| 2020-06-10 09:27:32 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20060019 |
| | ADD: 400 CLEMATIS ST. / CVS |
| | CONT: OAK CONSTRUCTION |
| | TEL: 954-583-9943 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 10TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) ENGINEERING SHEET FSI BY SHAWN R. ANDERSON IS NOT |
| | DIGITALLY SIGNED AND SEALED. FLORIDA ADMINISTRATIVE |
| | CODE 61G15-23.005 (3)(C) A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| | SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND |
| | SEALED ENGIN20040980EERING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) FSI SHEET ENGINEERED CALCULATIONS HAVE A INTERNAL |
| | PRESSURE COEFFICIENT +/- 0.18 (ENCLOSED). THIS IS ON |
| | THE EXTERNAL PORTION OF THE BUILDING, EXTERNAL. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) THE ADDITIONAL SCREEN LOADING TO THE ROOF TOP A/C |
| | STAND WOULD NEED TO BE CALCULATED TO THE EXISTING |
| | LOADING OF THE ROOF TOP A/C COMPRESSORS. PLEASE |
| | IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE |
| | AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS, |
| | CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE |
| | STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN |
| | PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES |
| | MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE |
| | ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |