Plan Review Details - Permit 20060420
Plan Review Stops For Permit 20060420
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By pleduc Date 2020-06-10 Time   Rev Time 0.00
Received By pleduc Date 2020-06-10 Time 14:04 Sent To  
Notes
2020-06-10 14:27:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN SHEET INDICATES THE NEW FYER DIRECTLY ON
 THE EDGE OF THE EXISTING HOOD ABOVE WITH NO OVERHANG.
  
 PER NFPA 96
  
 5.2 HOOD SIZE. HOODS SHALL BE SIZED AND CONFIGURED TO
 PROVIDE
 FOR THE CAPTURE AND REMOVAL OF GREASE-LADEN VAPORS.
 (SEE 8.2.2.)
  
 8.2.2 AIR VOLUME.
 8.2.2.1 EXHAUST AIR VOLUMES FOR HOODS SHALL BE OF A
 SUFFICIENT
 LEVEL TO PROVIDE FOR CAPTURE AND REMOVAL OF
 GREASE-LADEN COOKING
 VAPORS.8.2.2.2* TEST DATA, PERFORMANCE TESTS ACCEPTABLE
 TO THE AUTHORITY
 HAVING JURISDICTION, OR BOTH SHALL BE DISPLAYED,
 PROVIDED ON
 REQUEST, OR BOTH.
  
 A PREVIOUS HOOD PERMIT INDICATED THIS AS A UL 710,
 WHICH REQUIRES A MINIMUM OF 6".
  
 PLEASE PROVIDE THE REQUIRED OVERHANG AND THAT THIS
 INSTALL IS WITHIN THAT REQUIRERMENT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 14:24 Rev Time 0.00
Received By shill Date 2020-06-09 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-23 Cont ID  
Sent By medwards Date 2020-06-23 Time 14:04 Rev Time 0.00
Received By medwards Date 2020-06-23 Time 13:46 Sent To  
Notes
2020-06-23 14:05:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060420
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECS FOR NEW FRYER SHOWING THE BTU?S
 REQUIRED. FBC FS 107.2.1
  
 2) PLEASE PROVIDE A NEW GAS LINE DIAGRAM FOR THE
 ADDITION OF THIS NEW APPLIANCE. THIS MUST INCLUDE ALL
 EXISTING APPLIANCES ALONG WITH THE BTU?S OF EACH. FBC
 FS 107.2.1
  
 3) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THE
 BUILDING, SHOWING AIR BALANCE AND COMBUSTION AIR
 REQUIREMENTS FOR THE ADDITIONAL APPLIANCE. FBC FS
 107.2.1
  
 4) PLEASE PRODUCE SPECS FOR THE EXISTING HOOD. FBC FS
 107.2.1
  
 5) PLEASE SHOW CALCULATIONS FOR MAKEUP AIR AND HOOD
 EXHAUST FOR THIS ADDITIONAL APPLIANCE. FBC FS 107.2.1
  
 6) PLEASE SEE FIRE REVIEWER NOTES.
  
 NOTE: THIS PROJECT WILL REQUIRE A MECHANICAL AND GAS
 SUB PERMIT.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-23 Cont ID  
Sent By medwards Date 2020-06-23 Time 14:06 Rev Time 0.00
Received By medwards Date 2020-06-23 Time 14:05 Sent To  
Notes
2020-06-23 14:07:33PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy