Plan Review Details - Permit 20060036
Plan Review Stops For Permit 20060036
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-06-29 Cont ID  
Sent By sathomas Date 2020-06-29 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-06-29 Time 00:00 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By sathomas Date 2020-06-10 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-06-10 Time 00:00 Sent To M
Notes
2020-06-10 13:50:121. NO ADDRESS PROVIDED IN THE PLAN TITLE BLOCK
 INFORMATION.
 2. PDF 5 GIVES SPECIFICATIONS OF HOOD SUPPRESSION
 SYSTEM TO BE INSTALLED, IF NOT BY OTHERS:
 A. PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR ALL
 COMPONENTS (I.E. NOZZLES, FUSIBLE LINKS, CANISTERS,
 ETC.)
 B. PLEASE PROVIDE LAYOUT OF HOOD SYSTEM WITH APPLICABLE
 APPLIANCE DETAIL TO BE INSTALLED.
 3. PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL
 BE LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
 4. DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
 5.ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY
 WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 S.THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-13 Cont ID  
Sent By lmarchan Date 2020-07-13 Time 15:38 Rev Time 0.00
Received By lmarchan Date 2020-07-10 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-10 Cont ID  
Sent By lmarchan Date 2020-07-10 Time 11:40 Rev Time 0.00
Received By lmarchan Date 2020-06-23 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-06-17 Cont ID  
Sent By lmarchan Date 2020-06-17 Time 16:41 Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-07-13 Cont ID  
Sent By medwards Date 2020-07-13 Time 14:33 Rev Time 0.00
Received By medwards Date 2020-07-13 Time 14:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 11:21 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 10:35 Sent To  
Notes
2020-07-10 11:23:07APPROVED AS NOTED:
  
 MAU-1 AND EF-1 MUST MEET FBC M 304.11- GUARDS SHALL BE
 PROVIDED WHERE VARIOUS COMPONENTS THAT REQUIRE SERVICE
 ARE LOCATED WITHIN 10' OF A ROOF EDGE.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By medwards Date 2020-06-15 Time 13:46 Rev Time 0.00
Received By medwards Date 2020-06-15 Time 12:11 Sent To  
Notes
2020-06-15 13:47:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20060036
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE GREASE DUCT DRAWINGS FOR THIS
 PROJECT; INCLUDE LENGTH, SLOPE, CLEANOUTS, TERMINATION
 LOCATIONS THAT MEET EXHAUST CLEARANCES. ALSO SHOW
 DETAIL DRAWINGS OF CONNECTION TO THE HOOD AND THE
 TERMINATION AT ROOF. FBC FS 107.2.1
  
 2) PLEASE PROVIDE A FLOOR PLAN LAYOUT SHOWING THE HOOD
 AND MAKE UP AIR LOCATIONS AND APPLIANCES UNDER THE
 HOOD. FBC FS 107.2.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-13 Cont ID  
Sent By medwards Date 2020-07-13 Time 14:47 Rev Time 0.00
Received By medwards Date 2020-07-13 Time 14:34 Sent To  
Notes
2020-07-13 14:58:31APPROVED WITH NOTE PREVISO QUALIFIER MUST PRINT AND
 SIGN THEIR NAME ON EACH SHEET OF DRAWINGS. FBC FS
 471.025
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-10 Cont ID  
Sent By medwards Date 2020-07-10 Time 11:24 Rev Time 0.00
Received By medwards Date 2020-07-10 Time 11:23 Sent To  
Notes
2020-07-10 11:26:06ALL DRAWINGS MUST BE SIGNED AND SEALED BY THE DESIGNER.
 IF SUBMITTED DIGITALLY THEY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE DESIGNER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  