Plan Review Details - Permit 20060313
Plan Review Stops For Permit 20060313
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2020-07-22 Time 13:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 14:26 Sent To  
Notes
2020-06-25 14:57:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PREFAB GENERATOR PAD ENGINEERING IS FOR THE 32
 KW GENERAC GENERATOR. THE PERMIT APPLICATION IS FOR A
 22KW GENERATOR. SUBMIT MATCHING DOCUMENTS. FBC 107
  
 2) THE GENERATOR PAD ENGINEERING IS REQUIRED TO BE
 DIGITALLY SIGNED BY THE ENGINEER. FS 471 AND FAC 61G15

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-22 Cont ID  
Sent By fgiaquin Date 2020-07-22 Time 22:01 Rev Time 0.00
Received By fgiaquin Date 2020-07-22 Time 21:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-07-06 Cont ID  
Sent By fgiaquin Date 2020-07-06 Time 18:14 Rev Time 0.00
Received By fgiaquin Date 2020-07-06 Time 17:57 Sent To  
Notes
2020-07-06 18:15:36PLAN AND LOAD CALC MUST BE SIGNED BY QUALIFIER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-22 Cont ID  
Sent By fgiaquin Date 2020-07-22 Time 22:01 Rev Time 0.00
Received By fgiaquin Date 2020-07-07 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-07-06 Cont ID  
Sent By fgiaquin Date 2020-07-06 Time 18:15 Rev Time 0.00
Received By fgiaquin Date 2020-06-15 Time 14:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-22 Cont ID  
Sent By rmcdouga Date 2020-07-22 Time 13:05 Rev Time 0.00
Received By rmcdouga Date 2020-07-22 Time 13:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-25 Cont ID  
Sent By rmcdouga Date 2020-06-25 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2020-06-25 Time 14:26 Sent To  
Notes
2020-06-25 14:29:04THE ELECTRONICALLY SUBMITTED GENERATOR PAD DRAWINGS ARE
 REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE. FS
 471 & FAC 61G15

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By kalexand Date 2020-06-29 Time   Rev Time  
Received By   Date 2020-06-29 Time   Sent To I
Notes
***NONE***