Plan Review Details - Permit 20060445
Plan Review Stops For Permit 20060445
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-20 Cont ID  
Sent By ppetty Date 2020-08-20 Time 08:29 Rev Time 0.00
Received By ppetty Date 2020-08-20 Time 08:29 Sent To M
Notes
2020-08-20 08:30:50HOODS ADDED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-02 Cont ID  
Sent By pleduc Date 2020-07-02 Time   Rev Time 0.00
Received By pleduc Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By ppetty Date 2020-06-25 Time 08:53 Rev Time 0.00
Received By ppetty Date 2020-06-25 Time 08:53 Sent To  
Notes
2020-06-25 08:57:47PLEASE SEE F/D NOTE

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-08-19 Cont ID  
Sent By pleduc Date 2020-08-19 Time   Rev Time 0.00
Received By pleduc Date 2020-08-19 Time 10:02 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-07-02 Cont ID  
Sent By pleduc Date 2020-07-02 Time   Rev Time 0.00
Received By pleduc Date 2020-07-02 Time 11:54 Sent To I
Notes
2020-07-02 11:54:57IT DOES NOT APPEAR THAT ANY CHANGES OR CORRECTIONS HAVE
 BEEN MADE NOR INDICATED ON THE RESUBMITTAL.
  
 THE BELOW COMMENTS ARE RE-ENTERED AS THEY WERE NOT
 ADDRESSED.
  
 PLEASE ENSURE THAT THE COMMENTS ARE ADDRESSED,
 CORRECTED AND CLOUDED ON THE PLAN SHEET OR PROVIDE A
 DETAILED NARRATIVE DEFENDING WHY CORRECTIONS ARE NOT
 REQUIRED, INCLUDING SPECIFIC ODE REFERNECES.
  
 *******************************************************
 *********************************
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 1 OF 3 - THERE IS NO INDICATIONS OF
 NOTIFICATION WITHIN THE KITCHEN AREAS.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE EXPLANATION.
  
  
  
 2) THERE ARE NO INDICATIONS/CLEAR INDICATORS THAT THE
 KITCHEN HOOD SYSTEMS ARE TIED INTO THE FIRE ALARM.
  
 PLEASE REVIEW AND CORRECT OF SPECIFICALLY INDICATE THE
 REQUIRED RELAYS/CONNECTIONS
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-23 Cont ID  
Sent By pleduc Date 2020-06-23 Time   Rev Time 0.00
Received By pleduc Date 2020-06-23 Time 10:49 Sent To E
Notes
2020-06-23 11:16:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWING COMMENTS ARE PROVIDED IN AN EFFORT TO
 REDUCE FALSE FIRE ALARMS WHILE REMIANING COMPLIANT WITH
 CODE.
  
 THESE COMMENTS ARE PROVIDED AS IT APPEARS TO SOME
 OVER-DESIGN INDICATED AS THIS ASSEMBLY OCCUAPNY IS
 PROTECTED THROUGHOUT WITH A COMPLETE FIRE SPRINKLER
 SYSTEM.
  
 1) SHEET 1 OF 3 - THERE ARE INDICATIONS OF PULL
 STATIONS AT EACH EXIT DOOR.
  
 PER NFPA 101
  
 12.3.4.2 INITIATION.
 12.3.4.2.1 INITIATION OF THE REQUIRED FIRE ALARM SYSTEM
 SHALL BE BY
 BOTH OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1), UNLESS
 OTHERWISE
 PERMITTED BY ONE OF THE FOLLOWING:
 (A) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC FIRE
 DETECTION SYSTEM IN ACCORDANCE WITH 9.6.2.1(2) THAT
 PROVIDES FIRE DETECTION THROUGHOUT THE BUILDING.
 (B) THE REQUIREMENT OF 12.3.4.2.1(1) SHALL NOT APPLY
 WHERE
 INITIATION IS BY MEANS OF AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.6.2.1(3) THAT
 PROVIDES FIRE DETECTION AND PROTECTION THROUGHOUT THE
 BUILDING.
 (2) WHERE AUTOMATIC SPRINKLERS ARE PROVIDED, INITIATION
 OF THE
 FIRE ALARM SYSTEM BY SPRINKLER SYSTEM WATERFLOW, EVEN
 WHERE
 MANUAL FIRE ALARM BOXES ARE PROVIDED IN ACCORDANCE WITH
 12.3.4.2.1(1)
  
 THERE IS A FIRE SPRINKLER SYSTEM THROUGHOUT THE
 BUILDING.
  
 9.6.2 SIGNAL INITIATION.
 9.6.2.1 WHERE REQUIRED BY OTHER SECTIONS OF THIS CODE,
 ACTUATION
 OF THE FIRE ALARM SYSTEM SHALL OCCUR BY ANY OR ALL OF
 THE FOLLOWING
 MEANS OF INITIATION BUT SHALL NOT BE LIMITED TO SUCH
 MEANS:
 (1) MANUAL FIRE ALARM INITIATION
 (2) AUTOMATIC DETECTION
 (3) EXTINGUISHING SYSTEM OPERATION
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 ONLY 1 MANUAL FIRE ALARM BOX IS REQUIRED, THE ONE
 LOCATED AT THE MAIN DOUBLE DOOR EXIT.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 2) SHEET 1 OF 3 - THERE ARE SMOKE DECTORS LOCATED
 THROUGHOUT THE OCCUPANCY.
  
 I DO NOT SEE THAT SMOKE DETECTION IS REQUIRED WITHIN
 THIS ASSEMBLY OCCUPANCY,
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 3) SHEET 1 OF 3 - THERE ARE INDICATION OF HEAT
 DETECTORS WITHIN THE KITCHEN AREA.
  
 I DO NOT SEE THAT HEAT DETECTION IS REQUIRED WITHIN
 THIS AREA,
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
 4) SHEET 1 & 2 OF 3 - THERE IS A SYMBOL OF A SQUARE
 WITH AN M IN THE CENTER THAT IS NOT INCLUDED LEGEND.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET 1 OF 3 - THERE DOES NOT APPEAR TO BE A
 NOFICIATION DEVICE WITHIN THE SMALLER BATHROOM,ADA,
 WOMENS RESTROOM. IT DOES APPEAR IN THE MENS.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 6) SHEET 2 OF 3 - THERE IS AN INDICATION OF THE FACP
 LOCATED IN ELECTRICAL ROOM; HOWEVER, SHEET 1 OF 3 ONLY
 INDICATES THE POWER SUPPLY.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-21 Cont ID  
Sent By pvalenti Date 2020-08-21 Time 16:23 Rev Time 0.00
Received By pvalenti Date   Time   Sent To  
Notes
2020-08-12 12:38:34ROUTED TO FIRE BIN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-17 Cont ID  
Sent By rsklarew Date 2020-07-17 Time 11:58 Rev Time 0.00
Received By rsklarew Date 2020-06-28 Time 09:28 Sent To  
Notes
2020-06-25 17:07:30ROUTED TO FIRE BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-25 Cont ID  
Sent By ppetty Date 2020-06-25 Time 08:58 Rev Time 0.00
Received By ppetty Date 2020-06-18 Time 15:35 Sent To  
Notes
2020-06-18 15:35:53ROUTED TO FIRE BIN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-08-21 Cont ID  
Sent By pvalenti Date 2020-08-21 Time 16:21 Rev Time 0.00
Received By pvalenti Date 2020-08-21 Time 16:08 Sent To  
Notes
2020-08-21 16:22:51PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW NOT REQUIRED:
  
 NOTHING NEW SHOWN ON PLANS FOR MECHANICAL.
2020-08-20 08:28:01HOODS ADDED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-06-25 Cont ID  
Sent By ppetty Date 2020-06-25 Time 09:00 Rev Time 0.00
Received By ppetty Date 2020-06-25 Time 09:00 Sent To  
Notes
***NONE***