| 2020-07-09 16:13:26 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20060502 |
| | 7/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE CORRECTED |
| | PLANS ADDRESSING THE FOLLWING COMMENTS. |
| | |
| | 1) GAS ISOMETRIC DRAWING: |
| | A) IN ORDER TO ENSURE A SAFE OPERATING SYSTEM THE |
| | DRAWING MUST BE MODIFIED TO SHOW THE ENTIRE SYSTEM |
| | INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST |
| | REMOTE OUTLET.THE BTUH LOAD OF EACH EXISTING APPLIANCE |
| | AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON |
| | THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES. |
| | B) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM |
| | FROM THE METER TO THE MOST REMOTE OUTLET, AND ALL |
| | BRANCH LENGTH SIZES- SECTIONS G2413.4.1, G2413.4.2 & |
| | G2413.4.3. |
| | B) PROVIDE DELIVERY PRESSURE TO THE GENERATOR FROM THE |
| | OUTLET OF THE REGULATOR- SECTION G2421.1 |
| | C) CORRECT THE 576,000 BTUH LOAD LISTED FOR THE |
| | GENERATOR. THE SUBMITTED SPECS ON PAGE 3 INDICATE |
| | 375.000 BTUH FULL LOAD FOR MODEL RG032- 32KW - G2413.2 |
| | FBC RES. |
| | |
| | 2) SUBMIT SPECS FOR THE REGULATOR AT THE GENERATOR WITH |
| | MARKUPS TO INDICATE WHICH MODEL TO BE INSTALLED, INLET |
| | AND OUTLET PRESSURES, AND ORIFICE SIZE- SECTION |
| | G2421.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |