Plan Review Details - Permit 20060735
Plan Review Stops For Permit 20060735
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 13:04 Rev Time 0.00
Received By rmcdouga Date 2021-05-03 Time 13:04 Sent To  
Notes
2021-05-03 11:55:29PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS HAVE NOT BEEN REVIEWED AND
 APPROVED IN WRITING BY THE ENGINEER OF RECORD. SHOP
 DRAWING REVIEW STAMP REQUIRED. FBC 107.3.4 - PROVIDE
 TWO SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH
 ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE
 PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING
 INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES
 FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW
 (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR
 TYPES. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 2) SUBMIT PRODUCT APPROVALS FOR THE CASEMENT WINDOW AND
 THE EXTERIOR DOORS. (IF IMPACT RATED WINDOWS ARE NOT
 USED, SUBMIT PRODUCT APPROVALS, A KEY PLAN AND
 INSTALLATION FOR THE IMPACT PROTECTION DEVICES.) FAC
 61G20
  
 3) HI-LIGHT OR CIRCLE THE SPECIFIC TYPE, SIZE, DESIGN
 PRESSURES, ETC. FOR THE SPECIFIC ITEMS IN THE PRODUCT
 APPROVAL THAT WILL BE INSTALLED.
  
 5) THE CORRECTED ENERGY FORMS ARE NOT SIGNED AND DATED
 BY THE PREPARER AND OWNER. THE ENERGY FORMS ARE
 REQUIRED TO BE SIGNED BY THE PREPARER AND THE
 OWNER/AGENT. FBC ENERGY CONSERVATION SECTION 405.4
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. THIS HELP TO SHORTEN THE REVIEW TIME.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-10-07 Cont ID  
Sent By rmcdouga Date 2020-10-07 Time 17:06 Rev Time 0.00
Received By rmcdouga Date 2020-10-07 Time 15:03 Sent To  
Notes
2020-10-07 16:57:28PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. ONLY ONE SET IS
 REQUIRED TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED
 DOCUMENTS.
  
 2) THE INFORMATION SUBMITTED FOR THE SINGLE HUNG
 WINDOWS DOES NOT HAVE AN FL# AND DOES NOT APPEAR TO BE
 THE PRODUCT APPROVAL. SUBMIT THE COMPLETE PRODUCT
 APPROVAL WITH THE FL COVERSHEET. FBC 107.3.4
  
 3) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS
 HAVE A DESIGN PRESSURE OF + OR - 50 PSF. THIS IS NOT
 ADEQUATE FOR WINDOWS C & D IN THE CONVERTED GARAGE OR
 WINDOW L IN THE TWO STORY HOUSE. THEY HAVE PRESSURES
 THAT EXCEED -50 PSF.
  
 4) SUBMIT THE PRODUCT APPROVALS FOR THE DOORS AND THE
 STRUCTURAL MULLIONS. FBC 107.3.4
  
 5) THE DOCUMENTS SUBMITTED FOR THE SINGLE HUNG WINDOWS
 ARE FOR NON-IMPACT RATED WINDOWS. IMPACT PROTECTION IS
 REQUIRED FOR THE GLAZED OPENINGS PER FBC-R301.2.1.2
 PROTECTION OF OPENINGS. SUBMIT A KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVALS FOR THE STORM PANELS.
 FBC 107
  
 6) THE ENERGY FORMS ARE REQUIRED TO BE SIGNED BY THE
 PREPARER AND THE OWNER/AGENT. FBC ENERGY CONSERVATION
 SECTION 405.4
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
  
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. THIS HELP TO SHORTEN THE REVIEW TIME.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By jbrooks Date 2020-07-30 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-07-30 Time 07:37 Sent To  
Notes
2020-07-30 13:44:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BASED ON MY RESEARCH THE BUILDING IN THE REAR WAS
 ORIGINALLY PERMITTED AS A DETACHED GARAGE. THE WORK THE
 IS BEING PROPOSED IS TO CONVERT THE GARAGE TO HABITABLE
 SPACE. ACCORDING TO THE FBC EXISTING BUILDING SECTION
 1001.2.1 & 901, THIS IS A CHANGE OF USE WITHIN THE SAME
 OCCUPANCY CLASSIFICATION AND A LEVEL 3 ALTERATION.
 PLEASE REVISE NOTE THREE ON SHEET A1 FROM LEVEL 2
 ALTERATION.
  
