| 2020-06-12 11:48:08 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL THE |
| | BUILDING EXPOSURE FOR THIS HOUSE IS EXPOSURE "D". BASED |
| | ON TABLE R301.2(4) FBC-RESIDENTIAL THE DESIGN PRESSURES |
| | ARE -45.86 PSF AND +40.572 PSF. FLORIDA PRODUCT |
| | APPROVAL FL16107-R10 SUBMITTED IS FOR A GARAGE DOOR |
| | WITH THE DESIGN PRESSURES OF -44.0 PSF AND +38.0 PSF. |
| | NEED TO PROVIDE ANOTHER PRODUCT APPROVAL THAT MEETS THE |
| | DESIGN PRESSURES CALCULATED FROM TABLE R301.2(4) |
| | FBC-RESIDENTIAL OR PROVIDE SIGNED AND SEALED |
| | CALCULATIONS SHOWING THAT THE GARAGE DOOR PRODUCT |
| | APPROVAL SUBMITTED MEETS THE DESIGN PRESSURES FOR A |
| | BUILDING IN EXPOSURE "D". |
| | |
| | 2- CONTRACT SUBMITTED INDICATES THAT THE CUSTOMER NEEDS |
| | TO INSTALL CODE APPROVED OUTLET. AN ELECTRICAL |
| | SUBPERMIT IS REQUIRED IF THIS IS A NEW INSTALLATION. |
| | SEC. 105.1 CITY AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |