| Plan Review Stops For Permit 20060319 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-07-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-07-24 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-07-24 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2020-07-24 09:11:08 | CONTRACTOR DIDN'T SPECIFY TYPE OF EXISTING WINDOWS AS | | | REQUESTED BUT BASED ON PAPA'S STREET VIEW, IT LOOKS | | | LIKE THE EXISTING BEDROOM WINDOWS (G AND H) ARE SINGLE | | | HUNG. REPLACING THEM FOR SINGLE HUNG. JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-07-09 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-07-09 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2020-07-09 17:05:12 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | WINDOW REPLACEMENT | | | 1-PROVIDE FLOOR PLAN OR SKETCH IDENTIFYING THE ROOMS | | | WHERE WINDOWS ARE GOING TO BE REPLACED. FOR EXAMPLE: | | | BEDROOM, LIVING AREA, ETC. THIS IS REQUIRED TO IDENTIFY | | | THE BEDROOMS AND VERIFY COMPLIANCE WITH THE EGRESS | | | REQUIREMENTS. SEE COMMENT #2 BELOW. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2-SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND | | | TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE | | | EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING | | | BUILDING. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-06-23 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-06-23 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2020-06-23 16:22:25 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK | | | SHALL COMPLY WITH THE MATERIALS AND METHODS | | | REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | WINDOW REPLACEMENT | | | 1-PROVIDE FLOOR PLAN OR SKETCH IDENTIFYING THE ROOMS | | | WHERE WINDOWS ARE GOING TO BE REPLACED. FOR EXAMPLE: | | | BEDROOM, LIVING AREA, ETC. THIS ES REQUIRED TO IDENTIFY | | | TH BEDROOMS AND VERIFY COMPLIANCE WITH THE EGRESS | | | REQUIREMENTS. SEE COMMENT #2 BELOW. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2-SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND | | | TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE | | | EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING | | | BUILDING. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-07-23 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-07-23 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-07-23 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2020-07-23 09:30:37 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | | CONDITION(S): | | | | | | 1. ALL STREET FACING GLASS (E AND F) SHALL HAVE CLEAR | | | GLASS ONLY. | | | 2. ALL NON-STREET FACING GLASS (A, B, C, D, G, H, I, J) | | | SHALL HAVE PGT?S LIGHTEST GREY TINT. | | | 3. ALL WINDOWS SHALL MATCH THE EXISTING LITE-PATTERN | | | CONFIGURATION WITH AN EXTERNAL DIMENSIONAL PYRAMID | | | MUNTIN. | | | 4. WINDOW E SHALL HAVE THE APPEARANCE OF A CENTER FIXED | | | WINDOW AND FLANKING 8-LITE PATTERN TO RECREATE THE | | | EXISTING WINDOW APPEARANCE. | | | 5. ALL WINDOWS SHALL HAVE A WHITE EXTERIOR FRAME. | | | 6. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | | WINDOW FRAME OPENING AND MATCH THE INSET/LOCATION/DEPTH | | | OF THE ORIGINAL WINDOWS WITHIN THE FRAME OPENING. | | | | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-07-06 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-07-06 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-07-06 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2020-07-06 10:28:03 | THE PERMIT HAS FAILED PENDING CONFIRMATION OF THESE | | | PROPOSED CONDITIONS. | | | | | | 1. ALL STREET FACING GLASS (E AND F) SHALL HAVE CLEAR | | | GLASS ONLY. | | | 2. ALL NON-STREET FACING GLASS (A, B, C, D, G, H, I, J) | | | SHALL HAVE CLEAR GLASS OR CLASS CLEAR WITH LOW-E | | | COATING. | | | 3. ALL WINDOWS SHALL MATCH THE EXISTING LITE-PATTERN | | | CONFIGURATION WITH AN EXTERNAL DIMENSIONAL PYRAMID | | | MUNTIN. | | | 4. WINDOW E SHALL HAVE THE APPEARANCE OF A CENTER FIXED | | | WINDOW AND FLANKING 8-LITE PATTERN TO RECREATE THE | | | EXISTING WINDOW APPEARANCE. | | | 5. ALL WINDOWS SHALL HAVE A WHITE EXTERIOR FRAME. | | | 6. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | | WINDOW FRAME OPENING AND MATCH THE INSET/LOCATION/DEPTH | | | OF THE ORIGINAL WINDOWS WITHIN THE FRAME OPENING. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-06-15 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2020-06-15 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2020-06-09 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2020-06-15 10:42:22 | THE PERMIT HAS FAILED PENDING CONFIRMATION OF THESE | | | PROPOSED CONDITIONS. PLEASE REPLY TO THE EMAIL THAT WAS | | | SENT ON TUESDAY, JUNE 9TH AT 3:15 PM. | | | | | | 1. ALL STREET FACING GLASS (E AND F) SHALL HAVE CLEAR | | | GLASS ONLY. | | | 2. ALL NON-STREET FACING GLASS (A, B, C, D, G, H, I, J) | | | SHALL HAVE CLEAR GLASS OR CLASS CLEAR WITH LOW-E | | | COATING. | | | 3. ALL WINDOWS SHALL MATCH THE EXISTING LITE-PATTERN | | | CONFIGURATION WITH AN EXTERNAL DIMENSIONAL PYRAMID | | | MUNTIN. | | | 4. WINDOW E SHALL HAVE THE APPEARANCE OF A CENTER FIXED | | | WINDOW AND FLANKING 8-LITE PATTERN TO RECREATE THE | | | EXISTING WINDOW APPEARANCE. | | | 5. ALL WINDOWS SHALL HAVE A WHITE EXTERIOR FRAME. | | | 6. ALL WINDOWS SHALL BE SIZED TO FIT THE ORIGINAL | | | WINDOW FRAME OPENING AND MATCH THE INSET/LOCATION/DEPTH | | | OF THE ORIGINAL WINDOWS WITHIN THE FRAME OPENING. | | | | | | AARON BORNGRABER | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-07-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-07-24 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-07-22 |
Time |
13:54 |
Sent To |
I |
|
| Notes |
| 2020-07-22 13:54:58 | ROUTED TO ZONING BIN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-07-09 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-07-09 |
Time |
17:05 |
Sent To |
I |
|
| Notes |
| 2020-06-25 17:10:40 | ROUTED TO HISTORIC BIN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-06-23 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-06-09 |
Time |
11:22 |
Sent To |
I |
|
| Notes |
| 2020-06-15 14:39:01 | ROUTED TO BLDG. MISC 1 | | 2020-06-09 11:22:23 | ROUTED TO HISTORIC |
|
|