 2) AN IMPACT FEE REVIEW IS REQUIRED TO DETERMINE IF
 ADDITIONAL IMPACT FEES ARE DUE, WHEN CONVERTING STORAGE
 SPACE TO HABITABLE SPACE. SEE THE IMPACT FEE REVIEW
 STOP FOR DETAILS.
  
 3) THIS IS AN ENCLOSED STRUCTURE. PLEASE REVISE NOTE
 UNDER DESIGN CRITERIA ON SHEET A1.
  
 4) IN THE DESIGN CRITERIA ON SHEET A3 FOR THE MAIN
 HOUSE LIST THE ROOF HEIGHT AS 10 FEET AND IT IS TWO
 STORIES. PLEASE CORRECT. FBC 107
  
 5) ON SHEET A2 THERE ARE SOME INCONSISTENCIES. THE
 TYPICAL WALL SECTION SHOWS A FLAT SINGLE ASSEMBLY ROOF
 SYSTEM WITH NO EAVE VENTS. THE ENERGY CALCULATIONS HAS
 A VENTED ATTIC SPACE AND A CATHEDRAL CEILING. PLEASE
 CLARIFY AND MAKE CORRECTIONS. FBC 107
  
 6) ON SHEET A2 THE MECHANICAL DETAILS SHOW THE BATH
 EXHAUST ROUTED THROUGH THE ATTIC TO THE EAVE AND THERE
 MAY NOT BE THE SPACE TO DO THIS WITHOUT INTERFERING
 WITH THE REQUIRED INSULATION IN A SINGLE ASSEMBLY ROOF
 SYSTEM. PLEASE CLARIFY. FBC ENERGY CONSERVATION
  
 7) SPECIFY THE SIZE OF THE RAFTER/CEILING JOISTS IN THE
 EXISTING SINGLE ASSEMBLY ROOF SYSTEM. R806.3 VENT AND
 INSULATION CLEARANCE. WHERE EAVE OR CORNICE VENTS ARE
 INSTALLED, INSULATION SHALL NOT BLOCK THE FREE FLOW OF
 AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
  
 8) SPECIFY THE ROOF TO WALL CONNECTIONS. FBC-R301.1
  
 9) PROVIDE EXTERIOR ELEVATIONS OF THE BUILDING AND
 SPECIFY THE ROOF SLOPE. FBC 107.2.1
  
 10) SPECIFY THE REQUIRED WIND LOAD DESIGN PRESSURES FOR
 ALL EXTERIOR OPENINGS. FBC 107.3.5.3 - PROVIDE WIND
 DESIGN LOADS AND COMPONENT AND CLADDING DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 11) THE VALUATION THAT WAS APPLIED TO THIS PROJECT OF
 $6865.00 IS TOO LOW. THE IMPACT WINDOWS ALONE FOR BOTH
 THESE BUILDINGS IS MUCH MORE THAN THAT. PLEASE PROVIDE
 AN ACCURATE VALUATION. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 12) PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE
 PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND
 OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION
 FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO
 FBC 110 & FBC 117.
  
 FBC 110.1 GENERAL - CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 13) WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. THIS HELP TO SHORTEN THE REVIEW TIME.
  
  
  
  
  
2020-07-21 10:16:36JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT
 APPROVALS, PROVIDE THE FOLLOWING ADDITIONAL
 INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS
 WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER,
 STATUS, GENERAL INFORMATION ABOUT THE PRODUCT). PROVIDE
 TWO COMPLETE SETS FOR THE PROPOSED WINDOWS USED
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-10-20 Cont ID  
Sent By jleahy Date 2020-10-20 Time 08:44 Rev Time 0.00
Received By jleahy Date 2020-10-07 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By jleahy Date 2020-07-30 Time 10:49 Rev Time 0.00
Received By jleahy Date 2020-07-30 Time 08:43 Sent To  
Notes
2020-07-30 10:50:43NEED ZONING APPROVAL FOR SECOND METER AND SERVICE
 JLEAHY

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2021-04-22 Cont ID  
Sent By aborngra Date 2021-04-22 Time 08:49 Rev Time 0.00
Received By aborngra Date 2021-04-22 Time 08:48 Sent To  
Notes
2021-04-22 08:49:11THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. WINDOWS S AND R SHALL HAVE A VERTICAL 3/3 LITE
 PATTERN. (3A1D)
 2. WINDOW U CONSISTING OF TWO WINDOWS WITH A 1-INCH
 MULLION SHALL HAVE A VERTICAL 2/2 LITE PATTERN. (2A1D)
 3. ALL LITE PATTERNS SHALL BE VERTICALLY ORIENTED.
 4. ALL WINDOWS PREVIOUSLY REPLACED WITHOUT A PERMIT
 SHALL HAVE A LITE PATTERN ADDED TO EACH WINDOW. THE
 MUNTIN PROFILE SHALL HAVE AN EXTERNAL DIMENSIONAL
 PYRAMID PROFILE.
 4A. EACH WINDOW E SHALL HAVE A 6/6 LITE PATTERN (2A3D)
 4B. WINDOW G SHALL HAVE A VERTICAL 4/4 LITE PATTERN.
 (4A1D)
 4C. WINDOW H SHALL HAVE A VERTICAL 3/3 LITE PATTERN.
 (3A1D)
 4D. EACH WINDOW I SHALL HAVE A VERTICAL 3/3 LITE
 PATTERN. (3A1D)
 4E. ALL REMAINING WINDOWS NOT SPECIFICALLY OUTLINED IN
 THESE CONDITIONS SHALL HAVE A LITE PATTERN OF VERTICAL
 4/4 OR VERTICAL 3/3 BASED ON THE ORIGINAL WINDOWS THAT
 WERE REMOVED WITHOUT A PERMIT.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2020-10-08 Cont ID  
Sent By aborngra Date 2020-10-08 Time 14:39 Rev Time 0.00
Received By aborngra Date 2020-10-08 Time 14:39 Sent To  
Notes
2020-10-08 14:39:45THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PROVIDE EXISTING ELEVATIONS AND/OR PHOTOS OF THE
 REAR STRUCTURE TO BE CONVERTED.
 2. REVISE ACCESSORY STRUCTURE NORTH ELEVATION BATHROOM
 WINDOW TO HAVE SQUARE PROPORTIONS WITH A CASEMENT
 (HOPPER) WINDOW.
 3. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS EXTERIOR FRAME, GLASS GLAZING,
 LITE PATTERN, MUNTIN PROFILE AND MULLION WIDTH. A PHOTO
 OF EACH ELEVATION WITH EACH WINDOW MARKED.
 4. OPENING J IS A SLIDING GLASS DOOR. PROVIDE REASON
 WHY ITS GOING TO BE A PAIRED SINGLE-HUNG WINDOW.
 PROVIDE A PHOTO OF THIS OPENING.
 5. THE WINDOWS ON THE MAIN HOUSE WILL NEED TO BE
 MODIFIED TO RECREATE THE PREVIOUS ORIGINAL WINDOWS
 APPEARANCE. MUNTINS WITH AN EXTERNAL DIMENSIONAL
 PYRAMID PROFILE WILL BE REQUIRED TO BE ATTACHED THE
 GLASS.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By aborngra Date 2020-08-05 Time 14:38 Rev Time 0.00
Received By aborngra Date 2020-08-05 Time 14:38 Sent To  
Notes
2020-08-05 14:38:12THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PROVIDE EXISTING ELEVATIONS AND/OR PHOTOS OF THE
 REAR STRUCTURE TO BE CONVERTED.
 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS EXTERIOR FRAME, GLASS GLAZING,
 LITE PATTERN, MUNTIN PROFILE AND MULLION WIDTH. A PHOTO
 OF EACH ELEVATION WITH EACH WINDOW MARKED.
 3. OPENING J IS A SLIDING GLASS DOOR. PROVIDE REASON
 WHY ITS GOING TO BE A PAIRED SINGLE-HUNG WINDOW.
 4. STAFF IS UNDER THE IMPRESSION THE WINDOWS HAVE
 ALREADY BEEN INSTALLED. ARE NEW WINDOWS BEING INSTALLED
 OR IS THIS PERMIT TO BRING THE PREVIOUSLY INSTALLED
 WINDOWS INTO COMPLIANCE? PLEASE CLARIFY.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 13:04 Rev Time 0.00
Received By rmcdouga Date 2021-04-20 Time 10:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-20 Cont ID  
Sent By jleahy Date 2020-10-20 Time 08:45 Rev Time 0.00
Received By jleahy Date 2020-10-06 Time 16:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-10 Cont ID  
Sent By jbrooks Date 2020-08-10 Time 15:42 Rev Time 0.00
Received By cpuell Date 2020-06-18 Time 15:31 Sent To  
Notes
2020-06-18 15:31:22ROUTED TO BLDG. MISC 1

