Plan Review Details - Permit 20060490
Plan Review Stops For Permit 20060490
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-07-24 Cont ID  
Sent By jleahy Date 2020-07-24 Time 07:49 Rev Time 0.00
Received By jleahy Date 2020-07-24 Time 07:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-10 Cont ID  
Sent By lmarchan Date 2020-08-10 Time 08:28 Rev Time 0.00
Received By lmarchan Date 2020-08-07 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-24 Cont ID  
Sent By jleahy Date 2020-07-24 Time 07:49 Rev Time 0.00
Received By jleahy Date 2020-07-02 Time 12:40 Sent To  
Notes
2020-07-22 17:13:44CONVERTED TO DIGITAL. JG.
2020-07-02 12:41:00ROURTED TO MECH BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-17 Cont ID  
Sent By hmoser Date 2020-06-17 Time 11:39 Rev Time 0.00
Received By hmoser Date 2020-06-15 Time 11:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-08-10 Cont ID  
Sent By medwards Date 2020-08-10 Time 07:37 Rev Time 0.00
Received By medwards Date 2020-08-10 Time 07:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-07-23 Cont ID  
Sent By medwards Date 2020-07-23 Time 07:25 Rev Time 0.00
Received By medwards Date 2020-07-23 Time 07:25 Sent To  
Notes
2020-07-23 07:27:54PLEASE SEE NOTE 2 OF THE ORIGINAL REVIEWERS COMMENTS.
 YOU MUST PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By hmoser Date 2020-06-17 Time 11:12 Rev Time 0.00
Received By hmoser Date 2020-06-17 Time 14:37 Sent To I
Notes
2020-06-17 11:39:29PLAN DENIED
 1) REFER TO SECTION R303.1.2 EQUIPMENT EFFICIENCY
 RATINGS
 AHRI SHEETS REQUIRED 2017 FLORIDA ENERGY CODE
 2) REFER TO SECTION R403.7 HEATING COOLING EQUIPMENT.
 PROVIDE ENERGY CALCULATIONS AND HEAT LOADS.
 FLORIDA ENERGY CODE 2017.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
2020-06-15 14:38:02ROUTEDT TO MECHANICAL BIN