Plan Review Details - Permit 20060710
Plan Review Stops For Permit 20060710
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 16:50 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 16:35 Sent To  
Notes
2020-07-28 16:51:2007/28/20 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 AM / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-07-15 Cont ID  
Sent By jesmith Date 2020-07-15 Time 14:52 Rev Time 0.00
Received By jesmith Date 2020-07-15 Time 11:49 Sent To  
Notes
2020-07-15 14:50:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20060710 6300 GARDEN AVE
  
 2ND REVIEW
  
 GAS COMMENTS:
  
 1. SECOND REQUEST: PLEASE SHOW WHERE THIS BBQ IS
 LOCATED AND SHOW WALLS AND CEILING DETAIL. FBC 107.2.1.
 TO BE CLEAR, A HOUSE PLAN SHOWING THE LOCATION OF THE
 APPLIANCES INCLUSIVE OF THOSE OUTDOORS WITH THE
 LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS
 IN RELATION TO THE APPLIANCES IS REQUIRED. THE LOCATION
 OF THE APPLIANCES SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. PLEASE NOTE THAT
 OPEN PERMIT 20031407 FOR POOL INDICATES THAT THE POOL
 EQUIPMENT WHICH WOULD INCLUDE THE POOL HEATER IS
 LOCATED ON A WALL NEAR TWO (2) WINDOWS (SEE CLOSED
 PERMIT 16010471).
 2. SECOND REQUEST: SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES
 TO BE CLEAR, THIS SHALL INCLUDE GALVANIZED PIPING
 AND/OR CSST AT THE APPLIANCE. IF CSST IS USED, THE
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL
 BE SUBMITTED AND ALL MANUFACTURER?S RECOMMENDATION
 INCLUDING BUT NOT LIMITED TO PROTECTION OF EXPOSED
 PIPING SHALL BE ADHERED TO PER FBC FG 404.2.
 3. SECOND REQUEST: SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR THE BBQ GRILL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 NEW COMMENTS
 1. RE: ISOMETRIC (RISER DIAGRAM)
 A. TOTAL DEMAND HAS BEEN INCREASED BY 450 MBTU. PER WPB
 FBC 107.2.1, PROVIDE SIZING OF PIPING FROM METER TO
 CONNECTION OF NEW LINE. PIPING SHALL SUPPORT TOTAL 649
 MBTU AT LESS THAN 2PSI FOR A LONGEST LENGTH DISTANCE
 FOR THE SYSTEM WHICH IS 60 FEET AND SHALL BE SIZED PER
 TABLE 402.4(2). PLEASE NOTE THAT CLOSED PERMIT 16051054
 INDICATES THE EXISTING PIPING IS 1 INCH WHICH IS
 INADEQUATE.
 B. THE LONGEST LENGTH DISTANCE FOR THE SYSTEM, 90 FEET
 AS NOTED ON ISOMETRIC PIPING TO RANGE APPEARS TO BE
 INCORRECT. ACCORDING TO CLOSED PERMIT 16051054, THE
 ACTUAL DISTANCE FROM THE METER TO EXISTING RANGE IS 55
 FEET SO THE CORRECT LONGEST LENGTH OF 60 FEET IS
 APPLICABLE AS DESCRIBED IN SUBMITTED TABLE 402.4(21).
 THE PE BRANCH TO THE POOL HEATER IS UNDERSIZED AT 3/4
 INCH AND SHALL BE 1-1/4 INCH TO SUPPORT 400 MBTU.
 C. PER WPB FBC 107.2.1, INDICATE THE TRANSITION FITTING
 OR RISER COMPLYING WITH FBC FG 417.1 AND 417.2 FROM PE
 PIPING TO ABOVE GROUND SCHEDULE 40 GALVANIZED PIPING;
 INDICATE THE GALVANIZED PIPING.
 D. PER WPB FBC 107.2.1, PROVIDE NOTE SHOWING COMPLIANCE
 WITH FBC FG 417.3 STATING YELLOW INSULATED COPPER
 TRACER WIRE OR OTHER APPROVED CONDUCTOR SHALL BE
 INSTALLED ADJACENT TO UNDERGROUND NONMETALLIC PIPING.
 ACCESS SHALL BE PROVIDED TO THE TRACER WIRE OR THE
 TRACER WIRE SHALL TERMINATE ABOVE GROUND AT EACH END OF
 THE NONMETALLIC PIPING. THE TRACER WIRE SIZE SHALL BE
 NOT LESS THAN 18 AWG AND THE INSULATION TYPE SHALL BE
 SUITABLE FOR DIRECT BURIAL.
 E. PER WPB FBC 107.2.1, IDENTIFY SHUT OFF VALVES FOR
 APPLIANCES; A SEDIMENT TRAP IS REQUIRED COMPLYING WITH
 FBC FG 408.4.
 F. AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE GAS/PLUMBING
 PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR
 THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20060710 6300 GARDEN AVE
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2020-07-01 Time 16:32 Sent To  
Notes
2020-07-06 07:20:34GAS 1ST REVIEW COMMENTS:
 1) PERMIT APPLICATION ONLY LIST SCOPE OF WORK AS POOL
 HEATER. PLEASE REVISED AND ADJUST YOUR JOB VALUATION TO
 INCLUDE THE COST OF THE BBQ GRILL. FBC 109.3
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 4) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21
 5) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THE BBQ GRILL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 6) PLEASE PROVIDE WHERE THIS BBQ IS LOCATED AND SHOW
 WALLS AND CEILING DETAIL. FBC 107.2.1
 7) SUBMIT COPIES OF EACH APPLICABLE SIZING TABLES FOR
 EACH DIFFERENT MATERIAL BEING USED TO SIZE THE GAS
 SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING
 WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER
 STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4,
 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2,
 & G2413.3
 8) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 9) NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT
 THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 ( CAP GOVERNMENT )
 [email protected]
  
  
2020-07-01 16:32:59TIM HUNT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 16:51 Rev Time 0.00
Received By lcrespo Date 2020-07-17 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-15 Cont ID  
Sent By jesmith Date 2020-07-15 Time 14:54 Rev Time 0.00
Received By jesmith Date 2020-07-15 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By lmarchan Date 2020-07-06 Time 10:12 Rev Time 0.00
Received By lmarchan Date 2020-06-15 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 16:50 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-07-15 Cont ID  
Sent By jesmith Date 2020-07-15 Time 14:53 Rev Time 0.00
Received By jesmith Date 2020-07-15 Time 14:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2020-07-01 Time 16:32 Sent To  
Notes
2020-07-06 07:19:58 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2020-07-28 Cont ID  
Sent By lcrespo Date 2020-07-28 Time 16:51 Rev Time 0.00
Received By lcrespo Date 2020-07-28 Time 16:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-07-15 Cont ID  
Sent By jesmith Date 2020-07-15 Time 14:54 Rev Time 0.00
Received By jesmith Date 2020-07-15 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 07:22 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 07:22 Sent To  
Notes
***NONE***