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By rmcdouga Date 2020-07-30 Time 12:58 Rev Time 0.00
Received By rmcdouga Date 2020-07-30 Time 12:58 Sent To  
Notes
2020-07-30 13:24:04BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By medwards Date 2020-10-07 Time 08:50 Rev Time 0.00
Received By medwards Date 2020-10-07 Time 07:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-07-30 Cont ID  
Sent By medwards Date 2020-07-30 Time 07:46 Rev Time 0.00
Received By medwards Date 2020-07-30 Time 07:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-10-07 Cont ID  
Sent By lcrespo Date 2020-10-07 Time 16:28 Rev Time 0.00
Received By lcrespo Date 2020-10-07 Time 16:28 Sent To  
Notes
2020-10-07 16:28:3610/07/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-07-30 Cont ID  
Sent By jesmith Date 2020-07-30 Time 11:06 Rev Time 0.00
Received By jesmith Date 2020-07-30 Time 08:18 Sent To  
Notes
2020-07-30 11:03:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060735 816 L A KIRKSEY ST
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. RE: PLAN SHEET MEP; PER WPB FBC 107.2.1, CLEARLY
 INDICATE ON THE PLAN VIEW AND THE SANITARY RISER
 DIAGRAM HOW THE AUTOMATIC CLOTHES WASHER IS CONNECTED
 TO THE SANITARY SYSTEM. INCLUDE VENT AND FIXTURE DRAIN
 WITH SIZING.
 2. WILL THE NEW SANITARY BUILDING DRAIN AND SEWER
 CONNECT TO THE EXISTING BUILDING SEWER OR SEPARATELY TO
 THE CITY SEWER. PER WPB FBC 107.2.1, CLARIFY, PROVIDE
 ROUTING AND DETAILS ON THE SITE PLAN. SHOW LOCATION(S)
 OF REQUIRED CLEANOUT (S) COMPLYING WITH FBC RES
 P3005.2.2, P3005.2.3 AND P3005.2.4.
 3. RE: PLAN SHEET MEP; THE ELECTRICAL PANEL INDICATES A
 12 KW TANKLESS WATER HEATER. THE ENERGY CALCULATION
 SHEET (PG 2) IN SUPPORTING DOCUMENTS INDICATE A 30
 GALLON ELECTRIC TANK (STORAGE) TYPE WATER HEATER. PER
 WPB FBC 107.2.1, CLARIFY. AMEND WHICHEVER OF THE TWO
 DOCUMENTS THAT IS INCORRECT. ADDITIONALLY, SHOW
 LOCATION OF THE WATER HEATER ON THE FLOOR PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE WATER HEATER. PROVIDE CALCULATIONS TO SHOW HOT
 WATER DEMAND WILL BE SUPPORTED BY THE WATER HEATER.
 ALSO NOTE THAT PLUMBING NOTE #7 REQUIRES A GALVANIZED
 DRIP PAN AND DRAIN UNDER THE WATER HEATER. THIS IS ONLY
 REQUIRED BY CODE FOR TANK (STORAGE) TYPE WATER HEATERS.
 4. RE: PLAN SHEET MEP; PER WPB FBC 107.2.1 AND FBC RES
 P2903.5, PLUMBING NOTE #5 SHALL BE AMENDED TO STATE
 "THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010".
 ADDITIONALLY, THE VERBAGE AND POSSIBLE LACK OF
 PUNCTUATION IN THE NOTE REFERENCING 604.9 WATER HAMMER
 ARRESTORS IS CONFUSING. PLEASE CLARIFY.
 5. RE: PLAN SHEET MEP; PER WPB FBC 107.2.1 AND FBC RES
 P3005.3, PLUMBING NOTE #11 SHALL BE AMENDED TO STATE
 "?HORIZONTAL DRAINAGE PIPING SHALL BE INSTALLED IN
 UNIFORM ALIGNMENT AT UNIFORM SLOPES NOT LESS THAN 1/4
 INCH PER FOOT (2-PERCENT SLOPE) FOR 21/2 INCH DIAMETER
 AND LESS, AND NOT LESS THAN 1/8 INCH PER FOOT
 (1-PERCENT SLOPE) FOR DIAMETERS OF 3 INCHES OR MORE".
 6. RE: PLAN SHEET MEP; PER WPB FBC 107.2.1, FBC PL
 606.3 AND FBC RES 2601.1, SHOW ACCESSIBLE LOCATION OF
 SHUT OFF VALES FOR THE STACKED WASHER/DRYER COMBO.
 7. VALUE OF JOB IS INCONSISTENTLY PROVIDED ON SEPARATE
 PERMITS AND DOES NOT REFLECT THE VALUE INDICATED ON THE
 SUPPORTING DOCUMENT "REQUEST FOR REDUCTION OF FINE".
 PROVIDE AN ACCURATE VALUATION OF ALL WORK AND COST.
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL (1)CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 PAGES WHICH ARE REPLACED ARE REQUIRED TO HAVE A DIGITAL
 SIGNATURE IN ACCORDANCE WITH FS471, FAC61G15-23, OR
 APPLICANT IS TO PROVIDE ONE PAPER ORIGINAL AFTER ALL
 REVIEWS HAVE PASSED.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-05-03 Cont ID  
Sent By rmcdouga Date 2021-05-03 Time 11:40 Rev Time 0.00
Received By rmcdouga Date 2021-05-03 Time 11:40 Sent To  
Notes
2021-05-03 11:40:51THE PLANS ARE NOT SIGNED DIGITALLY BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-12-01 Cont ID  
Sent By medwards Date 2020-12-01 Time 14:01 Rev Time 0.00
Received By medwards Date 2020-12-01 Time 14:01 Sent To  
Notes
2020-12-01 14:01:50PAPER PLANS ON FILE, SIGNATURE AND SEAL APPROVED. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-10-07 Cont ID  
Sent By rmcdouga Date 2020-10-07 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2020-10-07 Time 17:07 Sent To  
Notes
2020-10-07 17:09:34THE PLANS ARE NOT SIGNED DIGITALLY BY THE ENGINEER.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-29 Cont ID  
Sent By shill Date 2020-07-29 Time 08:41 Rev Time 0.00
Received By shill Date 2020-07-29 Time 08:41 Sent To  
Notes
2020-07-29 08:42:55SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PAPER PLANS SUBMITTED, PREPARED BY CARL G FORBES, PE
 DATED 5/19/20.
  
 PROVISO: PAGES WHICH ARE REPLACED ARE REQUIRED TO HAVE
 A DIGITAL SIGNATURE IN ACCORDANCE WITH FS471,
 FAC61G15-23, OR APPLICANT IS TO PROVIDE ONE PAPER
 ORIGINAL AFTER ALL REVIEWS HAVE PASSED.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-22 Cont ID  
Sent By aborngra Date 2021-04-22 Time 08:49 Rev Time 0.00
Received By aborngra Date 2021-04-21 Time 11:53 Sent To  
Notes
2021-04-22 08:49:31THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. WINDOWS S AND R SHALL HAVE A VERTICAL 3/3 LITE
 PATTERN. (3A1D)
 2. WINDOW U CONSISTING OF TWO WINDOWS WITH A 1-INCH
 MULLION SHALL HAVE A VERTICAL 2/2 LITE PATTERN. (2A1D)
 3. ALL LITE PATTERNS SHALL BE VERTICALLY ORIENTED.
 4. ALL WINDOWS PREVIOUSLY REPLACED WITHOUT A PERMIT
 SHALL HAVE A LITE PATTERN ADDED TO EACH WINDOW. THE
 MUNTIN PROFILE SHALL HAVE AN EXTERNAL DIMENSIONAL
 PYRAMID PROFILE.
 4A. EACH WINDOW E SHALL HAVE A 6/6 LITE PATTERN (2A3D)
 4B. WINDOW G SHALL HAVE A VERTICAL 4/4 LITE PATTERN.
 (4A1D)
 4C. WINDOW H SHALL HAVE A VERTICAL 3/3 LITE PATTERN.
 (3A1D)
 4D. EACH WINDOW I SHALL HAVE A VERTICAL 3/3 LITE
 PATTERN. (3A1D)
 4E. ALL REMAINING WINDOWS NOT SPECIFICALLY OUTLINED IN
 THESE CONDITIONS SHALL HAVE A LITE PATTERN OF VERTICAL
 4/4 OR VERTICAL 3/3 BASED ON THE ORIGINAL WINDOWS THAT
 WERE REMOVED WITHOUT A PERMIT.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-10-08 Cont ID  
Sent By aborngra Date 2020-10-08 Time 14:42 Rev Time 0.00
Received By aborngra Date 2020-10-08 Time 14:39 Sent To  
Notes
2020-10-20 08:45:43AARON
  
 THEY HAVE ALSO PLACED A SEPARATE METER ON THIS
 STRUCTURE, NOT SURE IF IT OK PER ZONING. JAKE
2020-10-08 14:42:18THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PROVIDE EXISTING ELEVATIONS AND/OR PHOTOS OF THE
 REAR STRUCTURE TO BE CONVERTED.
 2. REVISE ACCESSORY STRUCTURE NORTH ELEVATION BATHROOM
 WINDOW TO HAVE SQUARE PROPORTIONS WITH A CASEMENT
 (HOPPER) WINDOW.
 3. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS EXTERIOR FRAME, GLASS GLAZING,
 LITE PATTERN, MUNTIN PROFILE AND MULLION WIDTH. A PHOTO
 OF EACH ELEVATION WITH EACH WINDOW MARKED.
 4. OPENING J IS A SLIDING GLASS DOOR. PROVIDE REASON
 WHY ITS GOING TO BE A PAIRED SINGLE-HUNG WINDOW.
 PROVIDE A PHOTO OF THIS OPENING.
 5. THE WINDOWS ON THE MAIN HOUSE WILL NEED TO BE
 MODIFIED TO RECREATE THE PREVIOUS ORIGINAL WINDOWS
 APPEARANCE. MUNTINS WITH AN EXTERNAL DIMENSIONAL
 PYRAMID PROFILE WILL BE REQUIRED TO BE ATTACHED THE
 GLASS.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  
 THIS PROPERTY IS ZONED CP-POR-C2, WHICH ALLOWS 14
 DWELLING UNITS PER ACRE. THE PROEPRTY IS .15 ACRES,
 ALLOWING 2.1 OR 2 (TWO) UNITS.
2020-10-07 08:42:08NOTE TO ZONING THIS STRUCTURE IS PROPOSING TO ADD
 ANOTHER METER TO THE PROPERTY FOR JUST THE GUEST HOUSE.
 THEY WILL END UP WITH ONE ON THE MAIN HOUSE AND ONE ON
 THE GUEST HOUSE

Review Stop Z ZONING
Rev No 1 Status F Date 2020-08-05 Cont ID  
Sent By aborngra Date 2020-08-05 Time 14:37 Rev Time 0.00
Received By aborngra Date 2020-08-05 Time 14:37 Sent To  
Notes
2020-08-05 14:37:55THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 1. PROVIDE EXISTING ELEVATIONS AND/OR PHOTOS OF THE
 REAR STRUCTURE TO BE CONVERTED.
 2. ALL WINDOW REPLACEMENT WORK REQUIRES TO FOLLOW THE
 WINDOW PERMIT APPLICATION EXAMPLE. PLEASE EMAIL STAFF
 AT [email protected] TO REQUEST THE EXAMPLE. AT
 MINIMUM, STAFF NEEDS TO KNOW THE EXISTING WINDOWS AND
 THE PROPOSED WINDOWS EXTERIOR FRAME, GLASS GLAZING,
 LITE PATTERN, MUNTIN PROFILE AND MULLION WIDTH. A PHOTO
 OF EACH ELEVATION WITH EACH WINDOW MARKED.
 3. OPENING J IS A SLIDING GLASS DOOR. PROVIDE REASON
 WHY ITS GOING TO BE A PAIRED SINGLE-HUNG WINDOW.
 4. STAFF IS UNDER THE IMPRESSION THE WINDOWS HAVE
 ALREADY BEEN INSTALLED. ARE NEW WINDOWS BEING INSTALLED
 OR IS THIS PERMIT TO BRING THE PREVIOUSLY INSTALLED
 WINDOWS INTO COMPLIANCE? PLEASE CLARIFY.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved