| 2020-07-01 15:28:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF THE CHANGES/REVISIONS ON |
| | THE SUBMITTED PLANS NOR ANY NARRATIVE EXPLAINING THE |
| | CHANGES. |
| | |
| | PER NFPA 1 |
| | |
| | 1.14 PLAN REVIEW. |
| | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| | |
| | PLEASE PROVIDE CLOUDED CHANGES ON THE PLAN SHEETS OR A |
| | DETAILED NARRATIVE FOR EACH CHANGE. |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | THE FOLLOWING COMMENTS WERE FROM THE ORIGINAL REVIEW |
| | THAT HAVE NOT BEEN ADDRESSED WITH ANY KIND OF CLARITY. |
| | |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) IT APPEARS THAT THERE IS NO RE-ENTRY WITHIN THE |
| | STAIRWELLS. |
| | |
| | PER NFPA 101 CH 28 AND CH 7, |
| | |
| | 28.2.2.2 DOORS. |
| | 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| | 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR |
| | 28.2.2.2.2.4. |
| | 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE |
| | LOCKED |
| | AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| | 28.2.2.2.2.2 DELAYED-EGRESS LOCKS COMPLYING WITH |
| | 7.2.1.6.1 SHALL |
| | BE PERMITTED. |
| | 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING |
| | WITH |
| | 7.2.1.6.2 SHALL BE PERMITTED. |
| | |
| | 7.2.1.5.8* EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE |
| | SERVING MORE |
| | THAN FOUR STORIES, UNLESS PERMITTED BY 7.2.1.5.8.2, |
| | SHALL MEET ONE |
| | OF THE FOLLOWING CONDITIONS: |
| | (1) RE-ENTRY FROM THE STAIR ENCLOSURE TO THE INTERIOR |
| | OF THE |
| | BUILDING SHALL BE PROVIDED. |
| | (2) AN AUTOMATIC RELEASE THAT IS ACTUATED WITH THE |
| | INITIATION OF |
| | THE BUILDING FIRE ALARM SYSTEM SHALL BE PROVIDED TO |
| | UNLOCK ALL |
| | STAIR ENCLOSURE DOOR ASSEMBLIES TO ALLOW RE-ENTRY. |
| | (3) SELECTED RE-ENTRY SHALL BE PROVIDED IN ACCORDANCE |
| | WITH |
| | 7.2.1.5.8.1. |
| | 7.2.1.5.8.1 DOOR ASSEMBLIES ON STAIR ENCLOSURES SHALL |
| | BE PERMITTED |
| | TO BE EQUIPPED WITH HARDWARE THAT PREVENTS RE-ENTRY |
| | INTO THE |
| | INTERIOR OF THE BUILDING, PROVIDED THAT ALL OF THE |
| | FOLLOWING CRITERIA |
| | ARE MET: |
| | (1) THERE SHALL BE NOT LESS THAN TWO LEVELS WHERE IT IS |
| | POSSIBLE TO |
| | LEAVE THE STAIR ENCLOSURE TO ACCESS ANOTHER EXIT. |
| | (2) THERE SHALL BE NOT MORE THAN FOUR STORIES |
| | INTERVENING |
| | BETWEEN STORIES WHERE IT IS POSSIBLE TO LEAVE THE STAIR |
| | ENCLOSURE TO ACCESS ANOTHER EXIT. |
| | (3) RE-ENTRY SHALL BE POSSIBLE ON THE TOP STORY OR |
| | NEXT-TO-TOP |
| | STORY SERVED BY THE STAIR ENCLOSURE, AND SUCH STORY |
| | SHALL ALLOW |
| | ACCESS TO ANOTHER EXIT. |
| | (4) DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE |
| | IDENTIFIED AS SUCH |
| | ON THE STAIR SIDE OF THE DOOR LEAF. |
| | (5) DOOR ASSEMBLIES NOT ALLOWING RE-ENTRY SHALL BE |
| | PROVIDED WITH |
| | A SIGN ON THE STAIR SIDE INDICATING THE LOCATION OF THE |
| | NEAREST |
| | DOOR OPENING, IN EACH DIRECTION OF TRAVEL, THAT ALLOWS |
| | RE-ENTRY |
| | OR EXIT. |
| | |
| | PLEASE REVIEW, CORRECT AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 2) STAIRS S 101 - THER APPEAARS TO BE ACCESS CONRTOL |
| | LIMITING THE EXIT FROM WITHIN THE STAIRWELL WITHOUT A |
| | CARDER READER. |
| | |
| | THOUGH THIS STAIR MAY NOT BE A REQUIRED EGRESS IF A |
| | PERSON IS ALLOWED TO ENTER IT, FROM ANY FLOOR, HOW |
| | WOULD THEY BE ABLE TO EXIT IT AT ANY FLOOR? |
| | |
| | 28.2.2.2.2.3 ACCESS-CONTROLLED EGRESS DOORS COMPLYING |
| | WITH |
| | 7.2.1.6.2 SHALL BE PERMITTED. |
| | |
| | 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES. |
| | WHERE |
| | PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN |
| | THE |
| | MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH |
| | ELECTRICAL |
| | LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL |
| | OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO |
| | UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON |
| | DETECTION |
| | OF AN APPROACHING OCCUPANT. |
| | (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE |
| | DIRECTION OF EGRESS |
| | UPON LOSS OF POWER TO THE SENSOR OR TO THE PART OF THE |
| | ACCESS |
| | CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES. |
| | (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF |
| | EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL |
| | OF |
| | THE FOLLOWING CRITERIA: |
| | (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE |
| | EGRESS |
| | SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) VERTICALLY |
| | ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) OF THE |
| | SECURED DOOR OPENINGS. |
| | (B) THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE |
| | AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS: |
| | PUSH TO EXIT. |
| | (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN |
| | DIRECT INTERRUPTION OF POWER TO THE LOCK ? INDEPENDENT |
| | OF THE LOCKING SYSTEM ELECTRONICS ? AND THE LOCK SHALL |
| | REMAIN UNLOCKED FOR NOT LESS THAN 30 SECONDS. |
| | (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE |
| | SIGNALING SYSTEM, IF |
| | PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES IN |
| | THE |
| | DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL REMAIN |
| | UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS |
| | BEEN |
| | MANUALLY RESET. |
| | (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT |
| | ACTIVATE THE |
| | BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN |
| | 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR |
| | LEAVES. |
| | (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| | FIRE |
| | DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| | UNLOCK THE |
| | DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR |
| | LEAVES |
| | SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE |
| | SIGNALING |
| | SYSTEM HAS BEEN MANUALLY RESET. |
| | (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, |
| | OTHER THAN |
| | EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE |
| | PROVIDED |
| | WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |