Plan Review Details - Permit 20060233
Plan Review Stops For Permit 20060233
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-27 Cont ID  
Sent By lcrespo Date 2020-07-27 Time 12:22 Rev Time 0.00
Received By lcrespo Date 2020-07-13 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-07-06 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-25 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-24 Cont ID  
Sent By tklarge Date 2020-06-24 Time 13:52 Rev Time 0.00
Received By tklarge Date 2020-06-11 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-27 Cont ID  
Sent By lcrespo Date 2020-07-27 Time 12:22 Rev Time 0.00
Received By lcrespo Date 2020-07-27 Time 12:22 Sent To  
Notes
2020-07-27 12:22:447/27/20 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/IRRIGATION)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM TO 7:30 / 2:00 PM TO 5:00 PM
 EMAIL: [email protected] CELL: 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 08:50 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 07:30 Sent To  
Notes
2020-07-06 08:50:11PLUMBING 2ND REVIEW COMMENTS: 20060233
 1) PLAN SHALL BE DIGITALLY SIGNED AND SEALED PER
 FLORIDA ADMIN CODE
 2) PLAN ONLY SHOWS MAIN LOOP. PLEASE INCLUDE ZONE
 VALVES AND BRANCH LINES. COMPLETE IRRIGATION SYSTEM
 MUST BE DRAWN ON PLANS. FBC 107.2.1
 3) ADD NOTE PIPING FROM THE WATER METER UP TO AND
 INCLUDING THE RPZ BACKFLOW DEVICE MUST BE MIN TYPE L
 COPPER, PERMITTED, AND INSTALLED ONLY BY LICENSED
 PLUMBING CONTRACTOR. PER 2017 W.P.B CROSS CONNECTION
 MANUAL AND F.S 489
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 (CAP GOVERNMENT)
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-06-24 Cont ID  
Sent By tklarge Date 2020-06-24 Time 13:52 Rev Time 0.00
Received By tklarge Date 2020-06-24 Time 13:31 Sent To  
Notes
2020-06-24 13:44:401) PLANS HAVE BEEN SUBMITTED BUT THERE IS NO IRRIGATION
 SYSTEM SHOWN ON THE PLANS. WHY WERE THESE PLANS
 SUBMITTED? CLARIFY
 2) SHOW THE LOCATION OF THE CONTROLLER AND RAIN SENSOR
 ON THE PLANS.
 3) CLEARLY SHOW THE WATER SOURCE FOR THE IRRIGATION
 SYSTEM ON THE PLANS. IF CONNECTED TO CITY WATER, A
 BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 IRRIGATION SYSTEM. A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE BACKFLOW DEVICE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-06-24 Cont ID  
Sent By tklarge Date 2020-06-24 Time 13:52 Rev Time 0.00
Received By tklarge Date 2020-06-24 Time 13:52 Sent To  
Notes
***NONE***