Plan Review Details - Permit 20060729
Plan Review Stops For Permit 20060729
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-09-17 Cont ID  
Sent By rmcphers Date 2020-09-17 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2020-09-17 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-08-27 Time 15:31 Sent To  
Notes
2020-08-27 15:32:10PATIO ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
 2ND REVIEW
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 08:09 Sent To  
Notes
2020-07-10 08:29:09PATIO ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-18 Cont ID  
Sent By jleahy Date 2020-09-18 Time 17:16 Rev Time 0.00
Received By jleahy Date 2020-09-18 Time 17:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-21 Cont ID  
Sent By jleahy Date 2020-07-21 Time 10:15 Rev Time 0.00
Received By jleahy Date 2020-07-21 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-18 Cont ID  
Sent By jleahy Date 2020-09-18 Time 17:28 Rev Time 0.00
Received By jleahy Date 2020-09-09 Time 16:05 Sent To  
Notes
2020-09-16 16:07:34UPLOADED REVISED DRAWING A2, ROOF TILE NOA AND ROOF
 UNDERLAYMENT NOA TO PROJECTDOX. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 15:42 Rev Time 0.00
Received By rmcphers Date 2020-08-18 Time 17:18 Sent To  
Notes
2020-08-18 17:19:39HARD COPY DRAWINGS A1 AND A2 WITH ARCHITECT'S ORIGINAL
 SEAL/SIGNATURE MATCH DRAWINGS UPLOADED TO PROJECTDOX.
 OWNER SUBMITTED ROOF COVERING NOA.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-21 Cont ID  
Sent By rmcphers Date 2020-07-21 Time 10:15 Rev Time 0.00
Received By jleahy Date 2020-06-22 Time 14:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2020-09-17 Cont ID  
Sent By rmcphers Date 2020-09-17 Time 08:58 Rev Time 0.00
Received By rmcphers Date 2020-09-17 Time 08:58 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-08-27 Cont ID  
Sent By rmcphers Date 2020-08-27 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2020-08-27 Time 15:32 Sent To  
Notes
2020-08-27 15:40:22ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL PROVIDED IS FOR TILE - THE DRAWINGS
 SHOW SHINGLES TO BE INSTALLED - PLEASE REVISE THE
 DRAWINGS TO SHOW TILE.
 2) TILE PRODUCT APPROVAL PROVIDED = PLEASE CIRCLE ON
 THE PRODUCT APPROVAL HOW THE TILE IS TO BE ATTACHED. IF
 USING AN ADHESIVE PLEASE PROVIDE THE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL FOR THE ADHESIVE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 08:21 Sent To  
Notes
2020-07-10 08:24:27ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING TO BE INSTALLED.
 (SHINGLES, TILE, ETC)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-16 Cont ID  
Sent By jgomez Date 2020-09-16 Time 16:07 Rev Time 0.00
Received By jgomez Date 2020-09-16 Time 16:07 Sent To  
Notes
2020-09-16 16:08:37REVISED DWG A2 HAS ARCHITECT'S EMBOSSED SEAL AND
 SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-18 Cont ID  
Sent By jgomez Date 2020-08-18 Time 17:12 Rev Time 0.00
Received By jgomez Date 2020-08-18 Time 17:12 Sent To  
Notes
2020-08-18 17:14:4508/18/2020 HARD COPY DRAWINGS A1 AND A2 WITH
 ARCHITECT'S ORIGINAL SEAL/SIGNATURE MATCH DRAWINGS
 UPLOADED TO PROJECTDOX.
 DRAWINGS SENT TO STORAGE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By rmcphers Date 2020-07-10 Time 08:25 Rev Time 0.00
Received By rmcphers Date 2020-07-10 Time 08:25 Sent To  
Notes
2020-07-10 08:27:41SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-06-29 Cont ID  
Sent By rthermid Date 2020-06-29 Time   Rev Time  
Received By rthermid Date 2020-06-29 Time   Sent To I
Notes
***NONE***