Plan Review Details - Permit 20060496
Plan Review Stops For Permit 20060496
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-29 Cont ID  
Sent By rmcphers Date 2020-07-29 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2020-07-29 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-14 Cont ID  
Sent By rmcphers Date 2020-07-14 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2020-07-14 Time 09:50 Sent To  
Notes
2020-07-14 09:58:12WIN/DOOR/SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ACCORDION SHUTTERS = THE EDGE DISTANCE SHOWN ON THE
 "SHUTTER SCHEDULE" OF 1" IS NOT ALLOWED - PLEASE SEE
 PRODUCT APPROVAL SHEET 13 OF 20 FOR THE MINIMUM EDGE
 DISTANCE GUIDE.
 2) PANEL SHUTTERS = THE MIN. EDGE DISTANCE FOR BLOCK IS
 2" PER SHEET 4 ON THE PRODUCT APPROVAL.
 3) PLEASE REVISE THE "SHUTTER ATTACHMENT SCHEDULE"

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 14:41 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 14:16 Sent To  
Notes
2020-06-16 14:41:50WINDOWS, DOORS, SHUTTERS.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 ALL PRODUCT APPROVALS PROVIDED SHOULD BE LOADED
 SEPARATELY INTO PROJECTDOX.
 1) PRODUCT APPROVAL 17-0420.12 HAS EXPIRED - PLEASE
 PROVIDE UPDATED PRODUCT APPROVAL.
 2) PLEASE FILL OUT AN "SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES OR ASSEMBLIES" FORM FOR THE
 INSTALLATION OF THE SHUTTERS.
 1. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON
 SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF
 USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 IF FORMS ARE NOT AVAILABLE ONLINE - EMAIL [email protected]
 AND ASK FOR THE FORM.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-29 Cont ID  
Sent By rmcphers Date 2020-07-29 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2020-07-22 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-14 Cont ID  
Sent By rmcphers Date 2020-07-14 Time 09:59 Rev Time 0.00
Received By rmcphers Date 2020-07-06 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-06-09 Time 11:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 14:42 Sent To  
Notes
***NONE***