Plan Review Details - Permit 20060507
| Plan Review Stops For Permit 20060507 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-09-04 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-09-04 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2020-09-04 10:31:29 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT STRUCTURAL DETAILS FOR THE ROOF OF THE | | | BUILDING. IF ADDITIONAL REINFORCEMENT OR MODIFICATIONS | | | ARE REQUIRED TO SUPPORT THE NEW EQUIPMENT OR PROVIDE | | | ANCHORING FOR THE ROOF STANDS SUBMIT SIGNED AND SEALED | | | DRAWINGS FROM A LICENSED DESIGN PROFESSIONAL. FBC | | | 107.2.1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-09-04 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-08-21 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-09-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-03 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-03 |
Time |
11:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-24 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-24 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2020-08-24 06:57:39 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20060507 | | | | | | CODES IN EFFECT: | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE SPEC SHEETS FOR THE CONDENSER STANDS. | | | THIS SHOULD ALSO INCLUDE THE TIE DOWN METHOD USED TO | | | SECURE THESE CONDENSER STANDS TO THE ROOF. FBC FS | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-09-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-09-04 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-24 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-24 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2020-08-24 07:00:01 | DESIGNER OF THE DRAWING MUST INCLUDE THE ADDRESS OF THE | | | BUILDING, DESIGNERS NAME, DESIGNERS SIGNATURE AND THE | | | DATE ON THE DRAWING. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
|