | DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER |
| | AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES |
| | THE MANUAL SEALING PROCEDURE SET OUT IN RULE |
| | 61G1-16.003, F.A.C. |
| | (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A |
| | DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL |
| | ASSURE THAT THE DIGITAL SIGNATURE IS: |
| | (A) UNIQUE TO THE PERSON USING IT; |
| | (B) CAPABLE OF VERIFICATION; |
| | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND |
| | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE |
| | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE |
| | DOCUMENT ARE CHANGED. |
| | (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN |
| | AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST |
| | DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD |
| | PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012, |
| | WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE |
| | BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE |
| | S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE |
| | INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP |
| | S/FIPS180-4/FIPS-180-4.PDF. |
| | |
| | 2) IN THE SUPPORTING DOCUMENT FILE THERE WAS A DATA |
| | SHEET FOR PROFLEX 90 MSC, NO TEST REPORTS. FOR TILE, |
| | STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| | HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| | THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS SHOWING |
| | COMPLIANCE WITH: |
| | |
| | TYPE I AND II BUILDINGS |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2D) THE CITY HAS A FILE IN OUR COMPUTER FOR FLOOR |
| | UNDERLAYMENT?S. WE HAVE NO INFORMATION ON PROFLEX 90 |
| | MSC. WE DO HAVE THE TEST REPORTS (ALL 3) FOR PROFLEX |
| | SUPERSIM 90 APPLIED TO A 6 INCH CONCRETE SLAB FOR |
| | MARBLE & TILE. |
| | ASTM E-90 STC 52 DB |
| | ASTM E-492 IIC 50 DB |
| | FLAME SPREAD ASTM E 84 |
| | IF THIS PRODUCT IS WHAT YOU WOULD LIKE TO USE NOTE SO |
| | ON THE PLANS, NO TEST REPORTS ARE REQUIRED. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |