| Plan Review Stops For Permit 20060544 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-14 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-08-14 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-24 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-24 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2020-06-24 15:41:53 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR EXHAUST IS TO BE LOCATED 10 FEET FROM | | | ANY OPENINGS INTO THE STRUCTURE OR PER THE | | | MANUFACTURER'S SPECIFICATIONS. FBC FUEL GAS 616.1 | | | | | | 2) THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | ELECTRONICALLY SUBMITTED GENERATOR PAD DRAWINGS. FS 471 | | | & FAC 61G15 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-06-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-25 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-25 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2020-07-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-25 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-25 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2020-06-25 13:15:05 | SEPERATE GAS PERMIT REQUIRED. CT | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-08-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-28 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-25 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-24 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-14 |
Time |
06:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-14 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-07-27 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-07-06 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-06-11 |
Time |
09:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-25 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-25 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-08-14 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-08-14 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-06-24 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-06-24 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2020-06-24 15:42:14 | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON THE | | | ELECTRONICALL SUBMITTED GENERATOR PAD DRAWINGS. FS 471 | | | & FAC 61G15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2020-08-27 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-08-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-08-27 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2020-08-21 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-08-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-08-21 |
Time |
15:45 |
Sent To |
I |
|
| Notes |
| 2020-08-21 12:10:58 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 8/21/2020 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | | THAN 4 FEET INTO A REQUIRED SETBACK. THE REQUIRED | | | SETBACK FOR THIS PROPERTY IS 7.5 FEET, THE GENERATOR | | | MUST BE SETBACK AT LEAST 3.5 FEET FROM THE PROPERTY | | | LINE. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-07-31 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-07-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-07-31 |
Time |
|
Sent To |
I |
|
| Notes |
| 2020-07-31 11:05:28 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 7/31/2020 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED | | | GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE | | | CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | | REQUIRED SETBACK. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | TTY: 800.955.8771 | | | E: [email protected] | | | W: WPB.ORG |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-07-02 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-07-02 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2020-07-02 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-02 09:10:28 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 7/2/2020 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | | THAN 4 FEET INTO A REQUIRED SETBACK. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN | | | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE | | | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A | | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST | | | THAT IT BE SENT TO YOU BY EMAILING [email protected] | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1443 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG |
|
|